Variable Name: eis_ei_select

Variable ID: 0x408C

Variable Label: DI Select

Variable Help: Selection of the external input from the list. The selected input will be active, when the external input (no. 77 and 78) is activated * Start Batch: Activates the batching process. * Hold/Continue: Batch will be paused while external input is activated. * Stop Batch: Stops the batching process. * Zero Adjust: Activates the Zero adjust process. * Totalizer Reset: Selected totalizer will be reset. Either totalizer 1, totalizer 2 or both can be selected. * Force output: Flow meter will be forced on x(selected) % of Upper Value (-125% to +125%). * Freeze output: Flow meter will be frozen on the actual flow. If the input is selected as Batch input, the digital output will be set to batch as default.

Variable Handling: R/W

Variable Class: Correction

Variable Size: 1

Variable DataType: Enum

Variable Enum Value Variable Enum Text
0x0000 Off
0x0001 Start batch
0x0002 Hold/continue batch
0x0003 Stop batch
0x0004 Zero adjustment
0x0005 Totalizer reset
0x0006 Force output
0x0007 Freeze output

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
187 4102 ReadDigitalInputFunction

Variable Write Command List

Command Number Command ID Command Name
186 4103 WriteDigitalInputFunction