Variable Name: PZD_1130
Variable ID: 0x436C
Variable Label: Configuration invalid
Variable Help: One or more of the following parameter settings are invalid: - The device key of the electronic name plate is invalid. - The torques specified on the device key are implausible. - The parameterized tripping torque OPEN exceeds the maximum input torque OPEN for the valve - The parameterized tripping torque CLOSE exceeds the maximum input torque CLOSE for the valve - The parameterized tripping torque CLOSE / OPEN exceeds the configured maximum input torque for gear / thrust unit. - In case of a Profibus the redundancy concept has been configured via DPV2 for the redundancy concept, although the required DPV2 functionality hasn't been enabled on the device key.
Variable Handling: R/W
Variable Class: Diagnostic
Variable Size: 1
Variable DataType: Unsigned
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
162 | 4441 | cmd162_read_pzd |
Variable Write Command List
None