Variable Name: PRM_2577
Variable ID: 0x4246
Variable Label: Prioridad Remoto
Variable Help: Defines the interaction of the fieldbus interface and discrete I/Os. - Fieldbus: Commands of the discrete inputs are ignored - Additional inputs: Commands of the fieldbus interface are ignored - Equitable: The fieldbus commands and the commands of the discrete I/Os are validated in disjunction (logical OR combination). Observe: In the configuration 'Equitable' a limited usage for the prioritisation of the setpoint value and therefore also for the fail-safe exists. Only one controlling source is accepted. Once a discrete command input is configured as 'AUTOMATIC', the exclusive controlling source is the discrete I/O, otherwise the fieldbus. The priority of the commands is as follows: On/Off-Actuator: ESD > Stop > Command Modulating-Actuator: ESD > Automatic bit > Automatic via digital command input > Automatic via fieldbus > Stop > Command If different commands with the same priority are active at the same time, the command first activated command is adhered to!
Variable Handling: R/W
Variable Class: Device
Variable Size: 2
Variable DataType: Enum
Variable Enum Value | Variable Enum Text |
---|---|
0x0000 | Add on board |
0x0001 | Binary inputs |
0x0002 | Equivalente |
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
160 | 443F | cmd160_read_prm |
Variable Write Command List
Command Number | Command ID | Command Name |
---|---|---|
161 | 4440 | cmd161_write_prm |