0 |
Select Curve |
1 |
Last recording |
2 |
Curve 1 |
3 |
Curve 2 |
4 |
Curve 3 |
5 |
Curve 4 |
6 |
Demo curve |
7 |
Curve points OPEN |
8 |
Curve points CLOSE |
9 |
Description |
10 |
Timestamp curve OPEN |
11 |
Timestamp curve CLOSE |
12 |
Position buffer 1 |
13 |
Position buffer 2 |
14 |
Position buffer 3 |
15 |
Position buffer 4 |
16 |
Position buffer 5 |
17 |
Position buffer 6 |
18 |
Position buffer 7 |
19 |
Position buffer 8 |
20 |
Position buffer 9 |
21 |
Position buffer 10 |
22 |
Position buffer 11 |
23 |
Position buffer 12 |
24 |
Position buffer 13 |
25 |
Position buffer 14 |
26 |
Position buffer 15 |
27 |
Position buffer 16 |
28 |
Torque buffer 1 |
29 |
Torque buffer 2 |
30 |
Torque buffer 3 |
31 |
Torque buffer 4 |
32 |
Torque buffer 5 |
33 |
Torque buffer 6 |
34 |
Torque buffer 7 |
35 |
Torque buffer 8 |
36 |
Torque buffer 9 |
37 |
Torque buffer 10 |
38 |
Torque buffer 11 |
39 |
Torque buffer 12 |
40 |
Torque buffer 13 |
41 |
Torque buffer 14 |
42 |
Torque buffer 15 |
43 |
Torque buffer 16 |
44 |
Torque buffer 17 |
45 |
Torque buffer 18 |
46 |
Torque buffer 19 |
47 |
Torque buffer 20 |
48 |
Torque buffer 21 |
49 |
Torque buffer 22 |
50 |
Torque buffer 23 |
51 |
Torque buffer 24 |
52 |
Torque buffer 25 |
53 |
Torque buffer 26 |
54 |
Torque buffer 27 |
55 |
Torque buffer 28 |
56 |
Torque buffer 29 |
57 |
Torque buffer 30 |
58 |
Torque buffer 31 |
59 |
Torque buffer 32 |
60 |
Value |
61 |
Value x |
62 |
Min value |
63 |
Max value |
64 |
Min x-value |
65 |
Max x-value |
66 |
arr_CC_TOPO_XValues |
67 |
arr_CC_TOPO_Values |
68 |
CLOSE |
69 |
var CC TOPOC0 points |
70 |
|
71 |
OPEN |
72 |
var CC TOPOO0 points |
73 |
Torque curves |
74 |
Travel |
75 |
Torque |
76 |
curve CLOSE |
77 |
curve OPEN |
78 |
Load... |
79 |
load_CC_TOPO_select_curve |
80 |
load_CC_TOPO_read_actuatorinfo |
81 |
load_CC_TOPO_read_curveinfo |
82 |
load_CC_TOPO_read_curve |
83 |
read_CC_TOPO_data |
84 |
calc_CC_TOPO_position |
85 |
calc_CC_TOPO_torque |
86 |
Read firmware version |
87 |
Reset to Factory Defaults |
88 |
Reset Operational Data |
89 |
Reset HART parameter |
90 |
Set RTC (device) |
91 |
Read RTC (device) |
92 |
Read system time |
93 |
Device configuration locked |
94 |
Device is write-protected or is locked. |
95 |
Discrete variable simulation active |
96 |
The device is in simulation mode and one or more of its Discrete Variables are not representative of the process. |
97 |
Event notification overflow |
98 |
At least one event notification was not recorded due to event queue overflow. |
99 |
Failure |
100 |
Out of specification |
101 |
Function check |
102 |
DREHMO i-matic |
103 |
AUMA |
104 |
Status Bit Not Supported |
105 |
No Effect |
106 |
Maintenance Required |
107 |
Out of Specification |
108 |
Function Check |
109 |
Disabled |
110 |
Enabled |
111 |
Reset |
112 |
Set |
113 |
Used to map a status condition to a severity level. |
114 |
PV Analog Channel Saturated |
115 |
PV Analog Channel Fixed |
116 |
Critical Power Failure |
117 |
Simulation active |
118 |
Non-Volatile memory failure |
119 |
Volatile memory error |
120 |
Watchdog reset executed |
121 |
Power supply conditions out of range |
122 |
Environmental conditions out of range |
123 |
Electronic failure |
124 |
Status simulation active |
125 |
Discrete Variable Simulation active |
126 |
Event Notification Overflow |
127 |
Secondary Analog Channel Saturated |
128 |
Tertiary Analog Channel Saturated |
129 |
Quaternary Analog Channel Saturated |
130 |
