名称 ID 标签 描述 类型 访问 分类
sensor_upper_limit 4052 PV upper range limit PV upper range limit defines the maximum usable value for the PV upper range value. 浮点 2050
Out_Range_Low 400D PV lower range value 下限值——定义模拟值和范围0%点开始的操作端点。此外,下限值还定义与模拟量值关联的报警和与数值表示关联的报警开始的操作端点。 读/写 浮点 34
Out_Range_High 400C PV upper range value 上限值——定义模拟值和范围100%点开始的操作端点。此外,上限值还定义与模拟量值关联的报警和与数值表示关联的报警开始的操作端点。 读/写 浮点 34
Out_Mode 402D Analog output Selection of standard operation 4..20 mA (small output signal by small process variables) or inverse operation 20..4 mA (small output signal on high process variables). 读/写 枚举 2048
Out_Damping 402E Filter time Input for filter, from measurement recording to output. (0 to 60 seconds) 读/写 浮点 2048
Error_Mode 400E Fault condition Select the fault information on sensor fault. When a sensor defect is recognised the transmitter transmits the defined output value. 读/写 枚举 2048
Hi_Alarm_Output 4076 Failure output Defines the exact failure output value in case of high alarm between 21.6 mA and 23 mA. 读/写 浮点 2048
Out_Of_Range_Alarm 4069 Over/Und.rangealarm On: In case of under- or overrange the transmitter will switch to alarm. Off: In case of under- or overrange the analog output freezes at 3.8 mA in underrange and at 20.5 mA in overrange. 读/写 枚举 2048
Loop_Test 404A Simulation mode Simulation mode is used to change the device's operating mode. OFF for normal measure operation. ON for analog output simulation. The value of analog output can be inserted in the page Simulation value. 读/写 枚举 2048
Loop_Test_Value 404B Simulation value Current at the output when simulation is set to ON. (value between 3.58 and 21.7 mA) 读/写 浮点 2048