0 |
Select Curve |
1 |
Last recording |
2 |
Curve 1 |
3 |
Curve 2 |
4 |
Curve 3 |
5 |
Curve 4 |
6 |
Demo curve |
7 |
Curve points OPEN |
8 |
Curve points CLOSE |
9 |
Description |
10 |
Timestamp curve OPEN |
11 |
Timestamp curve CLOSE |
12 |
Position buffer 1 |
13 |
Position buffer 2 |
14 |
Position buffer 3 |
15 |
Position buffer 4 |
16 |
Position buffer 5 |
17 |
Position buffer 6 |
18 |
Position buffer 7 |
19 |
Position buffer 8 |
20 |
Position buffer 9 |
21 |
Position buffer 10 |
22 |
Position buffer 11 |
23 |
Position buffer 12 |
24 |
Position buffer 13 |
25 |
Position buffer 14 |
26 |
Position buffer 15 |
27 |
Position buffer 16 |
28 |
Torque buffer 1 |
29 |
Torque buffer 2 |
30 |
Torque buffer 3 |
31 |
Torque buffer 4 |
32 |
Torque buffer 5 |
33 |
Torque buffer 6 |
34 |
Torque buffer 7 |
35 |
Torque buffer 8 |
36 |
Torque buffer 9 |
37 |
Torque buffer 10 |
38 |
Torque buffer 11 |
39 |
Torque buffer 12 |
40 |
Torque buffer 13 |
41 |
Torque buffer 14 |
42 |
Torque buffer 15 |
43 |
Torque buffer 16 |
44 |
Torque buffer 17 |
45 |
Torque buffer 18 |
46 |
Torque buffer 19 |
47 |
Torque buffer 20 |
48 |
Torque buffer 21 |
49 |
Torque buffer 22 |
50 |
Torque buffer 23 |
51 |
Torque buffer 24 |
52 |
Torque buffer 25 |
53 |
Torque buffer 26 |
54 |
Torque buffer 27 |
55 |
Torque buffer 28 |
56 |
Torque buffer 29 |
57 |
Torque buffer 30 |
58 |
Torque buffer 31 |
59 |
Torque buffer 32 |
60 |
Value |
61 |
Value x |
62 |
Min value |
63 |
Max value |
64 |
Min x-value |
65 |
Max x-value |
66 |
arr_CC_TOPO_XValues |
67 |
arr_CC_TOPO_Values |
68 |
CLOSE |
69 |
var CC TOPOC0 points |
70 |
|
71 |
OPEN |
72 |
var CC TOPOO0 points |
73 |
Torque curves |
74 |
Travel |
75 |
Torque |
76 |
curve CLOSE |
77 |
curve OPEN |
78 |
Load... |
79 |
load_CC_TOPO_select_curve |
80 |
load_CC_TOPO_read_actuatorinfo |
81 |
load_CC_TOPO_read_curveinfo |
82 |
load_CC_TOPO_read_curve |
83 |
read_CC_TOPO_data |
84 |
calc_CC_TOPO_position |
85 |
calc_CC_TOPO_torque |
86 |
Read firmware version |
87 |
Reset to Factory Defaults |
88 |
Reset Operational Data |
89 |
Reset HART parameter |
90 |
Set RTC (device) |
91 |
Read RTC (device) |
92 |
Read system time |
93 |
Device configuration locked |
94 |
Device is write-protected or is locked. |
95 |
Discrete variable simulation active |
96 |
The device is in simulation mode and one or more of its Discrete Variables are not representative of the process. |
97 |
Event notification overflow |
98 |
At least one event notification was not recorded due to event queue overflow. |
99 |
Failure |
100 |
Out of specification |
101 |
Function check |
102 |
DREHMO i-matic |
103 |
AUMA |
104 |
Status Bit Not Supported |
105 |
No Effect |
106 |
Maintenance Required |
107 |
Out of Specification |
108 |
Function Check |
109 |
Disabled |
110 |
Enabled |
111 |
Reset |
112 |
Set |
113 |
Used to map a status condition to a severity level. |
114 |
PV Analog Channel Saturated |
115 |
PV Analog Channel Fixed |
116 |
Critical Power Failure |
117 |
Simulation active |
118 |
Non-Volatile memory failure |
119 |
Volatile memory error |
120 |
Watchdog reset executed |
121 |
Power supply conditions out of range |
122 |
Environmental conditions out of range |
123 |
Electronic failure |
124 |
Status simulation active |
125 |
Discrete Variable Simulation active |
126 |
Event Notification Overflow |
127 |
Secondary Analog Channel Saturated |
128 |
Tertiary Analog Channel Saturated |
129 |
Quaternary Analog Channel Saturated |
130 |
Quinary Analog Channel Saturated |
131 |
Subdevice list changed |
132 |
Duplicate master detected |
133 |
Sub-device mismatch |
134 |
Sub-devices with duplicate IDs found |
135 |
Stale data notice |
136 |
Capacity Denied |
137 |
Bandwidth allocation pending |
138 |
Block transfer pending |
139 |
Radio failure |
140 |
Secondary Analog Channel Fixed |
141 |
Tertiary Analog Channel Fixed |
142 |
Quaternary Analog Channel Fixed |
143 |
Quinary Analog Channel Fixed |
144 |
Condensed status simulation |
145 |
Allows simulation of different status conditions. |
146 |
Condensed status value |
147 |
Condensed Status |
148 |
Field Device Status Mapping |
149 |
Bit |
150 |
7 |
151 |
6 |
152 |
5 |
153 |
4 |
154 |
3 |
155 |
2 |
156 |
1 |
157 |
0 |
158 |
Device Specific Status Mapping |
159 |
Byte 0 |
160 |
Byte 1 |
161 |
Byte 2 |
162 |
Byte 3 |
163 |
Byte 4 |
164 |
Byte 5 |
165 |
Extended Status Mapping |
166 |
Extended FDS |
167 |
Device Op Mode |
168 |
Std Status 0 |
169 |
Std Status 1 |
170 |
Transaction 1 Mapping |
171 |
Analog Channel |
172 |
Std Status 2 |
173 |
Std Status 3 |
174 |
Analog Channel Fixed |
175 |
Byte 14 |
176 |
Byte 15 |
177 |
Byte 16 |
178 |
Byte 17 |
179 |
Byte 18 |
180 |
Byte 19 |
181 |
Byte 20 |
182 |
Byte 21 |
183 |
Byte 22 |
184 |
Byte 23 |
185 |
Byte 24 |
186 |
target mapping |
187 |
Status bit not supported |
188 |
DV0: Device Family |
189 |
Variable 0, value |
190 |
.2f |
191 |
DV0: Family Status |
192 |
DV0: Units |
193 |
DV0: Classification |
194 |
DV0: PDQ |
195 |
DV0: LS |
196 |
DV0: USL |
197 |
.3f |
198 |
DV0: LSL |
199 |
DV0: Minimum Span |
200 |
DV0: Damping Value |
201 |
8.3f |
202 |
DV0: Simulated |
203 |
DV0: Update Period |
204 |
DV0: Serial Number |
205 |
7d |
206 |
DV0: Lower trim |
207 |
DV0: Upper trim |
208 |
DV0: Trim support |
209 |
DV0: Min lower trim |
210 |
DV0: Max lower trim |
211 |
DV0: Min upper trim |
212 |
DV0: Pres Max upper trim |
213 |
DV0: Min trim diff |
214 |
Variable 0, simulation |
215 |
Update Period |
216 |
Serial Number |
217 |
Variable 1, value |
218 |
DV1: Device Family |
219 |
DV1: Family Status |
220 |
DV1: Units |
221 |
DV1: Classification |
222 |
DV1: PDQ |
223 |
DV1: LS |
224 |
DV1: USL |
225 |
DV1: LSL |
226 |
DV1: Minimum Span |
227 |
DV1: Damping Value |
228 |
DV1: Simulated |
229 |
DV1: Update Period |
230 |
DV1: Serial Number |
231 |
DV1: Lower trim |
232 |
DV1: Upper trim |
233 |
DV1: Trim support |
234 |
DV1: Min lower trim |
235 |
DV1: Max lower trim |
236 |
DV1: Min upper trim |
237 |
DV1: Pres Max upper trim |
238 |
DV1: Min trim diff |
239 |
Variable 1, simulation |
240 |
Variable 2, value |
241 |
.1f |
242 |
DV2: Device Family |
243 |
DV2: Family Status |
244 |
DV2: Units |
245 |
DV2: Classification |
246 |
DV2: PDQ |
247 |
DV2: LS |
248 |
DV2: USL |
249 |
DV2: LSL |
250 |
DV2: Minimum Span |
251 |
DV2: Damping Value |
252 |
DV2: Simulated |
253 |
DV2: Update Period |
254 |
DV2: Serial Number |
255 |
DV2: Lower trim |
256 |
DV2: Upper trim |
257 |
DV2: Trim support |
258 |
DV2: Min lower trim |
259 |
DV2: Max lower trim |
260 |
DV2: Min upper trim |
261 |
DV2: Pres Max upper trim |
262 |
DV2: Min trim diff |
263 |
Variable 2, simulation |
264 |
Variable 3, value |
265 |
DV3: Device Family |
266 |
DV3: Family Status |
267 |
DV3: Units |
268 |
DV3: Classification |
269 |
DV3: PDQ |
270 |
DV3: LS |
271 |
DV3: USL |
272 |
DV3: LSL |
273 |
DV3: Minimum Span |
274 |
DV3: Damping Value |
275 |
DV3: Simulated |
276 |
DV3: Update Period |
277 |
DV3: Serial Number |
278 |
DV3: Lower trim |
279 |
DV3: Upper trim |
280 |
DV3: Trim support |
281 |
DV3: Min lower trim |
282 |
DV3: Max lower trim |
283 |
DV3: Min upper trim |
284 |
DV3: Pres Max upper trim |
285 |
DV3: Min trim diff |
286 |
Variable 3, simulation |
287 |
Variable 4, value |
288 |
Run OPEN |
289 |
Run OPEN |
290 |
Run CLOSE |
291 |
Run CLOSE |
292 |
Run SETPOINT |
293 |
Run SETPOINT |
294 |
DV4: Device Family |
295 |
DV4: Family Status |
296 |
DV4: Units |
297 |
DV4: Classification |
298 |
DV4: PDQ |
299 |
DV4: LS |
300 |
DV4: USL |
301 |
DV4: LSL |
302 |
DV4: Minimum Span |
303 |
DV4: Damping Value |
304 |
DV4: Simulated |
305 |
DV4: Update Period |
306 |
DV4: Serial Number |
307 |
DV4: Lower trim |
308 |
DV4: Upper trim |
309 |
DV4: Trim support |
310 |
DV4: Min lower trim |
311 |
DV4: Max lower trim |
312 |
DV4: Min upper trim |
313 |
DV4: Pres Max upper trim |
314 |
DV4: Min trim diff |
315 |
Variable 4, simulation |
316 |
Variable 5, value |
317 |
g |
318 |
DV5: Device Family |
319 |
DV5: Family Status |
320 |
DV5: Units |
321 |
DV5: Classification |
322 |
DV5: PDQ |
323 |
DV5: LS |
324 |
DV5: USL |
325 |
DV5: LSL |
326 |
DV5: Minimum Span |
327 |
DV5: Damping Value |
328 |
DV5: Simulated |
329 |
DV5: Update Period |
330 |
DV5: Serial Number |
331 |
DV5: Lower trim |
332 |
DV5: Upper trim |
333 |
DV5: Trim support |
334 |
DV5: Min lower trim |
335 |
DV5: Max lower trim |
336 |
DV5: Min upper trim |
337 |
DV5: Pres Max upper trim |
338 |
DV5: Min trim diff |
339 |
Variable 5, simulation |
340 |
Variable 6, value |
341 |
Operation pause active |
342 |
Operation pause active |
343 |
In intermed. position |
344 |
In intermed. position |
345 |
Start stepping mode |
346 |
Start stepping mode |
347 |
Actuator running |
348 |
Actuator running |
349 |
Handwheel operation |
350 |
Handwheel operation |
351 |
Operation from Remote |
352 |
Operation from Remote |
353 |
Local operation |
354 |
Local operation |
355 |
Not ready Remote |
356 |
Not ready Remote |
357 |
Warning |
358 |
Warning |
359 |
Fault |
360 |
Fault |
361 |
Maintenance required |
362 |
Maintenance required |
363 |
Out of specification |
364 |
Out of specification |
365 |
Function check |
366 |
Function check |
367 |
Failure |
368 |
Failure |
369 |
Device ok |
370 |
Device ok |
371 |
Thermal fault |
372 |
Thermal fault |
373 |
Phase failure |
374 |
Phase failure |
375 |
Selector REMOTE |
376 |
Selector REMOTE |
377 |
Selector LOCAL |
378 |
Selector LOCAL |
379 |
Limit switch OPEN |
380 |
Limit switch OPEN |
381 |
Limit switch CLOSE |
382 |
Limit switch CLOSE |
383 |
Torque switch OPEN |
384 |
Torque switch OPEN |
385 |
Torque switch CLOSE |
386 |
Torque switch CLOSE |
387 |
End position OPEN |
388 |
End position OPEN |
389 |
End position OPEN |
390 |
End position OPEN |
391 |
Setpoint reached |
392 |
Setpoint reached |
393 |
Not ready Remote |
394 |
Not ready Remote |
395 |
Running OPEN |
396 |
Running OPEN |
397 |
Running CLOSE |
398 |
Running CLOSE |
399 |
DV6: Device Family |
400 |
DV6: Family Status |
401 |
DV6: Units |
402 |
DV6: Classification |
403 |
DV6: PDQ |
404 |
DV6: LS |
405 |
DV6: USL |
406 |
DV6: LSL |
407 |
DV6: Minimum Span |
408 |
DV6: Damping Value |
409 |
DV6: Simulated |
410 |
DV6: Update Period |
411 |
DV6: Serial Number |
412 |
DV6: Lower trim |
413 |
DV6: Upper trim |
414 |
DV6: Trim support |
415 |
DV6: Min lower trim |
416 |
DV6: Max lower trim |
417 |
DV6: Min upper trim |
418 |
DV6: Pres Max upper trim |
419 |
DV6: Min trim diff |
420 |
Variable 6, simulation |
421 |
Variable 7, value |
422 |
DV7: Device Family |
423 |
DV7: Family Status |
424 |
DV7: Units |
425 |
DV7: Classification |
426 |
DV7: PDQ |
427 |
DV7: LS |
428 |
DV7: USL |
429 |
DV7: LSL |
430 |
DV7: Minimum Span |
431 |
DV7: Damping Value |
432 |
DV7: Simulated |
433 |
DV7: Update Period |
434 |
DV7: Serial Number |
435 |
DV7: Lower trim |
436 |
DV7: Upper trim |
437 |
DV7: Trim support |
438 |
DV7: Min lower trim |
439 |
DV7: Max lower trim |
440 |
DV7: Min upper trim |
441 |
DV7: Pres Max upper trim |
442 |
DV7: Min trim diff |
443 |
Variable 7, simulation |
444 |
Variable 8, value |
445 |
Safe ESD |
446 |
Safe ESD |
447 |
Safe STOP |
448 |
Safe STOP |
449 |
SIL fault |
450 |
SIL fault |
451 |
SIL function active |
452 |
SIL function active |
453 |
Channel 1 active |
454 |
Channel 1 active |
455 |
Channel 1 Data Ex |
456 |
Channel 1 Data Ex |
457 |
Channel 1 FailState |
458 |
Channel 1 FailState |
459 |
Channel 1 bus activity |
460 |
Channel 1 bus activity |
461 |
Input DIN 1 |
462 |
Input DIN 1 |
463 |
Input DIN 2 |
464 |
Input DIN 2 |
465 |
Input DIN 3 |
466 |
Input DIN 3 |
467 |
Input DIN 4 |
468 |
Input DIN 4 |
469 |
Input DIN 5 |
470 |
Input DIN 5 |
471 |
Input DIN 6 |
472 |
Input DIN 6 |
473 |
Intermediate pos. 1 |
474 |
Intermediate pos. 1 |
475 |
Intermediate pos. 2 |
476 |
Intermediate pos. 2 |
477 |
Intermediate pos. 3 |
478 |
Intermediate pos. 3 |
479 |
Intermediate pos. 4 |
480 |
Intermediate pos. 4 |
481 |
Intermediate pos. 5 |
482 |
Intermediate pos. 5 |
483 |
Intermediate pos. 6 |
484 |
Intermediate pos. 6 |
485 |
Intermediate pos. 7 |
486 |
Intermediate pos. 7 |
487 |
Intermediate pos. 8 |
488 |
Intermediate pos. 8 |
489 |
DV8: Device Family |
490 |
DV8: Family Status |
491 |
DV8: Units |
492 |
DV8: Classification |
493 |
DV8: PDQ |
494 |
DV8: LS |
495 |
DV8: USL |
496 |
DV8: LSL |
497 |
DV8: Minimum Span |
498 |
DV8: Damping Value |
499 |
DV8: Simulated |
500 |
DV8: Update Period |
501 |
DV8: Serial Number |
502 |
DV8: Lower trim |
503 |
DV8: Upper trim |
504 |
DV8: Trim support |
505 |
DV8: Min lower trim |
506 |
DV8: Max lower trim |
507 |
DV8: Min upper trim |
508 |
DV8: Pres Max upper trim |
509 |
DV8: Min trim diff |
510 |
Variable 8, simulation |
511 |
Variable 9, value |
512 |
DV9: Device Family |
513 |
DV9: Family Status |
514 |
DV9: Units |
515 |
DV9: Classification |
516 |
DV9: PDQ |
517 |
DV9: LS |
518 |
DV9: USL |
519 |
DV9: LSL |
520 |
DV9: Minimum Span |
521 |
DV9: Damping Value |
522 |
DV9: Simulated |
523 |
DV9: Update Period |
524 |
DV9: Serial Number |
525 |
DV9: Lower trim |
526 |
DV9: Upper trim |
527 |
DV9: Trim support |
528 |
DV9: Min lower trim |
529 |
DV9: Max lower trim |
530 |
DV9: Min upper trim |
531 |
DV9: Pres Max upper trim |
532 |
DV9: Min trim diff |
533 |
Variable 9, simulation |
534 |
Variable 10, value |
535 |
DV10: Device Family |
536 |
DV10: Family Status |
537 |
DV10: Units |
538 |
DV10: Classification |
539 |
DV10: PDQ |
540 |
DV10: LS |
541 |
DV10: USL |
542 |
DV10: LSL |
543 |
DV10: Minimum Span |
544 |
DV10: Damping Value |
545 |
DV10: Simulated |
546 |
DV10: Update Period |
547 |
DV10: Serial Number |
548 |
DV10: Lower trim |
549 |
DV10: Upper trim |
550 |
DV10: Trim support |
551 |
DV10: Min lower trim |
552 |
DV10: Max lower trim |
553 |
DV10: Min upper trim |
554 |
DV10: Pres Max upper trim |
555 |
DV10: Min trim diff |
556 |
Variable 10, simulation |
557 |
Variable 11, value |
558 |
Fieldbus EMCY |
559 |
No text available. |
560 |
Fieldbus enable LOCAL CLOSE |
561 |
The operation of the actuator via the local control in direction CLOSE will be released in the case of a locked display unit. |
562 |
Fieldbus enable LOCAL OPEN |
563 |
The operation of the actuator via the local control in direction OPEN will be released in the case of a locked display unit. |
564 |
Fieldbus enable local control |
565 |
The operation of the actuator via the local control will be enabled in the case of a locked display unit. |
566 |
Fieldbus DOUT 1 |
567 |
Transmitting a digital signal from the DCS to the relay board of the controller. |