Quinary Analog Channel Saturated |
131 |
Subdevice list changed |
132 |
Duplicate master detected |
133 |
Sub-device mismatch |
134 |
Sub-devices with duplicate IDs found |
135 |
Stale data notice |
136 |
Capacity Denied |
137 |
Bandwidth allocation pending |
138 |
Block transfer pending |
139 |
Radio failure |
140 |
Secondary Analog Channel Fixed |
141 |
Tertiary Analog Channel Fixed |
142 |
Quaternary Analog Channel Fixed |
143 |
Quinary Analog Channel Fixed |
144 |
Condensed status simulation |
145 |
Allows simulation of different status conditions. |
146 |
Condensed status value |
147 |
Condensed Status |
148 |
Field Device Status Mapping |
149 |
Bit |
150 |
7 |
151 |
6 |
152 |
5 |
153 |
4 |
154 |
3 |
155 |
2 |
156 |
1 |
157 |
0 |
158 |
Device Specific Status Mapping |
159 |
Byte 0 |
160 |
Byte 1 |
161 |
Byte 2 |
162 |
Byte 3 |
163 |
Byte 4 |
164 |
Byte 5 |
165 |
Extended Status Mapping |
166 |
Extended FDS |
167 |
Device Op Mode |
168 |
Std Status 0 |
169 |
Std Status 1 |
170 |
Transaction 1 Mapping |
171 |
Analog Channel |
172 |
Std Status 2 |
173 |
Std Status 3 |
174 |
Analog Channel Fixed |
175 |
Byte 14 |
176 |
Byte 15 |
177 |
Byte 16 |
178 |
Byte 17 |
179 |
Byte 18 |
180 |
Byte 19 |
181 |
Byte 20 |
182 |
Byte 21 |
183 |
Byte 22 |
184 |
Byte 23 |
185 |
Byte 24 |
186 |
target mapping |
187 |
Status bit not supported |
188 |
DV0: Device Family |
189 |
Variable 0, value |
190 |
.2f |
191 |
DV0: Family Status |
192 |
DV0: Units |
193 |
DV0: Classification |
194 |
DV0: PDQ |
195 |
DV0: LS |
196 |
DV0: USL |
197 |
.3f |
198 |
DV0: LSL |
199 |
DV0: Minimum Span |
200 |
DV0: Damping Value |
201 |
8.3f |
202 |
DV0: Simulated |
203 |
DV0: Update Period |
204 |
DV0: Serial Number |
205 |
7d |
206 |
DV0: Lower trim |
207 |
DV0: Upper trim |
208 |
DV0: Trim support |
209 |
DV0: Min lower trim |
210 |
DV0: Max lower trim |
211 |
DV0: Min upper trim |
212 |
DV0: Pres Max upper trim |
213 |
DV0: Min trim diff |
214 |
Variable 0, simulation |
215 |
Update Period |
216 |
Serial Number |
217 |
Variable 1, value |
218 |
DV1: Device Family |
219 |
DV1: Family Status |
220 |
DV1: Units |
221 |
DV1: Classification |
222 |
DV1: PDQ |
223 |
DV1: LS |
224 |
DV1: USL |
225 |
DV1: LSL |
226 |
DV1: Minimum Span |
227 |
DV1: Damping Value |
228 |
DV1: Simulated |
229 |
DV1: Update Period |
230 |
DV1: Serial Number |
231 |
DV1: Lower trim |
232 |
DV1: Upper trim |
233 |
DV1: Trim support |
234 |
DV1: Min lower trim |
235 |
DV1: Max lower trim |
236 |
DV1: Min upper trim |
237 |
DV1: Pres Max upper trim |
238 |
DV1: Min trim diff |
239 |
Variable 1, simulation |
240 |
Variable 2, value |
241 |
.1f |
242 |
DV2: Device Family |
243 |
DV2: Family Status |
244 |
DV2: Units |
245 |
DV2: Classification |
246 |
DV2: PDQ |
247 |
DV2: LS |
248 |
DV2: USL |
249 |
DV2: LSL |
250 |
DV2: Minimum Span |
251 |
DV2: Damping Value |
252 |
DV2: Simulated |
253 |
DV2: Update Period |
254 |
DV2: Serial Number |
255 |
DV2: Lower trim |
256 |
DV2: Upper trim |
257 |
DV2: Trim support |
258 |
DV2: Min lower trim |
259 |
DV2: Max lower trim |
260 |
DV2: Min upper trim |
261 |
DV2: Pres Max upper trim |
262 |
DV2: Min trim diff |
263 |
Variable 2, simulation |
264 |
Variable 3, value |
265 |
DV3: Device Family |
266 |
DV3: Family Status |
267 |
DV3: Units |
268 |
DV3: Classification |
269 |
DV3: PDQ |
270 |
DV3: LS |
271 |
DV3: USL |
272 |
DV3: LSL |
273 |
DV3: Minimum Span |
274 |
DV3: Damping Value |
275 |
DV3: Simulated |
276 |
DV3: Update Period |
277 |
DV3: Serial Number |
