名称 | ID | 标签 | 描述 | 类型 | 访问 | 分类 |
---|---|---|---|---|---|---|
autotest_min_value | 404D | AT/Min(0-59)= | 读/写 | 无符号 | 8 | |
caution_setpoint_value | 404E | SetPt= | Gas concentration level used to detect alarm condition (also changes ResPt). | 读/写 | 浮点 | 1024 |
caution_respoint_value | 404F | ResPt= | Gas concentration level used to clear alarm condition. For high/low alarms, must be at or below/above SetPt. | 读/写 | 浮点 | 1024 |
caution_setdelay_value | 4050 | SetDly= | Time delay between alarm detection and indication. | 读/写 | 无符号 | 32 |
caution_resdelay_value | 4051 | ResDly= | Time delay after alarm condition subsides before clearing indication. | 读/写 | 无符号 | 1024 |
caution_active_value | 4053 | Active= | Selects the option for activating the alarm above or below the set point, or disables it. | 读/写 | 枚举 | 1024 |
caution_howreset_value | 4052 | How Reset= | Selects the option for resetting the alarm manually, or automatically. | 读/写 | 枚举 | 1024 |
caution_faultgoto_value | 4054 | Fault Goto= | Selects the alarm option during a fault condition as Hold, Set, or Clear. | 读/写 | 枚举 | 1024 |
warning_setpoint_value | 4055 | SetPt= | Gas concentration level used to detect alarm condition (also changes ResPt). | 读/写 | 浮点 | 1024 |
warning_respoint_value | 4056 | ResPt= | Gas concentration level used to clear alarm condition. For high/low alarms, must be at or below/above SetPt. | 读/写 | 浮点 | 1024 |
名称 | ID | 标签 | 描述 | 类型 | 访问 | 分类 |