568 |
Fieldbus DOUT 2 |
569 |
Fieldbus DOUT 3 |
570 |
Fieldbus DOUT 4 |
571 |
DV11: Device Family |
572 |
DV11: Family Status |
573 |
DV11: Units |
574 |
DV11: Classification |
575 |
DV11: PDQ |
576 |
DV11: LS |
577 |
DV11: USL |
578 |
DV11: LSL |
579 |
DV11: Minimum Span |
580 |
DV11: Damping Value |
581 |
DV11: Simulated |
582 |
DV11: Update Period |
583 |
DV11: Serial Number |
584 |
DV11: Lower trim |
585 |
DV11: Upper trim |
586 |
DV11: Trim support |
587 |
DV11: Min lower trim |
588 |
DV11: Max lower trim |
589 |
DV11: Min upper trim |
590 |
DV11: Pres Max upper trim |
591 |
DV11: Min trim diff |
592 |
Variable 11, simulation |
593 |
Loop Warning Variables |
594 |
Loop Warning Variables- Variables that display a warning message before new values are sent. |
595 |
Drive commands |
596 |
Fieldbus command close |
597 |
No text available. |
598 |
Fieldbus command open |
599 |
Fieldbus command set value |
600 |
Fieldbus command reset |
601 |
Fieldbus Speed |
602 |
no text |
603 |
% |
604 |
Setpoint |
605 |
Auxiliary commands |
606 |
Fieldb. enable LOCAL |
607 |
No text available. |
608 |
Fieldb. enable OPEN |
609 |
Fieldb. enable CLOSE |
610 |
PVST |
611 |
MPV_Cmd FBus |
612 |
No direct position |
613 |
Direct position 1 |
614 |
Direct position 2 |
615 |
Direct position 3 |
616 |
Direct position 4 |
617 |
Direct position 5 |
618 |
Direct position 6 |
619 |
Direct position 7 |
620 |
Direktposition 8 |
621 |
Direct position 9 |
622 |
Direct position 10 |
623 |
Direct position1 11 |
624 |
Direct position1 12 |
625 |
CW |
626 |
Direct position 1 CW |
627 |
Direct position 2 CW |
628 |
Direct position 3 CW |
629 |
Direct position 4 CW |
630 |
Direct position 5 CW |
631 |
Direct position 6 CW |
632 |
Direct position 7 CW |
633 |
Direct position 8 CW |
634 |
Direct position 9 CW |
635 |
Direct position 10 CW |
636 |
Direct position 11 CW |
637 |
Direct position 12 CW |
638 |
CCW |
639 |
Direct position 1 CCW |
640 |
Direct position 2 CCW |
641 |
Direct position 3 CCW |
642 |
Direct position 4 CCW |
643 |
Direct position 5 CCW |
644 |
Direct position 6 CCW |
645 |
Direct position 7 CCW |
646 |
Direct position 8 CCW |
647 |
Direct position 9 CCW |
648 |
Direct position 10 CCW |
649 |
Direct position 11 CCW |
650 |
Direct position 12 CCW |
651 |
Digital outputs |
652 |
Fieldbus DOUT 1 |
653 |
Fieldbus DOUT 2 |
654 |
Fieldbus DOUT 3 |
655 |
Fieldbus DOUT 4 |
656 |
Fieldbus DOUT 5 |
657 |
Fieldbus DOUT 6 |
658 |
Count of input data to read |
659 |
Input data byte 01 |
660 |
Input data byte 02 |
661 |
Input data byte 03 |
662 |
Input data byte 04 |
663 |
Input data byte 05 |
664 |
Input data byte 06 |
665 |
Input data byte 07 |
666 |
Input data byte 08 |
667 |
Input data byte 09 |
668 |
Input data byte 10 |
669 |
Input data byte 11 |
670 |
Input data byte 12 |
671 |
Input data byte 13 |
672 |
Input data byte 14 |
673 |
Input data byte 15 |
674 |
Input data byte 16 |
675 |
Input data byte 17 |
676 |
Input data byte 18 |
677 |
Input data byte 19 |
678 |
Input data byte 20 |
679 |
Input data byte 21 |
680 |
Input data byte 22 |
681 |
Input data byte 23 |
682 |
Input data byte 24 |
683 |
Input data byte 25 |
684 |
Input data byte 26 |
685 |
Input data byte 27 |
686 |
Input data byte 28 |
687 |
Input data byte 29 |
688 |
Input data byte 30 |
689 |
Input data byte 31 |
690 |
Input data byte 32 |
691 |
EDD generator |
692 |
Version EDD generator program |
693 |
01.00.05 |
694 |
Designated device version |
695 |
Device description is compatible to this device version family |
696 |
02.00.xx |
697 |
High scale value |
698 |
Defines which value corresponds to the final position OPEN |
699 |
Low scale value |
700 |
Defines which value corresponds to the final position CLOSE |
701 |
Position unit |
702 |
Sets the dimension of the position unit for the display output. If the dimension has changed, depending parameters must be adjusted manually (e.g. scale values). |
703 |
ppt |
704 |
° |
705 |
mm |
706 |
Decimal Position |
707 |
Sets the number of digits displayed after the comma in the main screen |
708 |
TAG/KKS-ID |
709 |
Process-specific identification of the actuator |
710 |
SW-Revision baseplate |
711 |
Software version of main board |
712 |
HW-Revision baseplate |
713 |
Hardware version of main board |
714 |
Device Manufacturer ID |
715 |
Manufacturer ID assigned by the Fieldbus organisation. |
716 |
Device Id |
717 |
Kind of electronic |
718 |
Serial number |
719 |
Serial number of electronic unit |
720 |
Original works number |
721 |
Serial number (works number) of the original produced actuator that included the control unit. |
722 |
Device certifications |
723 |
Device certifications |
724 |
Application |
725 |
Description of the actuator |
726 |
Installation area |
727 |
Process-specific part, where the actuator is installed |
728 |
Assembly date |
729 |
date when actuator was installed |
730 |
Actuator identifier no. |
731 |
Description of the actuator according to key with output and speed (e.g. DiM30 A-25) |
732 |
max. modulating torque |
733 |
Maximum available torque for modulating mode => setting defined by device key |
734 |
Rpm |
735 |
Speed of the output / Rpm |
736 |
Time / 90° |
737 |
The time needed to turn 90° (for DPiM) |
738 |
Mech. output form |
739 |
Mechanical output form |
740 |
min. ambient temp. |
741 |
Minimum allowed temperature when electronic unit is powered (heating is on) |
742 |
max. ambient temp. |
743 |
Maximum allowed temperature |
744 |
min. tripping torque |
745 |
Minimum available torque of the actuator output. Lower torques than this value cannot be detected! => setting defined by device key |
746 |
max. tripping torque |
747 |
Maximum available torque of the actuator output => setting defined by device key (see Control unit) |
748 |
Protection class |
749 |
Protection class |
750 |
Wiring diagram |
751 |
Wiring diagram of the actuator |
752 |
Commission no. |
753 |
Commission-number of the manufacturer |
754 |
Nominal voltage |
755 |
Angabe der Versorgungsspannung |
756 |
Phases |
757 |
Number of phases of the main power system |
758 |
Nominal frequency |
759 |
Angabe der Frequenz des Spannungsversorgungssystems |
760 |
Nominal current |
761 |
Angabe des Bemessungstromes |
762 |
A |
763 |
Starting current |
764 |
Maximum current when motor is energised |
765 |
Nominal power |
766 |
Angabe der Bemessungsleistung |
767 |
Phase shift (cos phi) |
768 |
Value of cosinus phi at nominal values. |
769 |
Output speed / Rpm |
770 |
Speed of motor at nominal values |
771 |
Type of duty |
772 |
Operational mode of the actuator (e.g. S2 10 min.) |
773 |
Motor type |
774 |
Angabe des Motortyps |
775 |
Insulation class |
776 |
Angabe der Isolationsklasse des Antriebsmotors |
777 |
Motor serial no. |
778 |
Angabe der Seriennummer des Antriebsmotors |
779 |
Internal positioner |
780 |
Information, whether the internal positioner is enabled or not => setting defined by device key |
781 |
Disabled V003 |
782 |
Enabled V005 |
783 |
Motor protection |
784 |
Sensor of motor temperature |
785 |
Thermal switch |
786 |
PTC |
787 |
Electrical specification |
788 |
Lists the electronic components of the actuator |
789 |
Local remote control |
790 |
Information, whether the actuator can be remote controlled using the interface of the display unit => setting defined by device key |
791 |
Disabled |
792 |
Enabled |
793 |
Enhanced controller |
794 |
This parameter controls the use of the enhanced controller that provides more complex settings for the controller. |
795 |
Disabled |
796 |
Enabled |
797 |
Serial number EM6 |
798 |
Serial number of combined sensor Em6 |
799 |
Snr. EM6 Remote |
800 |
Serial number of board inside actuator for wall mounted unit |
801 |
Motor monitoring |
802 |
Information about the version of the motor monitoring - PTC: the microcontroller does the motor monitoring - TMS: a certified module is used to do the motor monitoring. The microcontroller can not control this module |
803 |
Unknown |
804 |
PTC |
805 |
TMS |
806 |
Analogue output |
807 |
Indicates that the actuator was equipped with an anlog output by manufacturer |
808 |
Disabled |
809 |
Enabled |
810 |
Snr. base plate |
811 |
Serial number of base plate |
812 |
Snr. display plate |
813 |
Serial number of display plate |
814 |
Snr. Interface 1 |
815 |
Serial number of Interface board |
816 |
Snr. Interface 2 |
817 |
Serial number of additional, optional interface board |
818 |
SW-Revision display |
819 |
Software version of display board |
820 |
HW-Revision Display |
821 |
Hardware version of display board |
822 |
HW-Revision Interf. 1 |
823 |
Hardware version of interface board |
824 |
HW-Revision Interf. 2 |
825 |
Hardware version of additional, optional interface board |
826 |
Failure of internal 24V |
827 |
Indicates whether the internal power of 24 V DC - generated from mains power L1, L2 - is OK or failed. Enabling this indication makes only sense if the actuator is additionally powered by 24 V DC (either by external source or by battery backup). Otherwise - in case of a failure of the main power and thus a failure of the internal power, too - the electronic unit is deenergised, and therefore without function. |
828 |
Disabled |
829 |
Enabled |
830 |
Failure of external 24V |
831 |
Indicates whether the external power of 24 V DC is OK or failed. |
832 |
Phase failure |
833 |
Indicates whether a phase of the main power is missing. The indication is reset with the next movement or with a fault acknowledgement. If one of the two phases L1 and L2, which supply the electronic fail, the electronic will be without function. Only if the electronic is powered with additional 24 V DC, the failure of those two phases can be indicated. |
834 |
SW-Revision Interf. 1 |
835 |
Software version of interface board 1 |
836 |
SW-Revision Interf. 2 |
837 |
Software version of interface board 1 |
838 |
Actuator not starting |
839 |
If the time 'Delay run monit.' elapses while the motor is energised, and the position did not change significantly during this period, this indication is activated. This indication can be reset by a new movement or with a fault acknowledgement. |
840 |
Torque failure |
841 |
Indication is activated if the torque exceeds one of the values for the tripping torque |
842 |
Torque CLOSE |
843 |
Indicates that the closing torque exceeded the 'tripping torque' when closing the valve. The indication can be reset by moving the actuator into the other direction or with a fault acknowledgement. |
844 |
Torque OPEN |
845 |
Indicates that the opening torque exceeded the 'tripping torque' when opening the valve. The indication can be reset by moving the actuator into the other direction. |
846 |
Torque warning |
847 |
Is activated if the torque exceeds one of the values for the torque warning |
848 |
Torque warning CLOSE |
849 |
Indicates that the closing torque exceeds the warning value when closing the valve. The indication can be reset by moving the actuator into the other direction. |
850 |
Torque warning OPEN |
851 |
Indicates that the opening torque exceeds the warning value when opening the valve. The indication can be reset by moving the actuator into the other direction. |
852 |
Motor overtemperature |
853 |
Indication is activated if the motor temperature exceeds the permissible value. |
854 |
OFF mode |
855 |
Indicates that the actuator cannot move |
856 |
LOCAL mode |
857 |
Indicates that the actuator can be controlled by using the display unit. |
858 |
Emerg. shutdown tripped |
859 |
Is activate as long as the actuator executes an emergency shutdown |
860 |
Fail safe |
861 |
Is active as long as the actuator is in the mode fail safe. |
862 |
Hardware failure |
863 |
Indicates that during self test the electronic detected defective hardware components |
864 |
Combisensor failure |
865 |
Indicates that the electronic detected a malfunction of the combined sensor during self test. This indication lasts as long as the error. While this error is active, the actuator cannot be moved! The control unit tries to re-initialise the combined sensor to clear the error. |
866 |
Int. positioner disabled |
867 |
Indicates if the positioner of an actuator of type DiMxx5 is not enabled (command AUTOMATIC not active). |
868 |
Maintenance required |
869 |
Indicates if a limit of the operation data is exceeded. |
870 |
Mode not REMOTE |
871 |
Is active if the actuator is not in mode REMOTE |
872 |
Configuration invalid |
873 |
Indicates, that at least one of the tripping torques exceeds the maximum permissible torque values of either the additional component or the valve. |
874 |
Electronic overtemp. |
875 |
Indicates, that the electronic temperature is exceeding the permissible value |
876 |
Direction monitoring |
877 |
Indicates, that the actuator is turning the wrong way. This indication can be reset by a new movement or with a fault acknowledgement. |
878 |
Handwheel operation |
879 |
Indicates, that the position of the actuator is changing without giving a command to the motor. The indication is active as long as the position changes. |
880 |
Op-time survey |
881 |
Indicates, if the current running time exceeds one of the two values of 'Op-time survey CLOSE' or 'Op-time survey OPEN' |
882 |
Battery backup malf. |
883 |
Indicates an error with the internal accumulator. If this indication is active, the control unit cannot be supplied by the battery backup in case of mains power loss. |
884 |
Discrepancy power unit |
885 |
Indicates an error with the internal discrepancy analysis of the power module. |
886 |
Indicates whether the internal power of 24 V DC - generated from mains power L1, L2 - is OK or failed. Enabling this indication makes only sense if the actuator is additionally powered by 24 V DC (either by external source or by battery backup). Otherwise - in case of a failure of the main power and thus a failure of the internal power, too - the electronic unit is deenergised, and therefore without function. |
887 |
Indicates whether the external power of 24 V DC are OK or failed. |
888 |
Emergency-STOP |
889 |
Indicates an external Emergency-Stop signal. |
890 |
Disabled |
891 |
Enabled |
892 |
Indication is activated if the torque exceeds one of the values for the tripping torque |
893 |
Torque CLOSE |
894 |
Torque OPEN |
895 |
LOCAL mode |
896 |
Maintenance required |
897 |
Electronic overtemp. |
898 |
Indicates, that the position of the actuator is changing without giving a command to the motor. The indication is active as long as the position changes. |
