变量名称: var_ds_fHVDefault
变量ID: 0x402E
变量标签: HV Default
变量描述: HV Default This setting affects: - A quick operation point control after power failure After a power failure, the HV starts at the last "HV Average" value which results from the "HV Default". This will significantly reduce the start-up phase after power failure. - Error detection in case of HV-drift If the HV deviates too far (+40%, -20%) from the HV Default or if the HV reaches the limits of the range of 300 V or 1300 V, this is reported as an error. - Special feature: 0V For maintenance purposes, the HV Default can also be set to 0V. In this case, the mechanisms described above are suspended; after a power failure, the measurement begins to get adjusted at 800 V. "HV Default" has already determined and set by BERTHOLD TECHNOLOGIES.
变量处理: 读/写
变量分类: 设备
变量长度: 4
变量数据类型: 浮点
变量显示格式: |en|.0f
变量编辑格式: |en|.0f
变量单位:
变量最大值:
变量最小值:
变量读取命令列表
命令号 | 命令ID | 命令名称 |
---|---|---|
163 | 4205 | cmd_rd_detector_setup |
变量写入命令列表
命令号 | 命令ID | 命令名称 |
---|---|---|
164 | 4206 | cmd_wr_detector_startup |