Variable Name: PRM_2577

Variable ID: 0x4246

Variable Label: Priorita Remoto

Variable Help: Defines the interaction of the fieldbus interface and discrete I/Os. - Fieldbus: Commands of the discrete inputs are ignored - Additional inputs: Commands of the fieldbus interface are ignored - Equitable: The fieldbus commands and the commands of the discrete I/Os are validated in disjunction (logical OR combination). Observe: In the configuration 'Equitable' a limited usage for the prioritisation of the setpoint value and therefore also for the fail-safe exists. Only one controlling source is accepted. Once a discrete command input is configured as 'AUTOMATIC', the exclusive controlling source is the discrete I/O, otherwise the fieldbus. The priority of the commands is as follows: On/Off-Actuator: ESD > Stop > Command Modulating-Actuator: ESD > Automatic bit > Automatic via digital command input > Automatic via fieldbus > Stop > Command If different commands with the same priority are active at the same time, the command first activated command is adhered to!

Variable Handling: R/W

Variable Class: Device

Variable Size: 2

Variable DataType: Enum

Variable Enum Value Variable Enum Text
0x0000 Bus di campo
0x0001 Ingressi aggiuntivi
0x0002 Equivalente

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
160 443F cmd160_read_prm

Variable Write Command List

Command Number Command ID Command Name
161 4440 cmd161_write_prm