名称 | ID | 标签 | 描述 | 类型 | 访问 | 分类 |
---|---|---|---|---|---|---|
sensor_upper_limit | 4052 | PV upper range limit | PV upper range limit defines the maximum usable value for the PV upper range value. | 读 | 浮点 | 2050 |
Out_Range_Low | 400D | PV lower range value | 下限值——定义模拟值和范围0%点开始的操作端点。此外,下限值还定义与模拟量值关联的报警和与数值表示关联的报警开始的操作端点。 | 读/写 | 浮点 | 34 |
Out_Range_High | 400C | PV upper range value | 上限值——定义模拟值和范围100%点开始的操作端点。此外,上限值还定义与模拟量值关联的报警和与数值表示关联的报警开始的操作端点。 | 读/写 | 浮点 | 34 |
Out_Mode | 402D | Analog output | Selection of standard operation 4..20 mA (small output signal by small process variables) or inverse operation 20..4 mA (small output signal on high process variables). | 读/写 | 枚举 | 2048 |
Out_Damping | 402E | Filter time | Input for filter, from measurement recording to output. (0 to 60 seconds) | 读/写 | 浮点 | 2048 |
Error_Mode | 400E | Fault condition | Select the fault information on sensor fault. When a sensor defect is recognised the transmitter transmits the defined output value. | 读/写 | 枚举 | 2048 |
Hi_Alarm_Output | 4076 | Failure output | Defines the exact failure output value in case of high alarm between 21.6 mA and 23 mA. | 读/写 | 浮点 | 2048 |
Out_Of_Range_Alarm | 4069 | Over/Und.rangealarm | On: In case of under- or overrange the transmitter will switch to alarm. Off: In case of under- or overrange the analog output freezes at 3.8 mA in underrange and at 20.5 mA in overrange. | 读/写 | 枚举 | 2048 |
Loop_Test | 404A | Simulation mode | Simulation mode is used to change the device's operating mode. OFF for normal measure operation. ON for analog output simulation. The value of analog output can be inserted in the page Simulation value. | 读/写 | 枚举 | 2048 |
Loop_Test_Value | 404B | Simulation value | Current at the output when simulation is set to ON. (value between 3.58 and 21.7 mA) | 读/写 | 浮点 | 2048 |
名称 | ID | 标签 | 描述 | 类型 | 访问 | 分类 |