Loading…

Variable Name: var_ds_fExchangeMaxTimeConstant

Variable ID: 0x41C3

Variable Label: Max Time Constant

Variable Help: Max Time Constant The maximum allowable time constant must be greater than the current, automatically calculated time constant (see "Time Constant"). The value of the time constant approximately corresponds to the response time of the measurement. After entry of a value, the date on which the warning will be expected is displayed in "Warning Date". Due to the automatic decay compensation, the time constant is increased constantly until the maximum time constant is reached, whereupon the source exchange warning message is reported.

Variable Handling: R/W

Variable Class: Device

Variable Size: 4

Variable DataType: Float

Variable Display Format: |en|.1f

Variable Edit Format: |en|.1f

Variable Unit:

Variable Max:

Variable Min:

Variable Read Command List

Command Number Command ID Command Name
222 4231 cmd_rd_source_exchange_setup

Variable Write Command List

Command Number Command ID Command Name
225 4234 cmd_wr_source_exchange_time_const