899 |
Battery backup malf. |
900 |
Indicates an error with the internal accumulator. If this indication is active, the control unit cannot be supplied by the battery backup in case of mains power loss. |
901 |
Bluetooth PIN |
902 |
This parameter defines the PIN of the optional available Bluetooth interface. The PIN is used for authentication of the actuator during connexion establishment with the master station. |
903 |
Bluetooth name |
904 |
Defines the distinct identification of the actuator regarding the Bluetooth interface. |
905 |
Serial number |
906 |
TAG/KKS-ID |
907 |
Application |
908 |
Dyn. Consumptionvar. |
909 |
0..100% Verbrauch des Vertrauenskollektives der dynamischen Wartungsmeldung. Diese Variable gibt den höchsten relativen Verbrauch bezogen auf den jeweiligen Grenzwert der thermischen Alterung oder der mechanischen Alterung an. |
910 |
Discrepancy Error code |
911 |
Displays the error code describing the fault detected during discrepancy analysis of the power driver. If an error was detected the actuator can't be operated any more. Errorcodes for iMC devices: 10 - DO_MOT-EN not set, feedback MOT-EN-UE on low level. 11 - DO_MOT-EN set, feedback MOT-EN-UE on high level. 20 - S-RECHTS not set, feedback S-RECHTS-UE on low level. 21 - S-RECHTS set, feedback S-RECHTS-UE on high level. 22 - S-LINKS not set, feedback S-LINKS-UE on low level. 23 - S-LINKS set, feedback S-LINKS-UE on high level. 24 - ELR-RECHTS not set, feedback ELR-RECHTS-UE on low level. 25 - ELR-RECHTS set, feedback ELR-RECHTS-UE on high level. 26 - ELR-LINKS not set, feedback ELR-LINKS-UE on low level. 27 - ELR-LINKS set, feedback ELR-LINKS-UE on high level. 31 - Reset of DO_MOT-EN. Control the feedback MOT-EN-UE on high level. 32 - Set DO_MOT-EN. Control the feedback MOT-EN-UE on low level. 41 - Control the feedback S_RECHTS-UE on high level. 42 - Control the feedback S_LINKS-UE on high level. 43 - Control the feedback ELR_RECHTS-UE on high level. 44 - Control the feedback ELR-LINKS-UE on high level. 51 - Reset of DO_MOT-EN. Control the feedback MOT-EN-UE on high level. 61 - Set S-LINKS. Control the feedback S_LINKS-UE on high level. 62 - Reset S-LINKS, set S-RECHTS. Control of S_RECHTS-UE on high level. 63 - Reset S-RECHTS, set ELR_RECHTS. Control of ELR-LINKS-UE on high level. 64 - Reset ELR-LINKS, set ELR-RECHTS. Control of ELR-RECHTS-UE on high level. |
912 |
System test Error code |
913 |
Displays the code of the error which occurred during the self test of the actuator. Depending on the kind of error the system generates a reset and after power up assumes the state failsafe or just activates this indication. 0x00 - no error detected 0x01 - error during master routine 0x02 - watchdog (hardware) was elapsed 0x03 - watchdog (software) was elapsed 0x08 - stack overflow 0x09 - stack underflow 0x0A - unrecoverable hardware error - the electronic performs a reset until error is no longer valid! 0x11 - error during testing the flash memory 0x12 - error while reading the starting pattern of the flash memory 0x13 - error while reading the ending pattern of the flash memory 0x14 - error during checksum test of flash memory |
914 |
System test duration |
915 |
Displays the last duration for the self-test of the electronic unit in milliseconds |
916 |
ms |
917 |
Fault t-0 |
918 |
Shows the kind of last error and when it occurred |
919 |
None |
920 |
Torque OPEN |
921 |
Torque CLOSE |
922 |
Actuator start monitor. |
923 |
Direction monitoring |
924 |
Thermal overload |
925 |
Electronic overtemp. |
926 |
dummy |
927 |
Fail safe |
928 |
Encoder failure |
929 |
Encoder setup failure |
930 |
Torq. inp. gear exceed. |
931 |
Valve torque OPEN |
932 |
Valve torque CLOSE |
933 |
Systemtest fault |
934 |
24V internal failure |
935 |
24V external failure |
936 |
Phase 1 failure |
937 |
Phase 2 failure |
938 |
Phase 3 failure |
939 |
Phase correction failure |
940 |
Battery backup malf. |
941 |
24V external overload |
942 |
Emerg. shutdown (ESD) |
943 |
Discrepancy error |
944 |
Wrong power unit |
945 |
OFF mode |
946 |
LOCAL mode |
947 |
Mode not REMOTE |
948 |
Testmode enabled |
949 |
Simulation mode active |
950 |
Configuration invalid |
951 |
NV-Memory failure |
952 |
HW interface failure |
953 |
Device key invalid |
954 |
Encoder overflow |
955 |
Encoder range error |
956 |
Limit valve strokes |
957 |
Accum. operation cycles |
958 |
Current op. cycles/h |
959 |
Op-time survey OPEN |
960 |
Op-time survey CLOSE |
961 |
Gasket change recomm. |
962 |
Gear overhaul recomm. |
963 |
Torque warning CLOSE |
964 |
Handwheel operation |
965 |
Maintenance required |
966 |
Int. positioner disabled |
967 |
Position calibr. failure |
968 |
Torque calibr. failure |
969 |
Analog inp. calibr. failure |
970 |
Interlock LOCAL |
971 |
Interlock REMOTE |
972 |
TMS Module Error |
973 |
RTC Error |
974 |
RTC not set |
975 |
RTC battery low |
976 |
FO module error |
977 |
FOC budget ch. 1 |
978 |
FO failure ch. 1 |
979 |
FOC budget ch. 2 |
980 |
FO failure ch. 2 |
981 |
Fault t-1 |
982 |
Shows the kind of 2. error and when it occurred |
983 |
Fault t-2 |
984 |
Shows the kind of 3. error and when it occurred |
985 |
Fault t-3 |
986 |
Shows the kind of 4. error and when it occurred |
987 |
Fault t-4 |
988 |
Shows the kind of 5. error and when it occurred |
989 |
Fault t-5 |
990 |
Shows the kind of 6. error and when it occurred |
991 |
Fault t-6 |
992 |
Shows the kind of 7. error and when it occurred |
993 |
Fault t-7 |
994 |
Shows the kind of 8. error and when it occurred |
995 |
Valve torque CLOSE |
996 |
Fault t-8 |
997 |
Shows the kind of 9. error and when it occurred |
998 |
Fault t-9 |
999 |
Shows the kind of 10. error and when it occurred |
1000 |
Time t-0 |
1001 |
Shows the time (Up time electronic) of the fault |
1002 |
Time t-1 |
1003 |
Time t-2 |
1004 |
Time t-3 |
1005 |
Time t-4 |
1006 |
Shows the time (Up time electronic) of the fault |
1007 |
Time t-5 |
1008 |
Time t-6 |
1009 |
Time t-7 |
1010 |
Time t-8 |
1011 |
Time t-9 |
1012 |
Device Key |
1013 |
This key defines the configuration of the control unit (e.g. integral positioner, timer). A new key is only valid after a reset procedure. |
1014 |
Operation mode |
1015 |
Displays the active mode |
1016 |
LOCAL |
1017 |
OFF |
1018 |
REMOTE |
1019 |
LEARN |
1020 |
Setpoint position |
1021 |
Displays the setpoint value in the unit specified |
1022 |
Actual position |
1023 |
Displays the position in the unit specified in parameters>data logging>position unit |
1024 |
Breakdown delay |
1025 |
Sets the time of the delay between failure and activation of the fail safe action. |
1026 |
Reaction |
1027 |
Sets the action of the actuator if the setpoint value does not lie in the range 3.0...22 mA, or the fieldbus communication fails for a longer duration than specified with the parameter 'Breakdown delay'. |
1028 |
Act. run to fail safe |
1029 |
Stop actuator |
1030 |
Disabled |
1031 |
Position modulating act. |
1032 |
Sets the fail safe position for an actuator with integrated positioner |
1033 |
Fail safe |
1034 |
Information about the state of the fail safe function |
1035 |
Disabled |
1036 |
Active |
1037 |
Position on-off actuator |
1038 |
Sets the fail safe position for an on-off or inching actuator |
1039 |
0% CLOSE |
1040 |
100% OPEN |
1041 |
Intermediate position 1 |
1042 |
Sets the value for the intermediate position 1 in the current unit |
1043 |
Intermediate position 2 |
1044 |
Sets the value for the intermediate position 2 in the current unit |
1045 |
Intermediate position 3 |
1046 |
Sets the value for the intermediate position 3 in the current unit |
1047 |
Intermediate position 4 |
1048 |
Sets the value for the intermediate position 4 in the current unit |
1049 |
Intermediate position 5 |
1050 |
Sets the value for the intermediate position 5 in the current unit |
1051 |
Intermediate position 6 |
1052 |
Sets the value for the intermediate position 6 in the current unit |
1053 |
Intermediate position 7 |
1054 |
Sets the value for the intermediate position 7 in the current unit |
1055 |
Intermediate position 8 |
1056 |
Sets the value for the intermediate position 8 in the current unit |
1057 |
Remote priority |
1058 |
Defines the interaction of the fieldbus interface and discrete I/Os. - Fieldbus: Commands of the discrete inputs are ignored - Additional inputs: Commands of the fieldbus interface are ignored - Equitable: The fieldbus commands and the commands of the discrete I/Os are validated in disjunction (logical OR combination). Observe: In the configuration 'Equitable' a limited usage for the prioritisation of the setpoint value and therefore also for the fail-safe exists. Only one controlling source is accepted. Once a discrete command input is configured as 'AUTOMATIC', the exclusive controlling source is the discrete I/O, otherwise the fieldbus. The priority of the commands is as follows: On/Off-Actuator: ESD > Stop > Command Modulating-Actuator: ESD > Automatic bit > Automatic via digital command input > Automatic via fieldbus > Stop > Command If different commands with the same priority are active at the same time, the command first activated command is adhered to! |
1059 |
Add on board |
1060 |
Binary inputs |
1061 |
Equitable |
1062 |
Control mode |
1063 |
Sets the function of the REMOTE command inputs. In 'Inching operation' the command is active as long as the signal is active. In 'Maintain mode' the command is activated with an edge triggered command and deactivated in case of final position switch off, a command in reverse direction or stop command, or actuator switch off due to failure. |
1064 |
Inching operation |
1065 |
Maintain mode |
1066 |
Fail safe reaction |
1067 |
Defines whether for actuators with internal positioner the fail safe action is only performed if the automatic command is active or in every case. |
1068 |
Respect Automatic |
1069 |
Ignore Automatic |
1070 |
Stepping mode select |
1071 |
Sets the cyclic pulse time Ton to a fixed value (Linear), or reduces the time Ton from the specified value to the minimum value of 0.5 seconds during movement (Decreasing). With decreasing stepping mode, the minimum Ton is reached in final position CLOSE - regardless of the direction. |
1072 |
linear |
1073 |
Decreasing |
1074 |
Thermal failure delay |
1075 |
Sets the time delay between detection of a motor overtemperature, and the indication and switch off. The temperature sensor is only powered by the main power of the actuator. If the main power fails, the temperature detection is not powered, and therefore the motor temperature is detected as too high. The motor overtemperature indication will be activated. To suppress this indication due to short power failures, the delay time can be set. |
1076 |
Phase correction |
1077 |
Defines the rotating field for the connected power system. If set to 'Detect', the rotating field is checked continuously. |
1078 |
Enabled |
1079 |
CW phase sequence |
1080 |
CCW phase sequence |
1081 |
Phase monitoring |
1082 |
If activated detects if a phase is missing. In this case the motor is de-energised, and the indication 'phase failure' is given. The indication is reset with the next movement or fault acknowledgement. |
1083 |
Disabled |
1084 |
Enabled latching |
1085 |
Enabled non latching |
1086 |
Phase monitoring delay |
1087 |
Defines the delay time of the indications 'phase correction error' or 'Failure of internal 24V'. |
1088 |
Stepping mode opening |
1089 |
Enables the stepping mode if opening the valve. |
1090 |
Stepping mode closing |
1091 |
Enables the stepping mode if closing the valve. |
1092 |
Stepping mode T on |
1093 |
Sets the duration the motor is energised during cyclic operation. |
1094 |
Stepping mode T off |
1095 |
Sets the duration the motor is deenergised during cyclic operation. |
1096 |
max. electr. temp. |
1097 |
The maximum allowed temperature of electronic |
1098 |
min. electronics temp. |
1099 |
The minimum allowed temperature of electronic |
1100 |
Thermal failure reset |
1101 |
A tripped motor protection requires the cooling down of the motor into a valid operating temperature range. A reset of the failure indication and thus a new motor run is possible by: 1. Automatic failure reset. Set parameterisation to 'Automatic'. 2. An explicit required manual confirmation. Set parameterisation to 'Manuell'. A failure confirmation can be done at the local control station as well as from a remote command or parameterisation in operation mode REMOTE. In case of EX proofed actuators, the parameterisation to 'Automatic' is only allowed if the duty type is strictly observed. |
1102 |
Automatic |
1103 |
Manual |
1104 |
Start pulse internal |
1105 |
Defines the second limit of the stepping mode. The first limit is always position CLOSE. |
1106 |
Step. mode pulse source |
1107 |
Sets the source which controls whether the stepping mode is active. If set to 'Internal', the stepping mode is active from position CLOSE to 'Start pulse internal'. If set to 'External', the stepping mode is active as long as the command is active and the actuator turns into a direction the stepping mode has been enabled. |
1108 |
Internal |
1109 |
External |
1110 |
Hysteresis 1 |
1111 |
Hysteresis for signalling the specific intermediate position. |
1112 |
Hysteresis 2 |
1113 |
Hysteresis 3 |
1114 |
Hysteresis 4 |
1115 |
Hysteresis 5 |
1116 |
Hysteresis 6 |
1117 |
Hysteresis 7 |
1118 |
Hysteresis 8 |
1119 |
Signal behaviour 1 |
1120 |
Specifies the signal behaviour of the specific intermediate position. No signal The intermediate position will not be signalized. C____------O The signal of the intermediate position will be high inbetween the specified intermediate position and the final position OPEN. C------____O The signal of the intermediate position will be high in between the final position CLOSE and the specified intermediate position. C___---___O The signal of the intermediate position will be high in a range specified by the hysteresis arround the specified intermediate position. |
1121 |
No signal |
1122 |
C____------O |
1123 |
C------____O |
1124 |
C___---___O |
1125 |
Signal behaviour 2 |
1126 |
Signal behaviour 3 |
1127 |
Signal behaviour 4 |
1128 |
Signal behaviour 5 |
1129 |
Signal behaviour 6 |
1130 |
Signal behaviour 7 |
1131 |
Signal behaviour 8 |
1132 |
Closing direction |
1133 |
Turning direction of the actuator, if the valve is closing, seen from the motor side of the actuator |
1134 |
Counter clockwise CCW |
1135 |
Clockwise CW |
1136 |
Operation time CLOSE |
1137 |
