Variable Name: PRM_2911
Variable ID: 0x42CC
Variable Label: Segnalazione coppia
Variable Help: This Parameter specifies the torque monitoring behaviour during an externally received emergency shutdown command. Respect: Torque monitoring is operating normal. In case of a torque tripping in intermediate positions the actuator will stop with a fault indication. Ignore: Torque monitoring is disabled during external emergency shutdown request. The actuator will drive into the specified direction without monitoring the torque. This will result in an actuator movement with stall torque. If a torque final position cut off is specified in the respective direction the actuator will not stop in final position. In this case the value 'Respect in final positions' should be specified. Respect in final positions: Torque monitoring in intermediate positions is disabled during emergency shutdown. The torque monitoring will be activated if the parameterized final position is reached .
Variable Handling: R/W
Variable Class: Device
Variable Size: 2
Variable DataType: Enum
Variable Enum Value | Variable Enum Text |
---|---|
0x0000 | Attenzione |
0x0001 | Ignora |
0x0002 | Badare in finecorsa |
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
160 | 443F | cmd160_read_prm |
Variable Write Command List
Command Number | Command ID | Command Name |
---|---|---|
161 | 4440 | cmd161_write_prm |