Loading…
Loading…
Variable Name: DetailedStatusByte3
Variable ID: 0x4037
Variable Label: Advisory Detail Status Byte 1
Variable Help:
Variable Handling: R
Variable Class: Dynamic | Diagnostic | Device
Variable Size: 1
Variable DataType: BitEnum
Variable Enum Value | Variable Enum Text |
---|---|
0x0001 | Analog Output 1 (HART PV) is Fixed |
0x0002 | Analog Output 2 (HART SV) is Fixed |
0x0004 | Analog Output 1 Validity |
0x0008 | Analog Output 2 Validity |
0x0010 | Frequency Output 1 Data is Invalid |
0x0020 | Frequency Output 2 Data is Invalid |
0x0040 | Analog Output 1 Test Enable |
0x0080 | Analog Output 2 Test Enable |
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
140 | 4033 | ReadDetailedStatus |
Variable Write Command List
None