Name ID Label Description Type Access Class
PV_Unit 4021 PV unit Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit R/W Enum 32
RJ_Max_Indicator 403F Max RJ value Shows the maximum RJ value. R Float 34
RJ_Min_Indicator 4040 Min RJ value Shows the minimum RJ value. R Float 34
Extended_Functions 4030 Drift alert mode Enables the seneor drift monitioring Alarm: The 'Caution' icon becomes active on the display. The device switches to error signal. Warning: The 'Caution' icon becomes active on the display. A warning is transmitted via the HART protocol. R/W Enum 2048
Drift_Underusage 4074 Drift mode Higher: Warning or alarm is activated in case of exceedance of chosen deviation value. Lower: Warning or alarm is activated in case of under-usage of chosen deviation. R/W Enum 2048
Drift_Alert_Value 4031 Drift alert value Define the deviation set point for before chosen warning or alarm. R/W Float 2048
Alarm_Ambient_Temp 400F Ambient alert Activate the ambient temperature alarm. If the parameter OFF is selected only a warning is issued on exceeding the specification. If ON is selected then an alarm is initiated when this value is exceeded. R/W Enum 2048
Filter_50_60_Hz 4033 Mains filter Select power filter, dependent on matching frequency of individual power networks. R/W Enum 2048
Corrosion_Detection 4032 Corros. detection Switch corrosion monitor on or off. R/W Enum 2048
Failure_Tolerance 4068 Alarmhysteresis Hysteresis switch for the analog output in case of alarm. Possibilities are off, 2 seconds or 5 seconds that analog output freezes in case of alarm. R/W Enum 2048