Variable Name: PRM_2451
Variable ID: 0x421E
Variable Label: Errore test sistema,codice
Variable Help: Displays the code of the error which occurred during the self test of the actuator. Depending on the kind of error the system generates a reset and after power up assumes the state failsafe or just activates this indication. 0x00 - no error detected 0x01 - error during master routine 0x02 - watchdog (hardware) was elapsed 0x03 - watchdog (software) was elapsed 0x08 - stack overflow 0x09 - stack underflow 0x0A - unrecoverable hardware error - the electronic performs a reset until error is no longer valid! 0x11 - error during testing the flash memory 0x12 - error while reading the starting pattern of the flash memory 0x13 - error while reading the ending pattern of the flash memory 0x14 - error during checksum test of flash memory
Variable Handling: R
Variable Class: Device
Variable Size: 1
Variable DataType: Unsigned
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
160 | 443F | cmd160_read_prm |
Variable Write Command List
None