Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
Two_Wire_Comp_1 | 4029 | 2-wire comp. S2 | Correction value for compensation for the cable resistance when using 2 wire RTDs. 0 Ohm to 30 Ohm can be set up. | R/W | Float | 2048 |
Bias_1 | 402A | Offset sensor 2 | Additional calibration of the input signal in order to offset measurement deviations due to the installation or to compensate any sensor drift. An offset of -10 to +10 K (-18 F to 18 F) can be set up. | R/W | Float | 2048 |
Unit_1 | 400B | Measuring unit S2 | Display of sensor 2 engineering units. It can only be changed, if PV=SV1 is adjusted. | R/W | Enum | 32 |
SV2_Serial_No | 402B | Serial no. S2 | Input of sensor 2 serial number. (12 characters). | R/W | PackedAscii | 2048 |
SV2_Coeff_x0 | 4082 | Coefficient X0 | X0 Coefficient for a user defined linearisation. The linearisation is done by a polynom of fourth degree. | R/W | Float | 2048 |
SV2_Coeff_x1 | 4083 | Coefficient X1 | X1 Coefficient for a user defined linearisation. The linearisation is done by a polynom of fourth degree. | R/W | Float | 2048 |
SV2_Coeff_x2 | 4084 | Coefficient X2 | X2 Coefficient for a user defined linearisation. The linearisation is done by a polynom of fourth degree. | R/W | Float | 2048 |
SV2_Coeff_x3 | 4085 | Coefficient X3 | X3 Coefficient for a user defined linearisation. The linearisation is done by a polynom of fourth degree. | R/W | Float | 2048 |
SV2_Coeff_x4 | 4086 | Coefficient X4 | X4 Coefficient for a user defined linearisation. The linearisation is done by a polynom of fourth degree. | R/W | Float | 2048 |
SV2_CalVanDusen_A | 4087 | Coefficient A | Coefficient A for Callendar van-Dusen linearisation. | R/W | Float | 2048 |
Name | ID | Label | Description | Type | Access | Class |