Loading…

Variable Name: PRM_2552

Variable ID: 0x423A

Variable Label: Reaction

Variable Help: Sets the action of the actuator if the setpoint value does not lie in the range 3.0...22 mA, or the fieldbus communication fails for a longer duration than specified with the parameter 'Breakdown delay'.

Variable Handling: R/W

Variable Class: Device

Variable Size: 2

Variable DataType: Enum

Variable Enum Value Variable Enum Text
0x0000 Act. run to fail safe
0x0001 Stop actuator
0x0002 Disabled

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
160 443F cmd160_read_prm

Variable Write Command List

Command Number Command ID Command Name
161 4440 cmd161_write_prm