Variable Name: loop_alarm_code
Variable ID: 0x00EC
Variable Label: Loop Alarm Type
Variable Help: Loop Alarm Type Here you specify the fault current, i.e. the current that is to be output in case of error. Important: In Safety Mode, the fault current is automatically set to High. You have the following setting options: High In case of error the current output is set to 22mA. Low In case of error the current output is set to 2mA. Hold Last Value In case of error the current output holds the last measured value. Value In case of error, the current output is set to the current value, which is set in Error Current Value.
Variable Handling: R/W
Variable Class: AnalogOut
Variable Size: 1
Variable DataType: Enum
Variable Enum Value | Variable Enum Text |
---|---|
0x0000 | HIGH |
0x0001 | LOW |
0x00EF | HOLD LAST VALUE |
0x00F0 | VALUE |
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
175 | 4211 | cmd_rd_alarm_setup |
15 | 00B7 | read_pv_output_info |
Variable Write Command List
Command Number | Command ID | Command Name |
---|---|---|
177 | 4213 | cmd_wr_alarm_code |