Loading…

Variable Name: PRM_2855

Variable ID: 0x429A

Variable Label: Maintain in final pos.

Variable Help: Defines whether the actuator shall move automatically into the final position even after removing the command, if in the end position. Enable only if the valve has at least one final position with switch-off by torque!

Variable Handling: R/W

Variable Class: Device

Variable Size: 2

Variable DataType: Enum

Variable Enum Value Variable Enum Text
0x0000 Disabled
0x0001 Enabled

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
160 443F cmd160_read_prm

Variable Write Command List

Command Number Command ID Command Name
161 4440 cmd161_write_prm