Variable Name: PZD_1142
Variable ID: 0x4376
Variable Label: Systemtesterror
Variable Help: During self-examination of the Hard.- and Software the contro unitl has detected an error and then performed a system reset. - The error indication can reset via slot 1, index 240 from REMOTE with a Profibus interface. The error type can read over the acyclic services 'System test error code' from slot 1, index 195. - The error message can LOCAL using the function System > Reset, or by an off-on switch cycle reset. The error type can be retrieved in local menu under the actual values / diagnosis. - This message is important for safety-related systems when the actuator must drive to a safe position due an pending error.
Variable Handling: R/W
Variable Class: Diagnostic
Variable Size: 1
Variable DataType: Unsigned
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
162 | 4441 | cmd162_read_pzd |
Variable Write Command List
None