Method Name: meth_SetSafetyModeOn

Method ID: 0x4251

Method Label: Safety ON

Method Help: Safety ON The safety mode has to be enabled for safety-relevant applications. In safety mode, safety-limiting values are set to a safety-compatible setting. In addition, you will be prompted to protect the detector with a password. The following settings are set automatically when safety mode is enabled: Current Loop Monitoring: = ENABLED HV Mode = AUTO Test Settings = NORMAL Error Handling = SENSITIV Digital inputs: = OFF Multidrop: Poll Addr = 0


  • {
  • char status[3];
  • int i;
  • SET_NUMBER_OF_RETRIES(7); _set_no_device(2); _set_all_resp_code(0); _set_device_status(0xFF,0); _set_xmtr_all_resp_code(0); _set_xmtr_device_status(0xFF,0);;
  • send(143, status); if(status[0] != 0) { display_response_status(143, status[0]); process_abort(); };
  • if(_ivar_value(16398) == _ivar_value(16400))
  • {
  • ACKNOWLEDGE("|en|Safety is already activated!");
  • }
  • else
  • {
  • send(15, status); if(status[0] != 0) { display_response_status(15, status[0]); process_abort(); };
  • if(_ivar_value(167) == _ivar_value(16384))
  • {
  • _get_dev_var_value(("|en|Enter Password:"),0,16388);
  • _vassign(16398,16400);
  • send(144, status); if(status[0] != 0) { display_response_status(144, status[0]); process_abort(); };