Loading…
Loading…
Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
upper_range_val | 401F | Valor de faixa superior | Valor de faixa superior- Define o endpoint operacional do qual o valor analógico, e o ponto 100% da faixa de porcentagem são derivados. Além do que, o valor da faixa superior define um endpoint operacional no qual o alarme associado com o valor analógico, e os alarmes associados com a representação do valor digital são derivados. | R/W | Float | 64 |
ma_fixed | 4020 | Hold fix | mA-output value when Hold-Fixed selected | R/W | Float | 64 |
sc_err1_hs | 4023 | Err.1 | Error message configuration. Soft fail will give a flashing FAIL flag. Hard fail will give a steady FAIL flag and, when enabled an updated mA-output value | R/W | Enum | 1024 |
sc_err5_hs | 4024 | Err.5 | Error message configuration. Soft fail will give a flashing FAIL flag. Hard fail will give a steady FAIL flag and, when enabled an updated mA-output value | R/W | Enum | 1024 |
sc_err6_hs | 4025 | Err.6 | Error message configuration. Soft fail will give a flashing FAIL flag. Hard fail will give a steady FAIL flag and, when enabled an updated mA-output value | R/W | Enum | 1024 |
sc_err7_hs | 4026 | Err.7 | Error message configuration. Soft fail will give a flashing FAIL flag. Hard fail will give a steady FAIL flag and, when enabled an updated mA-output value | R/W | Enum | 1024 |
sc_err8_hs | 4027 | Err.8 | Error message configuration. Soft fail will give a flashing FAIL flag. Hard fail will give a steady FAIL flag and, when enabled an updated mA-output value | R/W | Enum | 1024 |
sc_err13_hs | 4028 | Err.13 | Error message configuration. Soft fail will give a flashing FAIL flag. Hard fail will give a steady FAIL flag and, when enabled an updated mA-output value | R/W | Enum | 1024 |
table_0 | 4029 | 0% | mA-output table 0% value (4.0 mA) | R/W | Float | 64 |
table_5 | 402A | 5% | mA-output table 5% value (4.8 mA) | R/W | Float | 64 |
Name | ID | Label | Description | Type | Access | Class |