Duration of the last complete closing of the valve starting at open position |
1138 |
Operation time OPEN |
1139 |
Duration of last complete opening of the valve starting at close position |
1140 |
Actual operation time |
1141 |
Duration of last movement |
1142 |
Calibration date |
1143 |
Date, when actuator was last calibrated. |
1144 |
Configuration date |
1145 |
This field can be used to store the date of the last configuration changes |
1146 |
Motor operation time |
1147 |
Accumulated operating time of motor |
1148 |
Position trippings |
1149 |
Number of stops due to reaching a final position |
1150 |
Operation cycles |
1151 |
Number of motor start-ups |
1152 |
Actual op. cycles/h |
1153 |
Information of number of motor start-ups during the last hour. Value is updated continuously |
1154 |
1/h |
1155 |
Torque tripping |
1156 |
Number of stops due to a torque exceeding the 'Tripping torque ...' |
1157 |
Adjustment range |
1158 |
Information about the stroke in the configured unit (see parameters>data logging>position unit) |
1159 |
Motor oper. time total |
1160 |
Operating time of motor. This value cannot be reset. |
1161 |
Position trippings total |
1162 |
Number of stops due to reaching a final position. This value cannot be reset. |
1163 |
Tolerance pos. CLOSE |
1164 |
Sets the range for the positioner to interpret a setpoint value as final position CLOSE. The actuator will move automatically until it reaches the final position if the setpoint value has a value between position close and this value. The final position is left if the setpoint value is higher than the final position + tolerance + Xp. |
1165 |
Tolerance pos. OPEN |
1166 |
Sets the range for the positioner to interpret a setpoint value as final position OPEN. The actuator will move automatically until it reaches the final position if the setpoint value has a value between position open and this value. The final position is left if the setpoint value is lower than the final position - tolerance - Xp. |
1167 |
Switching off mode |
1168 |
Sets the switch-off conditions of the valve |
1169 |
torque CLOSE/OPEN |
1170 |
Pos.CLOSE/torqueOPEN |
1171 |
torqueCLOSE/pos.OPEN |
1172 |
Final position limit sw. |
1173 |
Torque |
1174 |
Displays the current torque |
1175 |
Tripping torque CLOSE |
1176 |
The actuator switches off if the torque exceeds this value when closing |
1177 |
Tripping torque OPEN |
1178 |
The actuator switches off if the torque exceeds this value when opening |
1179 |
Torque unit |
1180 |
Sets the unit for the torque |
1181 |
Nm |
1182 |
ft-lb |
1183 |
Valve stroke |
1184 |
Value of the accumulated valve travel in multiples of complete stroke (= 1) |
1185 |
> Limit valve stroke |
1186 |
Maximum allowed valve travel in multiples of complete stroke (= 1). If the value is exceeded, an indication 'maintenance required' is generated. If value '0' is set, this check is disabled. |
1187 |
Maintenance date |
1188 |
This field can be used to store the date of the last maintenance |
1189 |
Thermal ageing |
1190 |
Calculates the ageing process of temperature dependent components of the actuator like gaskets. Those ageing processes are depending on the ambient temperature. |
1191 |
> Limit thermal ageing |
1192 |
Limit for the thermal ageing. If this value is exceeded, the indications 'maintenance essential' and 'Gasket change recomm.' are generated. If value is set to '0', this check is disabled. |
1193 |
Mechanical ageing |
1194 |
Calculates the abrasion of components of the internal gear. |
1195 |
> Limit mechanical ageing |
1196 |
Limit for mechanical ageing. If this value is exceeded, the indications 'maintenance essential' and 'gear overhaul recomm.' are generated. If value is set to '0', this check is disabled. |
1197 |
Type mech. ageing |
1198 |
This parameter defines the algorithm used for the calculation of the mechanical ageing. It is required to select the adequate actuator type in order to use the correct calculation algorithm. Setting of the value to 'No' results in a deactivation of the mechanical ageing calculation. |
1199 |
No |
1200 |
D30 5-15Nm |
1201 |
D30 10-30Nm |
1202 |
DR30 15-30Nm |
1203 |
DP30 10-30Nm |
1204 |
D59 20-60Nm |
1205 |
DR59 30-60Nm |
1206 |
DP59 20-60Nm |
1207 |
D60 20-60Nm |
1208 |
DR60 30-60Nm |
1209 |
D120 40-120Nm |
1210 |
DR120 60-120Nm |
1211 |
D249 80-250Nm |
1212 |
D250 40-120Nm |
1213 |
D250 80-250Nm |
1214 |
DR250 120-250Nm |
1215 |
D500 150-500Nm |
1216 |
DR500 200-500Nm |
1217 |
D1000 300-1000Nm |
1218 |
DR1000 500-1000Nm |
1219 |
DP119 40-120Nm |
1220 |
DP319 120-320Nm |
1221 |
DP799 320-800Nm |
1222 |
DP1599 800-1600Nm |
1223 |
D250 60-120Nm |
1224 |
D2000 800-2000Nm |
1225 |
DP150 50-150Nm |
1226 |
DP299 125-300Nm |
1227 |
DP300 125-300Nm |
1228 |
DP450 250-450Nm |
1229 |
DP600 200-600Nm |
1230 |
DP900 500-900Nm |
1231 |
DP1200 500-1200Nm |
1232 |
DP1800 1000-1800Nm |
1233 |
> Preset mechanical ageing |
1234 |
This parameter can be used to preset the '> Limit mechanical ageing' to a limit fitting to the present actuator´s size. |
1235 |
Manufacturer |
1236 |
Manufacturer of the valve, which was delivered with the actuator |
1237 |
Indication about the actuators manufacturer |
1238 |
Valve type |
1239 |
Information about the moving of the valve |
1240 |
linear |
1241 |
90° |
1242 |
rotating |
1243 |
Actuator model |
1244 |
Power source of the actuator |
1245 |
electrical-pneumatic |
1246 |
electrical |
1247 |
electrical-hydraulic |
1248 |
Others |
1249 |
Serial number |
1250 |
Serial number of valve |
1251 |
Actuator serial number => setting defined by device key |
1252 |
Serial number |
1253 |
Serial number of component |
1254 |
Angabe des Herstellers |
1255 |
Add. gear model |
1256 |
type of additional component |
1257 |
Gearbox assembly date |
1258 |
Date of installation of component |
1259 |
Thermal overload |
1260 |
Number of times when motor was overheated |
1261 |
Electronics overtemp. |
1262 |
Accumulated duration of electronic temperature exceeding maximum allowed value. |
1263 |
Actuator start failures |
1264 |
Number of times while the motor is energised and the position did not change significantly during this period. |
1265 |
Up time electronic |
1266 |
The time the electronic was energised |
1267 |
Number of power on |
1268 |
The number of system resets |
1269 |
Dead time |
1270 |
Automatic Bit |
1271 |
This parameter can be used to avoid the required automatic bit for the activation of the internal positioner. Instead of the usage of the automatic bit it is possible - to permanently enable the internal positioner -> 'Force enabled', thus control via setpoint value - to permanently disable the internal positioner -> 'Force disabled', thus control via discrete commands OPEN, CLOSE |
1272 |
Force disabled |
1273 |
Force enabled |
1274 |
acc. REMOTE |
1275 |
Edge detection remote |
1276 |
This parameter is relevant for the actuator action in case of a change of the operation mode into REMOTE. If the parameter is set to 'Activated', a new actuator start command 'edge triggered behaviour' is required to initiate an actuator run. If the parameter is set to 'Deactivated', in case of a switch over to mode REMOTE, an actuator run starts directly if a running command is still active. |
1277 |
Enabled |
1278 |
Torque bypass final pos. |
1279 |
Disables the torque detection during the time 'Delay final positions' when trying to leave a final position. If the torque still exceeds the 'tripping torque' if the actuator leaves the end position or if the delay time is exceeded, a torque indication is generated and the actuator switches off. |
1280 |
Disabled |
1281 |
In position OPEN |
1282 |
In position CLOSE |
1283 |
In both final positions |
1284 |
Torque warnings |
1285 |
Number of warnings due to a torque exceeding the 'Torque warning level' |
1286 |
Output Torque |
1287 |
Defines the output of the torque value. With 'Actual value' the current torque is output. When using slow fieldbus or DCS systems, peaks of the torque might not be detected. 'Max. value' outputs the maximum torque of the last movement. A new movement resets the value of the torque. 'Max. value wo. fin. Pos.' (Maximum value without final positions) is identical to 'Max. value', except that the value of the torque is not output within the range of the final positions. With 'Trend value' the maximum value of the torque is output for 1 second, and automatically cleared afterwards. We recommend this function for slow DCS systems. |
1288 |
Actual value |
1289 |
Max. value |
1290 |
Max.value wo. fin. Pos. |
1291 |
Trend value |
1292 |
Final position indication |
1293 |
Sets the indication of the final positions. If set to ''Position'' the indication is activated if the limit positions are reached. If set to 'Act. cut off mode' the indication is only activated if the actuator reaches the final positions. |
1294 |
Position |
1295 |
Acc. Switch-off mode |
1296 |
Torque indication |
1297 |
Sets whether a torque exceeding the tripping torque shall or shall not be indicated if the actuator is in an end position. |
1298 |
No ind. in final positions |
1299 |
Ind. in final positions |
1300 |
Maintain in final pos. |
1301 |
Defines whether the actuator shall move automatically into the final position even after removing the command, if in the end position. Enable only if the valve has at least one final position with switch-off by torque! |
1302 |
Torque warning CLOSE |
1303 |
The warning indication is activated if the torque exceeds this value when closing |
1304 |
Torque warning OPEN |
1305 |
The warning indication is activated if the torque exceeds this value when opening |
1306 |
Lock display unit |
1307 |
Defines how the command 'Enable LOCAL' works: - 'Disable completely' is like having a lock through the enter button - no push button can be operated - 'Disable local operation' only disables the motor operation - 'Ignore signal' disables this command input |
1308 |
Disable completely |
1309 |
Disable local operation |
1310 |
Ignore signal |
1311 |
Torque byp. interm. pos. |
1312 |
Enables the breakdown torque of the motor when trying to leave an intermediate position. The bypass is not enabled if the actuator switched off due to a high torque. |
1313 |
Disabled |
1314 |
Enabled |
1315 |
> Limit cycles |
1316 |
Limit of number of motor start-ups. If the value is exceeded, an indication 'maintenance essential' is generated. If value is set to '0', this check is disabled. |
1317 |
Deadband OPEN |
1318 |
modulating tolerance in direction OPEN |
1319 |
Deadband CLOSE |
1320 |
modulating tolerance in direction CLOSE |
1321 |
Outer deadband |
1322 |
max. input torque |
1323 |
Value of maximum permissible input torque of component. The parameter 'Tripping torque CLOSE', 'Tripping torque OPEN' in the submenu valve cannot exceed this value. |
1324 |
Gear ratio |
1325 |
Angabe der Übersetzung des Zusatzgetriebes |
1326 |
Gear factor |
1327 |
Angabe des Getriebefaktors |
1328 |
Mechnical form of output |
1329 |
max. cycles / hour |
1330 |
Record of maximum value of 'Actual op. cycles / h'. |
1331 |
> Limit cycles / hour |
1332 |
Limit of number of motor start-ups during one hour. |
1333 |
Maintain mode LOCAL |
1334 |
If this parameter is enabled and a local command close or open is given, the actuator runs until a final position is reached or an error occurs. |
1335 |
Language |
1336 |
Sets the language of the display |
1337 |
German |
1338 |
English |
1339 |
Loaded language |
1340 |
LCD backlight delay |
1341 |
Sets the time after which the backlight is switched off if no button is pressed |
1342 |
Automatic logout |
1343 |
Defines whether and how an automatic logout is accomplished |
1344 |
Disabled |
1345 |
On delay time |
1346 |
At menu exit |
1347 |
Logout delay time |
1348 |
Sets the time after which an automatic logout is accomplished |
1349 |
PC-interface |
1350 |
This parameter can block the Infrared port |
1351 |
Disabled |
1352 |
Enabled |
1353 |
Actual duty cycle value |
1354 |
Duration of energised motor during the last hour. Value is updated continuously. |
1355 |
max. duty cycle value |
1356 |
Information about longest duration of energised motor during one hour. |
1357 |
Running indication |
1358 |
If enabled, the appropriate Local Lamp (OPEN or CLOSE) is blinking fast, if the motor is energised. |
1359 |
directional flashing |
1360 |
undirectional flashing |
1361 |
undirectional static |
1362 |
Delay time final pos. |
1363 |
Sets the duration the actuator can move with the breakdown torque of the motor - without a torque indication - to leave a final position |
1364 |
Delay time interm. pos. |
1365 |
Sets the duration of the disabled torque detection if leaving an intermediate position |
1366 |
Position output |
1367 |
Defines how the position is displayed: - With ''Over-/underflow'' the position is not limited to values between CLOSE and OPEN (see data logging -> high scale value, low scale value) - With 'Limited' the displayed position is limited to the range between CLOSE and OPEN |
1368 |
Over-/underflow |
1369 |
Limited |
1370 |
Enhanced controller |
1371 |
Disabled |
1372 |
Enabled |
1373 |
Op-time survey CLOSE |
1374 |
Sets the time which may not be exceeded when moving from OPEN to final position CLOSE at once. If the current running time is longer than this value, the indication 'op-time survey' is activated. If this value is '0', the survey is disabled. |
1375 |
Op-time survey OPEN |
1376 |
Sets the time which may not be exceeded when moving from CLOSE to final position OPEN at once. If the current running time is longer than this value, the indication 'op-time survey' is activated. If this value is '0', the survey is disabled. |
1377 |
max. torque OPEN |
1378 |
Maximum permissible torque of valve or gear in direction open. A value of 0 means no restriction. |
1379 |
max. torque CLOSE |
1380 |
Maximum permissible torque of valve or gear in direction close. A value of 0 means no restriction. |
1381 |
Phase sequence |
1382 |
Information about the input power |
1383 |
Failure |
1384 |
CW detected |
1385 |
CCW detected |
1386 |
CW manual |
1387 |
CCW manual |
1388 |
Detection in progress |
1389 |
Phase 1 |
1390 |
Displays the state of phase L1. The indication is reset with the next movement or with a fault acknowledgement. |
1391 |
Failure |
1392 |
Ok |
1393 |
Detection disabled |
1394 |
Phase 2 |
1395 |
Displays the state of phase L2. The indication is reset with the next movement or with a fault acknowledgement. |
1396 |
Phase 3 |
1397 |
