Loading…

Variable Name: bs_nf

Variable ID: 0x404B

Variable Label: Noise filter

Variable Help: The MASS 6000 carries out signal processing using digital filtering. This technology allows sensor signals encumbered with noise to be filtered with different intensities. This applies to the mass flow measurement only. Setting 5 represents the maximum possible filtration and setting 1 represents the minimum possible filtration. Low filtering (setting 1) gives fast response to changes in flow and low immunity to noise. High filtering (setting 5) gives slow response to changes in flow and high noise immunity.

Variable Handling: R/W

Variable Class: Correction

Variable Size: 1

Variable DataType: Enum

Variable Enum Value Variable Enum Text
0x0003 1 * min
0x0004 2 **
0x0000 3 ***
0x0001 4 ****
0x0002 5 ***** max

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
131 40ED read_unsigned8

Variable Write Command List

Command Number Command ID Command Name
144 40EE write_unsigned8