Loading…
Loading…
Variable Name: device_status
Variable ID: 0x0097
Variable Label: Device Status
Variable Help: field device status: data indicating that the field device has detected condition(s) in the field device relating to: its hardware the validity of a variable its operating status an internal process.
Variable Handling: R/W
Variable Class: Dynamic | Diagnostic | HART
Variable Size: 1
Variable DataType: BitEnum
Variable Enum Value | Variable Enum Text |
---|---|
0x0001 | Process applied to the primary variable is outside the operating limits of the field device |
0x0002 | Process applied to the non-primary variable is outside the operating limits of the field device |
0x0004 | Analog output 1 and its digital representation are outside the operating range limits, and not responding to input |
0x0008 | Analog output 1 and its digital representation are in fixed mode, and not responsive to input changes |
0x0010 | Field device has more status available |
0x0020 | A reset or self test of the field device has occurred, or power has been removed and reapplied |
0x0040 | A modification has been made to the configuration of the field device |
0x0080 | Field device has malfunctioned due to a hardware error or failure |
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
144 | 4000 | read_linearization_control |
149 | 4022 | read_sensor_serial_number |
158 | 4024 | read_device_coding |
163 | 4026 | read_type_of_device |
153 | 403E | read_status_control_limit_switch |
134 | 4042 | read_low_flow_cutoff_control_and_values |
151 | 4047 | read_data_of_operating_fluid |
156 | 4055 | read_name_of_operating_fluid |
146 | 4057 | read_linearization_data |
148 | 4096 | read_firmware_version |
0 | 00AE | read_unique_identifier |
1 | 00AF | read_pv |
2 | 00B0 | read_pv_current_and_percent_range |
3 | 00B1 | read_dynamic_variables_and_pv_current |
12 | 00B4 | read_message |
13 | 00B5 | read_tag_descriptor_date |
14 | 00B6 | read_pv_sensor_info |
15 | 00B7 | read_pv_output_info |
16 | 00B8 | read_final_assembly_number |
33 | 0FA5 | read_transmitter_variables |
48 | 0FCE | read_additional_transmitter_status |
Variable Write Command List
None