Name ID Label Description Type Access Class
input_range_units 401F PV rnge unit Range Unit- Engineering unit to be displayed with the Upper Range Value and Lower Range Value R Enum 32
input_upper_value 4020 PV URV Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 32
input_lower_value 4021 PV LRV Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 32
sensor_serial_number 400B Snsr s/n Sensor Serial Number- Uniquely identifies the sensor from which the Digital Value representation or Field Device variable is primarily derived. R Unsigned 2048
sensor2_value 4022 SV Field Device Variable Value- Digital value that changes magnitude with respect to time with no user intervention R Float 10
sensor2_units 4023 Temperature unit Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit R Enum 8
sensor_type 4006 Sensor type R/W Enum 64
linearizer_form 4007 Linearizer form R/W Enum 64
cjc 4008 CJC config R/W Enum 64
cjc_temp 4009 CJC temp R/W Float 64
Name ID Label Description Type Access Class