Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
Bias_0 | 4025 | Offset sensor 1 | Additional calibration of the input signal in order to offset measurement deviations due to the installation or to compensate any sensor drift. An offset of -10 to +10 K (-18 F to 18 F) can be set up. | R/W | Float | 2048 |
unit_0 | 4008 | Measuring unit S1 | Display of sensor 1 engineering units. | R/W | Enum | 32 |
SV1_Serial_No | 4026 | Serial no. S1 | Input of sensor 1 serial number. (12 characters). | R/W | PackedAscii | 2048 |
SV1_Coeff_x0 | 4078 | Coefficient X0 | X0 Coefficient for a user defined linearisation. The linearisation is done by a polynom of fourth degree. | R/W | Float | 2048 |
SV1_Coeff_x1 | 4079 | Coefficient X1 | X1 Coefficient for a user defined linearisation. The linearisation is done by a polynom of fourth degree. | R/W | Float | 2048 |
SV1_Coeff_x2 | 407A | Coefficient X2 | X2 Coefficient for a user defined linearisation. The linearisation is done by a polynom of fourth degree. | R/W | Float | 2048 |
SV1_Coeff_x3 | 407B | Coefficient X3 | X3 Coefficient for a user defined linearisation. The linearisation is done by a polynom of fourth degree. | R/W | Float | 2048 |
SV1_Coeff_x4 | 407C | Coefficient X4 | X4 Coefficient for a user defined linearisation. The linearisation is done by a polynom of fourth degree. | R/W | Float | 2048 |
SV1_CalVanDusen_A | 407D | Coefficient A | Coefficient A for Callendar van-Dusen linearisation. | R/W | Float | 2048 |
SV1_CalVanDusen_B | 407E | Coefficient B | Coefficient B for Callendar van-Dusen linearisation. | R/W | Float | 2048 |
Name | ID | Label | Description | Type | Access | Class |