Displays the state of phase L3. The indication is reset with the next movement or with a fault acknowledgement. |
1398 |
24V internal |
1399 |
Displays the state of the 24 V driven by the main power |
1400 |
24V external |
1401 |
Displays the state of the externally powered 24 V |
1402 |
Electronic temperature |
1403 |
Displays the temperature of electronic |
1404 |
Temperature corr. value |
1405 |
Defines the difference between measured and ambient temperature. E.g. if set to 10°C, the ambient temperature is 10K less than the measured temperature. |
1406 |
NV-Memory failure |
1407 |
Displays whether the non-volatile memory showed an error during the boot procedure |
1408 |
No |
1409 |
Yes |
1410 |
Information, whether the communication to the interface board is OK |
1411 |
EM6 Error code |
1412 |
The control unit checks the combined sensor (EM6) during the automatically performed self test. In case of an error the indication 'Combisensor failure' is activated. This parameter describes which kind of error was detected. The EM6 is checked in several steps which generate different error code groups. Errors during general communication with EM6: 101 - no communication possible with remote EM6 102 - no communication possible with remote EM6 103 - no communication possible with remote EM6 104 - no communication possible with remote EM6 105 - no communication possible with remote EM6 106 - reference voltage is not valid 107 - communication to remote EM6 is lost 108 - reference voltage is no longer valid 109 - critical communication error with EM6 The non-volatile memory of the combined sensor EM6 is checked in regular intervals. Detected errors are coded as follows: 1 - Read error of serial number 2 - Read error of offset of angle 3 - Read error of correction factor for analogue values 4 - Read error of closing direction 5 - Read error of torque value 6 - Read error of LEARN values 7 - Read error of checksum flag Errors with wall mounted unit: 11 - Read error of serial number 12 - Read error of serial number of board DiM-06 13 - Read error of part number of board DiM-06 14 - Read error of closing direction 15 - Read error of torque value 16 - Read error of LEARN values |
1413 |
Orientation |
1414 |
Specifies if the display content is shown normal or 180° rotated. |
1415 |
Normal |
1416 |
Rotated |
1417 |
Hysteresis output |
1418 |
Delay torque monitoring |
1419 |
Sets the duration the actuator ignores torque trippings to filter out peaks in torque measurement. |
1420 |
Limit to max. Torque |
1421 |
If enabled the actuator monitors for the maximum adjustable torque during monitoring delay. If disabled the actuator operates at stall torque. |
1422 |
Emerg. shutdown (ESD) |
1423 |
Sets the action of this function. If enabled the actuator moves to the specified final position. The following indications can be activated to stop the movement or to be ignored. |
1424 |
0% CLOSE |
1425 |
100% OPEN |
1426 |
Emerg. shutdown (ESD) |
1427 |
Information about the state of the emergency shutdown command. Enabled: External emergency shutdown is requested. Disabled: External emergency shutdown is not requested. |
1428 |
Disabled |
1429 |
Enabled |
1430 |
If ignored the actuator moves to the specified final position even if the motor becomes too hot. For explosion proofed actuators the setting has to be specified as 'Respect'. Attention: The parameterization 'Ignore' may result in damage and personal injury. |
1431 |
Respect |
1432 |
Ignore |
1433 |
Torque indication |
1434 |
This Parameter specifies the torque monitoring behaviour during an externally received emergency shutdown command. Respect: Torque monitoring is operating normal. In case of a torque tripping in intermediate positions the actuator will stop with a fault indication. Ignore: Torque monitoring is disabled during external emergency shutdown request. The actuator will drive into the specified direction without monitoring the torque. This will result in an actuator movement with stall torque. If a torque final position cut off is specified in the respective direction the actuator will not stop in final position. In this case the value 'Respect in final positions' should be specified. Respect in final positions: Torque monitoring in intermediate positions is disabled during emergency shutdown. The torque monitoring will be activated if the parameterized final position is reached . |
1435 |
Respect |
1436 |
Respect in final positions |
1437 |
LOCAL mode |
1438 |
If ignored the actuator moves even if the mode is Local. Attention: The parameterization 'Ignore' may result in damage and personal injury. |
1439 |
OFF mode |
1440 |
If ignored the actuator moves even if the mode is OFF. Attention: The parameterization 'Ignore' may result in damage and personal injury. |
1441 |
Actuator run monitor. |
1442 |
If enabled checks whether the position changes if the motor is energised. This indication is reset with a new command or with a fault acknowledgement. |
1443 |
Delay run monit. |
1444 |
Sets the time of the parameter 'Drive start up monitoring'. If the position has not changed significantly before the time elapses, the indication 'Drive start up monit.' is activated. |
1445 |
Reversing delay |
1446 |
Defines the dead time between reversal of rotation direction |
1447 |
Power unit |
1448 |
Sets the type of the used power control unit. Choose the option Standard for standard contactor unit or standard solid state relay. Alternatively the option ATEX can be chosen for all pole disconnecting solid state relay. |
1449 |
Standard |
1450 |
ATEX |
1451 |
Colour LED OPEN |
1452 |
Blue |
1453 |
Green |
1454 |
Red |
1455 |
Yellow |
1456 |
Orange |
1457 |
Cyan |
1458 |
Pink |
1459 |
White |
1460 |
Colour LED Torque OPEN |
1461 |
Colour LED Fault |
1462 |
Colour LED Torque CLOSE |
1463 |
Colour LED CLOSE |
1464 |
Max. runtime torque cut off |
1465 |
Within this time a waypoint must be followed by a torque signal. Otherwise a mechanical fault is assumed and the actuator stops giving an error indication. |
1466 |
Position indication |
1467 |
If enabled, the appropriate Local Lamp (OPEN or CLOSE) is blinking fast, if the motor is energised. |
1468 |
Final positions |
1469 |
Final and Intermediate |
1470 |
Final and Interm. inv. |
1471 |
German |
1472 |
English |
1473 |
Chinese |
1474 |
Spanish |
1475 |
Italian |
1476 |
Dutch |
1477 |
Polish |
1478 |
Russian |
1479 |
Interface board |
1480 |
This parameter specifies if an additional IO board (e.g. fieldbus interface board) is mounted. The parameter has the value 'Yes' if an additional IO board was detected. If the board shall be removed from the actuator, the parameter has to be set to 'No' manually. |
1481 |
No |
1482 |
Yes |
1483 |
Position output |
1484 |
Defines how the position is output: - With 'Over-/underflow' the position is not limited to values between CLOSE and OPEN (see data logging -> high scale value, low scale value) - With 'Limited' the displayed position is limited to the range between CLOSE and OPEN |
1485 |
Data to host |
1486 |
Displays the data of the telegram to the fieldbus master in hexadecimal numbers. Refer to complementary operating manual for actuators with fieldbus systems. |
1487 |
Data from host |
1488 |
Displays the data of the telegram from the fieldbus master in sedecimal numbers. Refer to complementary operating manual for actuators with fieldbus systems. |
1489 |
Baudrate |
1490 |
The actual transmission speed of the fieldbus interface is given |
1491 |
Interface type |
1492 |
Information about the kind of interface card |
1493 |
None |
1494 |
Relays |
1495 |
Profibus |
1496 |
RS485 |
1497 |
Profibus VPC3 |
1498 |
Foundation Fieldbus |
1499 |
NA 6 |
1500 |
NA 7 |
1501 |
DeviceNet 1CH |
1502 |
DeviceNet 2CH |
1503 |
NA 10 |
1504 |
NA 11 |
1505 |
NA 12 |
1506 |
NA 13 |
1507 |
NA 14 |
1508 |
HART |
1509 |
NA 16 |
1510 |
Modbus |
1511 |
Addresses |
1512 |
Shows the actual adress of the actuator. |
1513 |
RTC Enabled |
1514 |
Activation and deactivation of the real time clock |
1515 |
Time |
1516 |
Date |
1517 |
DST |
1518 |
Manual |
1519 |
Automatic |
1520 |
Time zone GMT |
1521 |
Time format |
1522 |
12h |
1523 |
24h |
1524 |
Date format |
1525 |
DD.MM.YYYY |
1526 |
YYYY-MM-DD |
1527 |
MM-DD-YYYY |
1528 |
Show date/time |
1529 |
Time sync. fieldbus |
1530 |
Load factory settings |
1531 |
The factory setting will be loaded |
1532 |
Store factory settings |
1533 |
Stores the settings as factory setting. |
1534 |
Output O1 |
1535 |
Defines the functions of the outputs. The functions can be allocated to the outputs in any way. |
1536 |
Disabled |
1537 |
Final position |
1538 |
Final position CLOSE |
1539 |
Final position OPEN |
1540 |
Pos. b. CLOSE and Int.1 |
1541 |
Pos. b. Int.2 and OPEN |
1542 |
Act. running-permanent |
1543 |
Act. running-flashing |
1544 |
Act. closing-permanent |
1545 |
Act. closing-flashing |
1546 |
Act. opening-permanent |
1547 |
Act. opening-flashing |
1548 |
Actuator not starting |
1549 |
Torque tripping |
1550 |
Torque tripping CLOSE |
1551 |
Torque tripping OPEN |
1552 |
Torque warning |
1553 |
Collective failure 1 |
1554 |
Collective failure 2 |
1555 |
Motor overtemperature |
1556 |
Remote control |
1557 |
OFF |
1558 |
Local control |
1559 |
Emerg. shutdown tripped |
1560 |
Combisensor failure |
1561 |
Int. positioner disabled |
1562 |
Maintenance required |
1563 |
Mode not REMOTE |
1564 |
Handwheel operation |
1565 |
Systemtest fault |
1566 |
Intermediate position 1 |
1567 |
Intermediate position 2 |
1568 |
Intermediate position 3 |
1569 |
Intermediate position 4 |
1570 |
Intermediate position 5 |
1571 |
Intermediate position 6 |
1572 |
Intermediate position 7 |
1573 |
Intermediate position 8 |
1574 |
Fieldbus DOUT1 |
1575 |
Fieldbus DOUT2 |
1576 |
Fieldbus DOUT3 |
1577 |
Fieldbus DOUT4 |
1578 |
PVST active |
1579 |
PVST error |
1580 |
PVST abort |
1581 |
Emergency-STOP |
1582 |
Output O2 |
1583 |
Torque tripping CLOSE |
1584 |
Torque tripping OPEN |
1585 |
Motor overtemperature |
1586 |
Int. positioner disabled |
1587 |
Output O3 |
1588 |
Collective failure 1 |
1589 |
Collective failure 2 |
1590 |
Int. positioner disabled |
1591 |
Output O4 |
1592 |
Output O5 |
1593 |
Output O6 |
1594 |
Output O7 |
1595 |
Logic Output O1 |
1596 |
The physical implementation of the indication outputs are normally open contacts (NO). If configured to normally closed contacts (NC), the relays are powered if the indication is not active, and deenergised if the indication is active. If power fails, these relays are released, and output thus an active signal. |
1597 |
NO contact |
1598 |
NC contact |
1599 |
Logic Output O2 |
1600 |
Logic Output O3 |
1601 |
Logic Output O4 |
1602 |
Logic Output O5 |
1603 |
Logic Output O6 |
1604 |
Logic Output O7 |
1605 |
Dead time |
1606 |
Specifies the minimum impulse time for the digital command inputs. A command must be at least valid for the duration of the parameterized delay in order to take effect. |
1607 |
Command input 1 |
1608 |
Defines the functions of the command inputs. The functions can be allocated to the command inputs in any way. |
1609 |
Stop |
1610 |
CLOSE |
1611 |
OPEN |
1612 |
Automatic |
1613 |
Emerg. shutdown (ESD) |
1614 |
Stepping mode active |
1615 |
Enable LOCAL |
1616 |
Enable REMOTE |
1617 |
Enable CLOSE |
1618 |
Enable OPEN |
1619 |
Fault acknowledge |
1620 |
Force LOCAL |
1621 |
Force LOCAL STOP |
1622 |
Force LOCAL CLOSE |
1623 |
Force LOCAL OPEN |
1624 |
Execute PVST |
1625 |
Command input 2 |
1626 |
Command input 3 |
1627 |
Command input 4 |
1628 |
Logic Command inp.1 |
1629 |
Defines if the command is active with 24 V DC (high-active) or with 0 V (low-active). |
1630 |
high-active |
1631 |
low-active |
1632 |
Logic Command inp. 2 |
1633 |
Logic Command inp. 3 |
1634 |
Logic Command inp. 4 |
1635 |
Analogue output 1 |
1636 |
Defines which kind of information should be output as a 4...20 mA signal using analogue output 1. The calibration of the analogue signals - only possible for position output - can be done using the parameters of the Learn mode. The possible parameters are situated in the submenu 'Analogue signal>output', and include 'Value 100%' and 'Value 0%'. Those parameters have the same effect on output 1 and 2. The range for the analogue signals is: -Position: CLOSE...OPEN -torque: Depending on the configuration of the parameter 'Data logging>Torque sign' either -100%...+100%, or 0...100% Electronic temperature: -25°C...+100°C |
1637 |
Position |
1638 |
Electronic temperature |
1639 |
Fieldbus AOUT1 |
1640 |
Current Flow |
1641 |
Indicates if the connection type is 'Actuator' and a current source (Low Impedance) is detected, or when the connection type is 'Current Output' a current sink (High Impedance) is detected. If no current signal is detected, the value 0 (No Impedance) is reported. |
1642 |
No Impedance |
1643 |
Low Impedance |
1644 |
High Impedance |
1645 |
Device Conn. Type |
1646 |
Defines the Device Connection Type of the actuator. The default value of the DREHMO actuator is the type: Actuator. The following type exists: 0 = Not defined 1 = Current Input 2 = Current Output 3 = Voltage Input 4 = Voltage Output 5 = Secondary 6 = Transmitter 7 = Actuator 8 = Non-DC Isolated Bus Device 9 = DC Isolated Bus Device |
1647 |
Not defined |
1648 |
Current Input |
1649 |
Current Output |
1650 |
Voltage Input |
1651 |
Voltage Output |
1652 |
Secondary |
1653 |
Transmitter |
1654 |
Actuator |
1655 |
Non-DC Iso Bus Dev |
1656 |
DC Iso Bus Dev |
1657 |
AnaIn Current Zero |
1658 |
Reference value for 4 mA, which is used for calculation of the loop current (trimming) from the physical input signal. |
1659 |
AnaIn Current Span |
1660 |
Reference value for 20 mA, which is used for the calculation of the loop current (trimming) of the physical input signal. |
1661 |
AnaOut Current Zero |
1662 |
Reference value for 4 mA, which is used for the correction (trimming) the internal loop current from the generated physical output signal. |
1663 |
AnaOut Current Span |
1664 |
Reference value for 20 mA, which is used for the correction (trimming) of the internal loop current from the generated physical output signal. |
1665 |
AnaIn LRV |
1666 |
With this function it is possible to set the range of the input current between -250% and +250%. |
1667 |
AnaIn URV |
1668 |
AnaOut LRV |
1669 |
AnaOut URV |
1670 |
With this function it is possible to set the range of the input current between -250% and +250%. |
1671 |
Polling Address |
1672 |
Identify unique addresses of all devices. The address values between 0 and 64. |
