Variable Name: Setpoint_highCutOff
Variable ID: 0x4323
Variable Label: Tight shut [End Position 100%]
Variable Help: The shut-off value 100% is a percentage of the operating range (with one decimal place) from which the 100% position is driven to Once the specified position limit value is reached, the actuator moves into the 100% mechanical end position. Input value: 80.0 ... 99.9 Factory setting: OFF In the 100% end position, it continues to be adjusted to the position setpoint. When a value is entered, the valve is moved into the mechanical 100% end position in control mode as a result of full evacuation or ventilation. Settings for Autoadjust: Rotary actuators = 99 When the limit value is reached, the actuator is fully ventilated. Linear actuators = 100 Controlling continues in the 100% position.
Variable Handling: R/W
Variable Class: Correction
Variable Size: 4
Variable DataType: Float
Variable Display Format: |en|5.1f
Variable Edit Format: |en|5.1f
Variable Unit:
Variable Max: 100
Variable Min: 55
Variable Read Command List
None
Variable Write Command List
None