Variable Name: var_ds_eSwitchFunction

Variable ID: 0x41CC

Variable Label: Switch Function

Variable Help: Switch Function You can specify whether the limit switch is used as a High Alarm or as a Low Alarm. The switching direction affects the fail-safe function of the digital output (open collector). To output the alarm as a signal via the open collector, you have to set "Digital Out Function" in the I/O Setup menu to LS ALARM. You have the following setting options: MAX The alarm is triggered when exceeding the switching threshold. MIN The alarm is triggered when falling below the switching threshold MAX + BUILD UP The alarm is triggered if the switching threshold is exceeded (High Alarm). In addition, monitoring is performed which triggers an alarm if wall deposits 1 is detected. Prerequisite for correct function is that both the count rate for empty and the count rate for full was measured. During the measurement of the empty value it must be ensured that no build-up occurs.

Variable Handling: R

Variable Class: Correction

Variable Size: 1

Variable DataType: Enum

Variable Enum Value Variable Enum Text
0x0000 MAX
0x0001 MAX + BUILD UP
0x0002 MIN

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
215 422E cmd_rd_meas_settings

Variable Write Command List