1673 |
Loop Current Mode |
1674 |
In Low Impedance Mode and 'Loop Current Mode'= Enabled (Defaultvalue) should the actuator drive by analog inputsignal. When parameter 'Loop Current Mode'= Disabled the actuator drives with the HART commands OPEN, CLOSE, SETPOINT. The parameter defines, if analog signal will be used or not. |
1675 |
Disabled |
1676 |
Enabled |
1677 |
BusAct Timeout |
1678 |
The Busactivity timeout should be configured from range 1 to 3600 sec. (default: 15 sec.). |
1679 |
APP FW-Version |
1680 |
Firmware version of LPT-Application from HART-Board. |
1681 |
Stack FW-Version |
1682 |
Firmware version of the HART-Stack. |
1683 |
IAP FW-Version |
1684 |
Firmware version of STM-Application (In-Application Program IAP) from HART-Board. |
1685 |
Manufacturer ID |
1686 |
Indicates the company that produced the device. Manufacturer Ids are allocated by the HART Communication Foundation. Only the designated manufacturer may use this ID. |
1687 |
Expanded Device Type |
1688 |
Indicates the type of the device (i.e., the product name). The 'Expanded Device Type' indicates the set of commands and data items supported by the Field Device. |
1689 |
Device ID |
1690 |
A number unique to a particular field device. This number must be different for every device produced with a given Device Type. |
1691 |
Device Revision Level |
1692 |
A whole Number indicating the revision level of command and data item set for this Device Type. |
1693 |
Software Revision Level |
1694 |
An unsigned integer indicating the revision level of the frmware in the field device. An increment of the revision number must occur for every released version of the field device's firmware. |
1695 |
Hardware Revision Level |
1696 |
An unsigned integer indicating the major revision level of the hardware in the field device. |
1697 |
Protocol Major Rev. Nr. |
1698 |
The HART Stack is kompatible with Protocol Revision 7.4 (Major Revision 7). |
1699 |
Identity Tag |
1700 |
An 8-character label assigned by the end user based on location and use of the field device. The Tag supports only the Packed ASCII character set. |
1701 |
Long Tag |
1702 |
A 32-character label assigned by the end user based on location and use of the field device. The Long Tag supports ISO Latin-1 characters from DCS. |
1703 |
Message |
1704 |
During commissioning the configurator write a message into the device for documentation. This process called 'As Installed Record Keeping'. |
1705 |
Date Code |
1706 |
Describe a date code, which only will be written by DCS-System. |
1707 |
Descriptor |
1708 |
Describe a 16 Byte Device Description value in ASCII format. Via HART will 12 Byte communicated in ASCII Packet format. |
1709 |
Final Assembly Nr |
1710 |
The Final Assembly Number is a 24-bit number (0...16.777.215) and will be used for administration of the device in the plant. |
1711 |
Req. Msg. Preamble Len. |
1712 |
Minimum number of Preambles required for the request message from the Master to the Slave. |
1713 |
Res. Msg. Preamble Len. |
1714 |
Minimum number of Preambles required for the response message from the Slave to the Master. |
1715 |
Config. Change Counter |
1716 |
The Configuration Change Counter must be incremented once for every command received thath changes the device configuration. The counter must also be incremented once for every user action that changes the device's configuration or calibration (e.g., from local operator interface). This value is never reset or written and must be maintained even if power is removed from the device or a device reset is performed. |
1717 |
Config. Changed Bit PM |
1718 |
If Configuration Change Counter has been incremented, then the Configuration Changed Bit for Primary Master (PM) will be set. |
1719 |
Config. Changed Bit SM |
1720 |
If Configuration Change Counter has been incremented, then the Configuration Changed Bit for Secondary Master (SM) will be set. |
1721 |
Wireless HART Adapter |
1722 |
If the parameter 'WirelessHART Adapter' is set to value 0 (Disabled), the power supply of 24V for the wireless adapter will be interrupted. Otherwise the voltage is provided when the system is ready for operation. |
1723 |
CurrentOut Resistor |
1724 |
If the parameter 'Current Out Resistor' has the value 0 (Disabled) the additional resistor is disabled by the switch S2 on the HART module. Otherwise it is enabled. |
1725 |
OFF mode |
1726 |
The actuator is in the OFF mode. The drive can not motor-driven. ATTENTION: Special rules may optionally be configured for fail-safe functions and ESD! |
1727 |
LOCAL mode |
1728 |
The acutator is in local mode. The actuator can be operated locally. The local method can be locked of remote DCS. Special arrangements may optionally be configured for fail-safe functions and ESD! |
1729 |
REMOTE mode |
1730 |
The actuator is in the REMOTE mode and can not be moved by DCS. |
1731 |
Mode not REMOTE |
1732 |
The actuator is not in mode REMOTE. |
1733 |
LEARN mode |
1734 |
The actuator is in LEARN mode. The actuator can be operated locally. The sensor calibration for the limit and torque detection can be performed. The local mode can be locked by a remote DCS. The fail-safe and ESD mechanisms are not available in this mode! For this mode, there are different access rights. |
1735 |
Service active |
1736 |
Future Use !!! At AUMA: For operation via service interface (Bluetooth) and service software AUMA Tool Suite. |
1737 |
Actuator running |
1738 |
The power unit of the drive is actuated. |
1739 |
Actuator running OPEN |
1740 |
The power unit of the drive is actuated in direction OPEN. |
1741 |
Actuator running CLOSE |
1742 |
The power unit of the drive is actuated in direction CLOSE. |
1743 |
Stepmode active |
1744 |
A stepmode is parameterized in direction OPEN or CLOSE and the following condition is also given: The process parameters 'clock source' is ' internal', or the process parameters 'clock source' is set to external and remote command 'clock mode active' is set. |
1745 |
Actuator in Stepmode |
1746 |
The actuator is in the range in which the stepmode is active. |
1747 |
Stepbreak active |
1748 |
The actuator stopped during stepmode operation. |
1749 |
The predefined setpoint is reached. |
1750 |
Limit Switch OPEN |
1751 |
The actuator is in a position outside the working range or not on position OPEN. |
1752 |
Limit Switch CLOSE |
1753 |
The actuator is in a position outside the working range or not on position CLOSE. |
1754 |
Limit reached |
1755 |
The actuator is in a position outside the working range or not on position OPEN and CLOSE. |
1756 |
Signal Limit OPEN |
1757 |
Signals the end position OPEN according to the setting of the 'end position'. Forms: 'travel position' or 'Switching off mode'. |
1758 |
Signal Limit CLOSE |
1759 |
Signals the end position CLOSE according to the setting of the 'end position'. Forms: 'travel position' or 'Switching off mode'. |
1760 |
Limit OPEN |
1761 |
Final position for OPEN, depends on the parameterized direction. With configured shutdown via limit switch this signal indicates when the endposition is exceeded. With configured torque shutdown the signal indicates the end position only if the tripping torque in direction OPEN is exceeded. |
1762 |
Limit CLOSE |
1763 |
Final position for CLOSE, depends on the parameterized direction. With configured shutdown via limit switch this signal indicates when the endposition is exceeded. With configured torque shutdown the signal indicates the end position only if the tripping torque in direction CLOSE is exceeded. |
1764 |
Torque OPEN |
1765 |
The torque measurement provides a value that is greater than the parameterized tripping torque OPEN. The signal is independent of other parameterizations. |
1766 |
Torque CLOSE |
1767 |
The torque measurement provides a value that is greater than the parameterized tripping torque CLOSE. The signal is independent of other parameterizations. |
1768 |
Signal Torque OPEN |
1769 |
The torque measurement provides a value that is greater than the parameterized tripping torque OPEN. The signal is indicated always in intermediate positions and only in final position, when the parameter 'torque indication' has the value 'Ind. in final positions'. |
1770 |
Signal Torque CLOSE |
1771 |
The torque measurement provides a value that is greater than the parameterized tripping torque CLOSE. The signal is indicated always in intermediate positions and only in final position, when the parameter 'torque indication' has the value 'Ind. in final positions'. |
1772 |
Signal Torque |
1773 |
Or function of the signals 'Signal Torque OPEN' and 'Signal Torque CLOSE'. |
1774 |
Torque failure OPEN |
1775 |
The torque measurement provides a value that is greater than the parameterized tripping torque OPEN. The signal is indicated always in intermediate positions and only in final position, when the parameter 'Switching off mode' has the value 'Final position limit sw.'. |
1776 |
Torque failure CLOSE |
1777 |
The torque measurement provides a value that is greater than the parameterized tripping torque CLOSE. The signal is indicated always in intermediate positions and only in final position, when the parameter 'Switching off mode' has the value 'Final position limit sw.'. |
1778 |
Torque failure |
1779 |
Or function of the signals 'Torque failure OPEN' and 'Torque failure CLOSE'. |
1780 |
Torque warning OPEN |
1781 |
The torque measurement provides a value that is greater than the configured warning torque OPEN. The signal is independent of other parameterizations. |
1782 |
Torque warning CLOSE |
1783 |
The torque measurement provides a value that is greater than the configured warning torque CLOSE. The signal is independent of other parameterizations. |
1784 |
Torque warning |
1785 |
Or function of the signals 'Torque warning OPEN' and 'Torque warning CLOSE'. |
1786 |
Signal torque warning OPEN |
1787 |
The torque measurement provides a value that is greater than the configured warning torque OPEN. The torque measurement provides a value that is greater than the configured warning torque OPEN. The signal is indicated always in intermediate positions and only in final position, when the parameter 'Switching off mode' has the value 'Final position limit sw.'. |
1788 |
Signal torque warning CLOSE |
1789 |
The torque measurement provides a value that is greater than the configured warning torque CLOSE. The torque measurement provides a value that is greater than the configured warning torque CLOSE. The signal is indicated always in intermediate positions and only in final position, when the parameter 'Switching off mode' has the value 'Final position limit sw.'. |
1790 |
Signal torque warning |
1791 |
Or function of the signals 'Signal torque warning OPEN' and 'Signal torque warning CLOSE'. |
1792 |
Device OK |
1793 |
Future Use |
1794 |
Emerg. shutdown (ESD) |
1795 |
An external ESD command is active and the currently configured ESD action is active. The execution of the ESD action is not blocked by a potentially operating mode, nor by a potentially motor overtemperature. |
1796 |
Fail safe active |
1797 |
The actuator is in internally generated state Fail-safe. This is only set in the mode REMOTE, when the external setpoint falls below a threshold value or the field communication failure have occured. |
1798 |
Emergency-STOP |
1799 |
Indicates an external Emergency-Stop signal. |
1800 |
Int. positioner disabled |
1801 |
The actuator can be operated from REMOTE only with discrete commands. To activate the internal positioner the bit Automatic must be active. A local fault H1 (entry in Fault Register Book) is generated only when the signal is mapped into the collective fault 1. |
1802 |
Interlock LOKAL active |
1803 |
One of the signals 'Enable LOCAL', 'Enable LOCAL OPEN' or 'Enable LOCAL CLOSE' is assigned to a command input and inactive. Drive the actuator in operating mode LOCAL is limited. |
1804 |
Interlock REMOTE active |
1805 |
One of the signals 'Enable REMOTE', 'Enable REMOTE OPEN' or 'Enable REMOTE CLOSE' is assigned to a command input and inactive. Drive the actuator in operating mode REMOTE is limited. |
1806 |
Handwheel operation |
1807 |
An actuator movement without activation of the power unit but with handwheel operation is present. |
1808 |
Acutator in LOCAL mode |
1809 |
The actuator is in LOCAL mode and the power unit is used. |
1810 |
Acutator in LOCAL mode OPEN |
1811 |
The actuator is in LOCAL mode and the power unit is used in direction OPEN. |
1812 |
Acutator in LOCAL mode CLOSE |
1813 |
The actuator is in LOCAL mode and the power unit is used in direction CLOSE. |
1814 |
Drives from REMOTE |
1815 |
The actuator is in the REMOTE mode and the power unit is active. |
1816 |
Local STOP |
1817 |
Find Device |
1818 |
Singals that the actuator is in a mode, which response all broadcast messages with it own device id. |
1819 |
Intermediate position 1 |
1820 |
Indication of the intermediate position according to the adjusted signal behavior. |
1821 |
Intermediate position 2 |
1822 |
Intermediate position 3 |
1823 |
Intermediate position 4 |
1824 |
Intermediate position 5 |
1825 |
Intermediate position 6 |
1826 |
Intermediate position 7 |
1827 |
Intermediate position 8 |
1828 |
Actual position |
1829 |
Actual actuator position in the range 0 ... 10000 (Format: Integer), scaled between the educated final positions CLOSE and OPEN. With the parameter 'Position output' from the Addon-Card it is possible to set the format form the actual position. The values from 'Position output' are 'Limited' or 'Over-/underflow'. Different from the other analog values is the scaling to the special applications (sealing gap control, etc.). |
1830 |
Torque actual value |
1831 |
Get the actual value of torque at the output. The format of the value is percent of the acutator's nominal torque (0% - 100%). |
1832 |
Delay run monitoring |
1833 |
The controll unit of the actuator does not register any movement despite activation of the power unit. |
1834 |
Rotation monitoring |
1835 |
The control of the actuator's power unit registers a movement in the wrong direction. |
1836 |
Op-time survey |
1837 |
Or function of the signals 'Op-time survey OPEN' and 'Op-time survey CLOSE'. |
1838 |
Op-time survey OPEN |
1839 |
The operating data for the current operating time survey in direction OPEN exceeds the configured valve limit. |
1840 |
Op-time survey CLOSE |
1841 |
The operating data for the current operating time survey in direction CLOSE exceeds the configured valve limit. |
