Variable Name: IpConverter_ipOffsetVenting
Variable ID: 0x427E
Variable Label: Y Offset Up
Variable Help: The offset for the output signal linearizes the behavior of the I/P module used and enables rapid compensation even in the case of small control deviations. The value is limited at the low end by a minimum value (neutral zone).The offset substantially affects the controlling speed for control deviations smaller than 5 %.To compensate for existing dissymmetries in the controlled system, the offset should be set separately for both directions (up/down).For most actuators, a satisfactory control response is achieved with offset values between 40 and 80 %. If, in the event of setpoint changes, the control response demonstrates an overshoot of less than 2 %, both offset values should be decreased.Both offset values should be increased when the actuator stops outside the tolerance band.Use this parameter to adjust the Y offset for the positioning direction down (towards 0 %)
Variable Handling: R/W
Variable Class: Correction
Variable Size: 4
Variable DataType: Float
Variable Display Format: |en|5.1f
Variable Edit Format: |en|5.1f
Variable Unit:
Variable Max: 100
Variable Min: 0
Variable Read Command List
None
Variable Write Command List
None