Variable Name: loop_alarm_code

Variable ID: 0x00EC

Variable Label: Loop Alarm Type

Variable Help: Loop Alarm Type Here you specify the fault current, i.e. the current that is to be output in case of error. Important: In Safety Mode, the fault current is automatically set to High. You have the following setting options: High In case of error the current output is set to 22mA. Low In case of error the current output is set to 2mA. Hold Last Value In case of error the current output holds the last measured value. Value In case of error, the current output is set to the current value, which is set in Error Current Value.

Variable Handling: R/W

Variable Class: AnalogOut

Variable Size: 1

Variable DataType: Enum

Variable Enum Value Variable Enum Text
0x0000 HIGH
0x0001 LOW
0x00EF HOLD LAST VALUE
0x00F0 VALUE

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
175 4211 cmd_rd_alarm_setup
15 00B7 read_pv_output_info

Variable Write Command List

Command Number Command ID Command Name
177 4213 cmd_wr_alarm_code