1842 |
Overtemperatur trip |
1843 |
The motor protection trips by motor overtemperature. The release may be delayed due the actuator parameter 'Thermal failure delay'. To reset the behavior set the parameter 'Thermal failure reset'. |
1844 |
Collective failure 1 |
1845 |
The 'Collective failure 1' can collect different signals with OR-functions. There appears an exclamation point as warning on LCD. This indication is self-resetting. |
1846 |
Collective failure 2 |
1847 |
The 'Collective failure 2' can collect different signals with OR-functions. There appears an exclamation point as warning on LCD. This indication is self-resetting. |
1848 |
Fahrbefehl abgewiesen |
1849 |
Occurs, if the command OPEN / CLOSE are excecute while setpoint and Automatic Bit are given in operating mode with internal positioner. |
1850 |
Configuration invalid |
1851 |
One or more of the following parameter settings are invalid: - The device key of the electronic name plate is invalid. - The torques specified on the device key are implausible. - The parameterized tripping torque OPEN exceeds the maximum input torque OPEN for the valve - The parameterized tripping torque CLOSE exceeds the maximum input torque CLOSE for the valve - The parameterized tripping torque CLOSE / OPEN exceeds the configured maximum input torque for gear / thrust unit. - In case of a Profibus the redundancy concept has been configured via DPV2 for the redundancy concept, although the required DPV2 functionality hasn't been enabled on the device key. |
1852 |
Device Key invalid |
1853 |
The parameterized device key in the electronic nameplate of the actuator control is invalid. |
1854 |
Discrepancy error |
1855 |
There is a discrepancy monitored between the electrical signals and the read-back signals in the hardware monitoring of the power unit. |
1856 |
Wrong power unit |
1857 |
A wrong power unit has been occured based on the evaluation of an hardware encoding as specified in the configuration. |
1858 |
RTC not set |
1859 |
Future Use |
1860 |
Torque of Gear / thrust unit |
1861 |
The parameterized Tripping torque OPEN / CLOSE exceeds the allowable input torque of the gear unit. |
1862 |
Torque valve OPEN |
1863 |
The parameterized tripping torque of the valve exceeds the allowed maximum torque OPEN. |
1864 |
Torque valve CLOSE |
1865 |
The parameterized tripping torque of the valve exceeds the allowed maximum torque CLOSE. |
1866 |
Hardware error |
1867 |
An error of hardware components has occurred and the hardware has been evaluated as a defect. |
1868 |
HW Interface error |
1869 |
An error of the interface module used has been occurred and it has been evaluated as defect. |
1870 |
Systemtesterror |
1871 |
During self-examination of the Hard.- and Software the contro unitl has detected an error and then performed a system reset. - The error indication can reset via slot 1, index 240 from REMOTE with a Profibus interface. The error type can read over the acyclic services 'System test error code' from slot 1, index 195. - The error message can LOCAL using the function System > Reset, or by an off-on switch cycle reset. The error type can be retrieved in local menu under the actual values / diagnosis. - This message is important for safety-related systems when the actuator must drive to a safe position due an pending error. |
1872 |
Sensor failure |
1873 |
During self-diagnosis of the combi sensor for position.- and torque sensing a fault has been detected, and the sensor has been defined as not working. Actuator movement is not possible and may be canceled. It tries out a new hardware configuration of the sensor to correct the error. The indication is self-resetting at troubleshooting. |
1874 |
Range overflow |
1875 |
At more than 1490 rotations of the hollow shaft, this signal enters. |
1876 |
Nomansland |
1877 |
Appears when the sensor position is below -50% or over +150%. |
1878 |
position calibration error |
1879 |
Error during calibration of the combi sensor. |
1880 |
Torque calibration error |
1881 |
Electronics overtemperature |
1882 |
The measured temperature on base board exceeds the 'max. electronics temperature'. |
1883 |
Battery module fault |
1884 |
An error in the optional battery module is present. More information available under actual values / diagnosis > Battery Backup. |
1885 |
NV-Memory error |
1886 |
An error occurred has occurred while accessing on the internal volatile memory . |
1887 |
Or function of the signals 'Phase 1 failure', 'Phase 2 failure' and 'Phase 3 failure'. |
1888 |
Phase 1 failure |
1889 |
Phase 1 of the power supply has failed. |
1890 |
Phase 2 failure |
1891 |
Phase 2 of the power supply has failed. |
1892 |
Phase 3 failure |
1893 |
Phase 2 of the power supply has failed. |
1894 |
Phase sequence failure |
1895 |
A phase sequence can not be detected automatically. |
1896 |
24V internal failure |
1897 |
The required AC voltage on the secondary side of the power transformer not present. The controller could be alternatively supplied via an external power supply. The control of reversing contactor units as a power unit is not possible due to the pending error. |
1898 |
24V external failure |
1899 |
The external 24V DC power supply is not connected. |
1900 |
Maintenance required |
1901 |
Collective message of various operating data counters and maintenance messages. This signal is present when one of the following limits are exceeded: - Limit valve stroke - Accum. operation cycles - Thermal aging - Mechanical aging |
1902 |
Limit valve stroke |
1903 |
The value of the operating data counter 'valve stroke' exceeds the associated configurable limit 'Limit valve stroke'. |
1904 |
Accum. operation cycles |
1905 |
The value of the operating data counter 'operation cycles' exceeds the associated configurable limit 'limit operation cycles'. |
1906 |
Actual op. cycles/h |
1907 |
The value of the operating data counter 'Actual op. cycles/h' exceeds the associated configurable limit 'Limit op. cycles/h'. |
1908 |
Dynamic maintenance |
1909 |
Or function of the signals 'mechanical aging' and 'thermal aging'. |
1910 |
Mechanical aging |
1911 |
The value for the mechanical aging exceeds the associated limit value for mechanical aging and activate the dynamic service message. |
1912 |
Thermal aging |
1913 |
The value for the thermal aging exceeds the associated limit for the thermal aging and activate the service message. |
1914 |
Dyn. Consumptionvar. |
1915 |
0..100% consumption of the collective confidence of the dynamic maintenance message. This variable indicates the highest relative consumption to the limit of thermal aging or mechanical aging. |
1916 |
Warning mains quality |
1917 |
Warning temperature |
1918 |
Warning humidity |
1919 |
Warning dew point |
1920 |
Warning vibration |
1921 |
Warning duty cycle value |
1922 |
Channel 1 activity |
1923 |
On channel 1 it has been valid data (baud rate found) detected of the connected fieldbus system. |
1924 |
Channel 2 activity |
1925 |
On channel 2 it has been valid data (baud rate found) detected of the connected fieldbus system. |
1926 |
Channel 1 DataEx |
1927 |
On channel 1 of the connected fieldbus is a validated data exchange with the host (data exchange). |
1928 |
Channel 2 DataEx |
1929 |
On channel 2 of the connected fieldbus is a validated data exchange with the host (data exchange). |
1930 |
Channel 1 active |
1931 |
Channel 1 of the connected fieldbus system is the active channel. The signals of this channel are used for remote control of the actuator. |
1932 |
Channel 2 active |
1933 |
Channel 2 of the connected fieldbus system is the active channel. The signals of this channel are used for remote control of the actuator. |
1934 |
CLEAR Channel 1 |
1935 |
All outputs of the hosts on the fieldbus channel 1 in the device (slave) are reset (Global Control Clear). |
1936 |
CLEAR Channel 2 |
1937 |
All outputs of the hosts on the fieldbus channel 2 in the device (slave) are reset (Global Control Clear). |
1938 |
AnaIn1 |
1939 |
0 ... 1000ppt the analog input 1, scaled between 4 ... 20 mA. |
1940 |
AnaIn2 |
1941 |
0 ... 1000ppt the analog input 2, scaled between 4 ... 20 mA |
1942 |
Dig. I/O Input 1 |
1943 |
Status of digital input 1. |
1944 |
Dig. I/O Input 2 |
1945 |
Status of digital input 2. |
1946 |
Dig. I/O Input 3 |
1947 |
Status of digital input 3. |
1948 |
Dig. I/O Input 4 |
1949 |
Status of digital input 4. |
1950 |
Dig. I/O Input 5 |
1951 |
Status of digital input 5. |
1952 |
Dig. I/O Input 6 |
1953 |
Status of digital input 6. |
1954 |
Status actual position |
1955 |
1 = ok, 0 = nok |
1956 |
Status AnaIn 1 |
1957 |
Status channel AnaIog Input 1. |
1958 |
Status AnaIn 2 |
1959 |
No setpoint available |
1960 |
It is not a valid setpoint for the internal positioner available. |
1961 |
Status Feldbus Channel 1 |
1962 |
Error state of the channel 1. |
1963 |
Status Feldbus Channel 1 |
1964 |
Error state of the channel 2. |
1965 |
Signal loss ParallelIfa AnaIn1 |
1966 |
Signal loss ParallelIfa AnaIn2 |
1967 |
PVST active |
1968 |
Future Use |
1969 |
PVST abort |
1970 |
PVST warning |
1971 |
Backflushing |
1972 |
Drives the actuator in direction OPEN when a discrete command from remote is released. It must be mode REMOTE active. If the type of the control is 'Int. positioner' and the parameter has the value 'Enabled V005', it must be reset the 'Automatic-bit'. The signal behavior can configured under menu item 'Control'. |
1973 |
Drives the actuator in direction CLOSE when a discrete command from remote is released. It must be mode REMOTE active. If the type of the control is 'Int. positioner' and the parameter has the value 'Enabled V005', it must be reset the 'Automatic-bit'. The signal behavior can configured under menu item 'Control'. |
1974 |
STOP |
1975 |
Stops the actuator when a discrete command from remote is released. It must be mode REMOTE active. If the type of the control is 'Int. positioner' and the parameter has the value 'Enabled V005', it must be reset the 'Automatic-bit'. The signal behavior can configured under menu item 'Control'. |
1976 |
automatic mode |
1977 |
Enables the integrated 3-point positioner, and allows driving the actuator via setpoint if the parameter 'Int. positioner' has the value 'Enabled V005'. |
1978 |
Stepping mode |
1979 |
Enables the step mode for extending the cycle time if the process parameters 'clock source' has the value 'External'. |
1980 |
Emergency Shutdown (ESD) |
1981 |
Enables Emergency shutdown 'ESD' of the actuator, if it is not deactivated by the control parameter 'Emergency shutdown ESD'. It is possible to enable the function in LOCAL or OFF mode by parameterization. The actuator's behavior for a possible torque or motor over-temperature shutdown can be parameterized. The control mode is always the 'Jog' even if 'Modal' is parameterized. For the ESD command is an enabled configured 'Edge detection REMOTE' inactive. This result change in a mode with different behavior as in the run command OPEN, CLOSE. |
1982 |
Activates the emergency STOP function. |
1983 |
Fieldbus enable REMOTE |
1984 |
Enable driving the actuator from REMOTE. |
1985 |
Fieldbus enable REMOTE OPEN |
1986 |
Enable driving the actuator from REMOTE in driection OPEN. |
1987 |
Fieldbus enable REMOTE CLOSE |
1988 |
Enable driving the actuator from REMOTE in driection CLOSE. |
1989 |
Fault acknowledge |
1990 |
Alternative reset mechanism for selected stored faults from REMOTE: - Reset command for a torque OPEN / CLOSE error instead of an acknowledge from a run command in opposite direction. - Reset command for a tripped 'Delay run monitoring error' instead of a new edge in the run command - Reset command for a tripped Phase 1, Phase 2 or Phase 3 error if the parameter 'phase failure monitoring' has not the value self-resetting. |
1991 |
Change fieldbus channel |
1992 |
Iin the case of an existing redundant fieldbus changes the connection with a pass from logic 0 to logic 1 the active channel, if a valid data exchange takes place on the other channel. |
1993 |
Partial Stroke |
1994 |
Default LOCAL |
1995 |
This signal allows an alternative REMOTE operation in a special mode 'Default LOCAL' via additional discrete commands 'Default LOCAL STOP', 'Default LOCAL CLOSE' and 'Default LOCAL OPEN'. The signals have only effects if the actuator is in the REMOTE mode and there is no blocking of the local operation. Because of an input signal changes the mode under these conditions to 'Default LOCAL'. The control over the discrete commands OPEN, CLOSE or setpoint are in REMOTE mode not possible as long as the signal is present. |
1996 |
Default LOCAL STOP |
1997 |
Stops the actuator, when control via the command 'Default LOCAL CLOSE' or 'Default LOCAL OPEN' is active in the 'Default LOCAL'. |
1998 |
Default LOCAL CLOSE |
1999 |
Drives the actuator in the mode 'Default LOCAL' in direction CLOSE. The command is usually performed in the jog-mode. If the command input has been configured as 'Default LOCAL STOP' works it with self-latching. |
2000 |
Default LOCAL OPEN |
2001 |
Drives the actuator in the mode 'Default LOCAL' in direction OPEN. The command is usually performed in the jog-mode. If the command input has been configured as 'Default LOCAL STOP' works it with self-latching. |
2002 |
Drive the actuator to the parameterized intermediate position via the internal positioner. |
2003 |
Setpoint value |
2004 |
0..1000ppt setpoint, scalled between end position CLOSED and OPEN. |
2005 |
Process actual value |
2006 |
Position value 0 ... 1000 ppt, scaled between end position CLOSED and AUF. Prozess actual value |
2007 |
Fieldbus AOUT |
2008 |
Transmitting an analog value from the DCS to the relay board of control. Scales in 0..1023 for 4-20mA. |
2009 |
Channel 1 active |
2010 |
Channel 1 active. |
2011 |
Channel 2 active. |
2012 |
Channel 1 DataEx |
2013 |
Dataexchange on channel 1. |
2014 |
Channel 2 DataEx |
2015 |
Dataexchange on channel 2. |
2016 |
Channel 1 Fail-State |
2017 |
Channel 1 fail-state fieldbus (0=OK; 1= fail-safe) |
2018 |
Channel 2 Fail-State |
2019 |
Channel 2 fail-state fieldbus (0=OK; 1= fail-safe) |
2020 |
Channel 1 Busactivity |
2021 |
Data transmission on channel 1. |
2022 |
Channel 2 Busactivity |
2023 |
Data transmission on channel 2. |
2024 |
Redundancy |
2025 |
The interface module has 2 channels (display in MMI). |
2026 |
Fail-safe |
2027 |
The interface module requests the state fail-safe. |
2028 |
Simulate |
2029 |
