变量名称: Controller_pidParKPup
变量ID: 0x4272
变量标签: KP Up
变量描述: The KP value is the gain of the controller. The control speed and stability are influenced by the KP value. With higher KP values, the control speed increases.To compensate for existing dissymmetries in the controlled system, the KP value should be set separately for both directions (up/down). For most actuators, a satisfactory control response is achieved with a KP value between 2.0 and 10.0.Use this parameter to adjust the KP value for the positioning direction up (towards 100 %).
变量处理: 读/写
变量分类: Correction
变量长度: 4
变量数据类型: 浮点
变量显示格式: |en|5.1f
变量编辑格式: |en|5.1f
变量单位:
变量最大值: 120.1
变量最小值: 0.1
变量读取命令列表
无
变量写入命令列表
无