The actuator can be simulated via fieldbus (0 = OFF, 1 = ON). |
2030 |
DataEx Fieldbus |
2031 |
The fieldbus is in data exchange and receives valid telegrams from the control system. |
2032 |
Squawk |
2033 |
If Squawk message is indicated all LEDs without the Bluetooth LED are flashing on display board (iMC02). |
2034 |
Optical Fiber Error |
2035 |
A possibly installed fiber optic module reports a general error. |
2036 |
Optical Fiber Budget Channel 1 |
2037 |
Warning: FO cable system reserve reached (critical or permissible Rx receive level). |
2038 |
Optical Fiber Error Channel 1 |
2039 |
Optical receiving signal (no or insufficient Rx receive level) or RS-485 format error. |
2040 |
Optical Fiber Budget Channel 2 |
2041 |
Optical Fiber Error Channel 2 |
2042 |
Not ready remote |
2043 |
Signalisiert das der Antrieb nicht über Feldbus verfahren werden kann. Sammlemeldung aus den Bytes 12 und 13. |
2044 |
Signalisiert eine Warnung im Gerät. Sammelmeldung aus den Bytes 16, 17, 18 und 19. |
2045 |
Error |
2046 |
Signalisiert einen Fehler im Gerät. Sammelmeldung aus Bytes 14 und 15. |
2047 |
NAMUR Meldung 'Wartungsbedarf' ist gesetzt, wenn das Ausgangssignal zwar noch gültig ist, aber der Abnutzungsvorrat demnächst erschöpft oder aufgrund von Einsatzbedingungen eine Funktion in Kürze eingeschränkt sein, z. B. Alterung der pH-Elektrode. |
2048 |
Out of specification |
2049 |
NAMUR Meldung 'Außerhalb der Spezifikation' ist gesetzt, wenn vom Gerät durch Selbstüberwachung ermittelte Abweichungen von den zulässigen Umgebungs-, Prozessbedingungen oder Störungen im Gerät darauf hinweisen, dass die Sollwertabweichung bei Aktoren wahrscheinlich größer ist als wie unter den normalen Betriebsbedingungen. |
2050 |
function check |
2051 |
NAMUR Meldung 'Funktionskontrolle' ist gesetzt, wenn am Feldgerät gearbeitet wird, das Ausgangssignal ist daher vorübergehend ungültig (z.B. eingefroren). |
2052 |
Failure |
2053 |
NAMUR Meldung "Funktionskontrolle" ist gesetzt, wenn aufgrund einer Funktionsstörung im Feldgerät oder an seiner Peripherie das Ausgangssignal ungültig ist. |
2054 |
Zeigt an das kein Fehler im System ist |
2055 |
Wrong operation command |
2056 |
Falls z.B. AUF/ZU Befehl gleichzeitig im Betrieb als Fahrbefehl an den Antrieb weitergleitet werden. In der iMC handhaben die Busplatinen diese Logik und nicht die Basisplatine. |
2057 |
Antrieb ist nicht in Betriebsart FERN. |
2058 |
Interlock active |
2059 |
Verriegelt den Betrieb über Feldbus. |
2060 |
Der Antrieb wurde lokal gestoppt. |
2061 |
EMERGENCY stop active |
2062 |
Eine externe Not HALT Anforderung liegt am Antrieb an. |
2063 |
EMERGENCY shutdown |
2064 |
Ein externer ESD Befehl steht an und die aktuell parametrierte ESD Aktion ist aktiv, wobei die Ausführung der ESD Aktion weder durch eine möglicherweise ausschließende Betriebsart, noch durch eine möglicherweise ausschließende Motorübertemperatur blockiert ist. |
2065 |
Der Antrieb befindet sich im intern generierten Zustand Fail-safe. Dieser wird ausschließlich in der Betriebsart FERN, bei Unterschreitung eines Grenzwertes der externen Sollwertvorgabe oder bei Feldbuskommunikationsausfall, gesetzt. |
2066 |
I/O interface |
2067 |
Signalisiert das der Antrieb über die zusätzlich analogen oder digitalen Ein-/ausgänge betrieben wird. |
2068 |
Patrial Stroke Test Betrieb. |
2069 |
Wartung aktiv. |
2070 |
Handwheel active |
2071 |
Armatur wird per Handrad betätigt. |
2072 |
Configuration error |
2073 |
Fehlerhafte Einstellungen der PRM vorgenommen. |
2074 |
Mains quality |
2075 |
HW-Komponente als defekt erkannt |
2076 |
Motorschutz hat ausgelöst wegen Motorübertemperatur |
2077 |
Phase fault |
2078 |
Eine der drei Phasen ist ausgefallen |
2079 |
Torque fault OPEN |
2080 |
Torque fault CLOSE |
2081 |
Internal fault |
2082 |
Bei Selbstüberprüfung hat die Steuerung einen Fehler festgestellt, einen Reset durchgeführt und versucht den fail-safe einzunehmen |
2083 |
No reaction |
2084 |
Zustandsmeldung |
2085 |
Phase correction |
2086 |
Collective failure 1 |
2087 |
Sammelstörung 1 |
2088 |
Sensor defect |
2089 |
Kombisensor EM6 ist nicht funktionstüchtig |
2090 |
Incorrect phase sequence |
2091 |
Antrieb dreht richtig oder falsch herum. |
2092 |
Torque Wrn CLOSE |
2093 |
Torque Wrn OPEN |
2094 |
Wrn controls temperature |
2095 |
Kritische Temperatur in der Strg (Elektornik Übertemperatur) |
2096 |
Wrn gearbox temperature |
2097 |
Kiritische Temp. im Getriebe |
2098 |
Wrn motor temperature |
2099 |
Kritische Temperatur am Motor |
2100 |
24 V DC external |
2101 |
Externe Speisespannung liegt nicht an. |
2102 |
24 V DC internal |
2103 |
Elektronik wird nicht mehr aus Anschlussnetz versorgt. |
2104 |
Collective failure 2 |
2105 |
Sammelstörung 2. |
2106 |
Wrn RTC not set |
2107 |
Realtime Clock nicht gesetzt. |
2108 |
Konfiguration ungültig |
2109 |
Warning LWL budget |
2110 |
Warnung der Lichtstärke |
2111 |
Warning LWL circle |
2112 |
LWL Ring unterbrochen |
2113 |
Warning input AIN 1 |
2114 |
Warnung am analog Eingang. |
2115 |
Warning input AIN 2 |
2116 |
Warnung am analog Eingang |
2117 |
Internal warning |
2118 |
Analog zum internen Fehler gibt es auch eine interne Warnung. Überprüft wird der Systemtestfehler. |
2119 |
Wrn on time starts |
2120 |
Warnung bei den Anläufen. |
2121 |
Wrn on time running |
2122 |
Warnung bei der Laufzeit |
2123 |
Operation time warning |
2124 |
Stellzeit größer als die Zeit für Laufzeitüberwachung |
2125 |
Wrn setpoint position |
2126 |
Kein Sollwert vorhanden. |
2127 |
Failure behaviour active |
2128 |
Antrieb befindet sich im Modus fail save. |
2129 |
PVST fault |
2130 |
FAULT |
2131 |
Signalisiert einen Fehler im System |
2132 |
Maintenance necessary |
2133 |
Wartung erforderlich |
2134 |
Berechnet den Verschleiß der internen Getriebekomponenten. |
2135 |
Berechnet aus der gemessenen Elektroniktemperatur die Alterung der Dichtungselemente. |
2136 |
Valve stroke |
2137 |
Gibt den akkumulierten Armaturenweg als Vielfaches des Gesamthubes wieder (1 = vollständiger Hub). |
2138 |
Accumulated cycles |
2139 |
Gibt die Gesamtzahl der Betätigungen des Leistungsstellgliedes an. |
2140 |
Number of cycles per hour |
2141 |
Gibt die Anzahl der Schaltspiele während der letzten Stunde an. Der Wert wird laufend aktualisiert |
2142 |
Wrn 24 V external |
2143 |
Wrn mains quality |
2144 |
Wrn temperature |
2145 |
Wrn humidity |
2146 |
Wrn dew point |
2147 |
Wrn vibration |
2148 |
Wrn duty cycle value |
2149 |
Warnings |
2150 |
Signalisiert eine Warnung im System |
2151 |
State position actual value |
2152 |
State input AIN 1 |
2153 |
State input AIN 2 |
2154 |
Internal Poistioner disabled |
2155 |
Interlock LOCAL active |
2156 |
Configuration |
2157 |
Diagnostic data |
2158 |
Maintanance |
2159 |
Reset functions |
2160 |
Real-Time Clock |
2161 |
Variable 0, AI loop current |
2162 |
Variable 1, AO loop current |
2163 |
Variable 2, setpoint position |
2164 |
Variable 3, actual position |
2165 |
Variable 4, commands |
2166 |
Variable 5, reserved |
2167 |
Variable 6, discrete signal 1 |
2168 |
Variable 7, torque |
2169 |
Variable 8, discrete signal 2 |
2170 |
Variable 9, analog input 1 |
2171 |
Variable 10, analog input 2 |
2172 |
Variable 11, additional commands |
2173 |
Input |
2174 |
Operating modes |
2175 |
Operating messages |
2176 |
Actuator position |
2177 |
Torque overload |
2178 |
Torque warning |
2179 |
Device status |
2180 |
Intermediate positions |
2181 |
Actual position |
2182 |
Torque value |
2183 |
Actuator faults |
2184 |
General faults |
2185 |
Electronic fault messages |
2186 |
Maintenance messages |
2187 |
Dynamic maintenance |
2188 |
Bus communication |
2189 |
AnalogIn |
2190 |
DigitalIn |
2191 |
Diagnosis |
2192 |
Partial Stroke Test |
2193 |
Output |
2194 |
Commands |
2195 |
Release commands |
2196 |
Additional commands |
2197 |
Setpoint |
2198 |
Digital Outputs |
2199 |
Analog Output |
2200 |
Fieldbus State |
2201 |
LWL State |
2202 |
Electronic name plate |
2203 |
Description |
2204 |
Actuator |
2205 |
Control unit |
2206 |
Basics |
2207 |
Components |
2208 |
Features |
2209 |
Motor |
2210 |
Gear / thrust unit |
2211 |
Valve |
2212 |
Oper. data acquisition |
2213 |
General |
2214 |
Operation data |
2215 |
Dynamic maintenance |
2216 |
Faults |
2217 |
System data |
2218 |
Actual values/diagnosis |
2219 |
Error stack |
2220 |
Process data |
2221 |
Power supply |
2222 |
System |
2223 |
Interface |
2224 |
Overview |
2225 |
HART |
2226 |
Version |
2227 |
Device Identification |
2228 |
Plant Identification |
2229 |
Communication State |
2230 |
Parameters |
2231 |
Power supply |
2232 |
Display unit |
2233 |
Language |
2234 |
Date and Time |
2235 |
LEDs |
2236 |
View |
2237 |
Usage |
2238 |
Data logging |
2239 |
Basic settings |
2240 |
Starting-up aid |
2241 |
Intermediate positions |
2242 |
Pivot points |
2243 |
Hysteresis |
2244 |
Signal behaviour |
2245 |
Monitoring |
2246 |
DCS / PLC system |
2247 |
Emerg. shutdown (ESD) |
2248 |
Fail safe |
2249 |
Collective failure 1 |
2250 |
Collective failure 2 |
2251 |
Control |
2252 |
Indications |
2253 |
Plant Configuration |
2254 |
Comm. Config |
2255 |
Calibrat. values |
2256 |
I/O interface |
2257 |
Outputs |
2258 |
Analogue outputs |
2259 |
Command inputs |
2260 |
Other |
2261 |
Basic settings |
2262 |
Process |
2263 |
Modulation behaviour |
2264 |
Stepping mode |
2265 |
Factory settings |
2266 |
Read parameters from device... |
2267 |
Write parameters to device... |
2268 |
Wireless |
2269 |
WirelessHART Device |
2270 |
IEEE 802.15.4 2.4GHz DSSS with O-QPSK Modulation |
2271 |
Primary |
2272 |
Primary Analog Channel |
2273 |
Secondary Analog Channel |
2274 |
Tertiary |
2275 |
Tertiary Analog Channel |
2276 |
Quaternary |
2277 |
Quaternary Analog Channel |
2278 |
Quinary |
2279 |
Quinary Analog Channel |
2280 |
Lock all |
2281 |
Trim not supported |
2282 |
Configuration cannot be changed |
2283 |
Locked by gateway |
2284 |
Analog Input Channel |
2285 |
Analog Output Channel |
2286 |
The device is in simulation mode and the level output is not representative of the process. |
2287 |
The Non-Volatile memory check is invalid or maybe corrupt, or the battery of a battery-backed memory has failed. |
2288 |
The RAM memory check is invalid or maybe corrupt |
2289 |
A watchdog reset has been performed |
2290 |
Voltage conditions out of range |
2291 |
A voltage condition is outside its allowable range |
2292 |
An internal or environmental condition is beyond acceptable limits. |
2293 |
A hardware problem not related to the sensor has been detected. |
2294 |
The device was unable to acquire the communication bandwidth required to support the Burst Messaging specified |
2295 |
Battery life |
2296 |
Percent range |
2297 |
Loop current |
2298 |
Primary variable |
2299 |
Secondary variable |
2300 |
Tertiary variable |
2301 |
Quaternary variable |
2302 |
Read receive time |
2303 |
Write date and time |
2304 |
Non-Volatile Clock |
2305 |
When set the device contains a battery-backed clock. In this case, the clock does not need to be reset if there is a power failure. |
2306 |
Clock Uninitialized |
2307 |
The real-time clock has never been set with the date and time. For example, the clock is volatile and power was removed from and restored to the device. |
2308 |
None |
2309 |
No restrictions |
2310 |
SI Only |
2311 |
Restricted to SI Unit codes only |
2312 |
Process automation device |
2313 |
Discrete device |
2314 |
Hybrid:Process automation+discrete |
2315 |
I/O System |
2316 |
WirelessHART Process automation device |
2317 |
WirelessHART Discrete device |
2318 |
WirelessHART Process automation+discrete |
2319 |
WirelessHART Gateway |
2320 |
WirelessHART Access point |
2321 |
WirelessHART Process adapter |
2322 |
WirelessHART Discrete adapter |
2323 |
WirelessHART enabled handheld/portable maintenance tool |
2324 |
Device Profile |
2325 |
US |
2326 |
United States of America |
2327 |
JP |
2328 |
Japan |
2329 |
DE |
2330 |
Germany |
2331 |
FR |
2332 |
France |
2333 |
ES |
2334 |
Spain |
2335 |
RU |
2336 |
Russian Federation |
2337 |
CN |
2338 |
People's Republic of China |
2339 |
Secondary Master |
2340 |
Primary Master |
2341 |
Device Diagnostic Status 0 |
2342 |
Device Diagnostic Status 1 |
2343 |
I/O and Subdevice Status |
2344 |
WirelessHART Status |
2345 |
Time Set Option |
2346 |
Real Time Clock Flags |
2347 |
Country |
2348 |
Country of intended device installation |
2349 |
SI Unit Control |
2350 |
Indicates if device should only display SI unit codes |
2351 |
Time Stamp |
2352 |
Relative time value on network |
2353 |
8u |
2354 |
Dynamic Variables Returned for Device Variables |
2355 |
Command Response Truncated |
2356 |
Configuration Change Counter Mismatch |
2357 |
Status bytes mismatch |
2358 |
count |
2359 |
Device Variable |
2360 |
Current Date |
2361 |
Current Date based upon the real-time clock in the field device |
2362 |
Current Time |
2363 |
Current Time based upon the real-time clock in the field device |
2364 |
Set Clock Time |
2365 |
Time to set the real time clock in the field device to, or time that the real-time clock was last set |
2366 |
Set Clock Date |
2367 |
Date to set the real-time clock in the field device to, or date that the real-time clock was last set |
2368 |
Variable to trim |
2369 |
STX Count |
2370 |
Count of STX messages received by this device |
2371 |
ACK Count |
2372 |
Count of ACK messages received by this device |
2373 |
BACK Count |
2374 |
Count of BACK messages received by this device |
2375 |
Analog Channel Number |
2376 |
Analog Channel Number- Index into an array of Analog Channels. |
2377 |
Index 1 into Analog Channel Array |
2378 |
Index into Analog Channel Array- Is the first of an array of addresses, whose value is identified by the Analog Channel Code. |
2379 |
Index 2 into Analog Channel Array |
2380 |
Index into Analog Channel Array- Is the second of an array of addresses, whose value is identified by the Analog Channel Code. |
2381 |
Index 3 into Analog Channel Array |
2382 |
Index into Analog Channel Array- Is the third of an array of addresses, whose value is identified by the Analog Channel Code. |
2383 |
Index 4 into Analog Channel Array |
2384 |
Index into Analog Channel Array- Is the fourth of an array of addresses, whose value is identified by the Analog Channel Code. |
2385 |
Retrieve data for: %{PRM_9425} |
2386 |
ERROR: loading data failed! |
2387 |
Read device information |
2388 |
Read properties of %{PRM_9425} |
2389 |
Read data for curve in direction OPEN |
2390 |
Read data for curve in direction CLOSE |
2391 |
Accomplished! |