278 |
DV3: Lower trim |
279 |
DV3: Upper trim |
280 |
DV3: Trim support |
281 |
DV3: Min lower trim |
282 |
DV3: Max lower trim |
283 |
DV3: Min upper trim |
284 |
DV3: Pres Max upper trim |
285 |
DV3: Min trim diff |
286 |
Variable 3, simulation |
287 |
Variable 4, value |
288 |
Run OPEN |
289 |
Run OPEN |
290 |
Run CLOSE |
291 |
Run CLOSE |
292 |
Run SETPOINT |
293 |
Run SETPOINT |
294 |
DV4: Device Family |
295 |
DV4: Family Status |
296 |
DV4: Units |
297 |
DV4: Classification |
298 |
DV4: PDQ |
299 |
DV4: LS |
300 |
DV4: USL |
301 |
DV4: LSL |
302 |
DV4: Minimum Span |
303 |
DV4: Damping Value |
304 |
DV4: Simulated |
305 |
DV4: Update Period |
306 |
DV4: Serial Number |
307 |
DV4: Lower trim |
308 |
DV4: Upper trim |
309 |
DV4: Trim support |
310 |
DV4: Min lower trim |
311 |
DV4: Max lower trim |
312 |
DV4: Min upper trim |
313 |
DV4: Pres Max upper trim |
314 |
DV4: Min trim diff |
315 |
Variable 4, simulation |
316 |
Variable 5, value |
317 |
g |
318 |
DV5: Device Family |
319 |
DV5: Family Status |
320 |
DV5: Units |
321 |
DV5: Classification |
322 |
DV5: PDQ |
323 |
DV5: LS |
324 |
DV5: USL |
325 |
DV5: LSL |
326 |
DV5: Minimum Span |
327 |
DV5: Damping Value |
328 |
DV5: Simulated |
329 |
DV5: Update Period |
330 |
DV5: Serial Number |
331 |
DV5: Lower trim |
332 |
DV5: Upper trim |
333 |
DV5: Trim support |
334 |
DV5: Min lower trim |
335 |
DV5: Max lower trim |
336 |
DV5: Min upper trim |
337 |
DV5: Pres Max upper trim |
338 |
DV5: Min trim diff |
339 |
Variable 5, simulation |
340 |
Variable 6, value |
341 |
Operation pause active |
342 |
Operation pause active |
343 |
In intermed. position |
344 |
In intermed. position |
345 |
Start stepping mode |
346 |
Start stepping mode |
347 |
Actuator running |
348 |
Actuator running |
349 |
Handwheel operation |
350 |
Handwheel operation |
351 |
Operation from Remote |
352 |
Operation from Remote |
353 |
Local operation |
354 |
Local operation |
355 |
Not ready Remote |
356 |
Not ready Remote |
357 |
Warning |
358 |
Warning |
359 |
Fault |
360 |
Fault |
361 |
Maintenance required |
362 |
Maintenance required |
363 |
Out of specification |
364 |
Out of specification |
365 |
Function check |
366 |
Function check |
367 |
Failure |
368 |
Failure |
369 |
Device ok |
370 |
Device ok |
371 |
Thermal fault |
372 |
Thermal fault |
373 |
Phase failure |
374 |
Phase failure |
375 |
Selector REMOTE |
376 |
Selector REMOTE |
377 |
Selector LOCAL |
378 |
Selector LOCAL |
379 |
Limit switch OPEN |
380 |
Limit switch OPEN |
381 |
Limit switch CLOSE |
382 |
Limit switch CLOSE |
383 |
Torque switch OPEN |
384 |
Torque switch OPEN |
385 |
Torque switch CLOSE |
386 |
Torque switch CLOSE |
387 |
End position OPEN |
388 |
End position OPEN |
389 |
End position OPEN |
390 |
End position OPEN |
391 |
Setpoint reached |
392 |
Setpoint reached |
393 |
Not ready Remote |
394 |
Not ready Remote |
395 |
Running OPEN |
396 |
Running OPEN |
397 |
Running CLOSE |
398 |
Running CLOSE |
399 |
DV6: Device Family |
400 |
DV6: Family Status |
401 |
DV6: Units |
402 |
DV6: Classification |
403 |
DV6: PDQ |
404 |
DV6: LS |
405 |
DV6: USL |
406 |
DV6: LSL |
407 |
DV6: Minimum Span |
408 |
DV6: Damping Value |
409 |
DV6: Simulated |
410 |
DV6: Update Period |
411 |
DV6: Serial Number |
412 |
DV6: Lower trim |
413 |
DV6: Upper trim |
414 |
DV6: Trim support |
415 |
DV6: Min lower trim |
416 |
DV6: Max lower trim |
417 |
DV6: Min upper trim |
418 |
DV6: Pres Max upper trim |
419 |
DV6: Min trim diff |
420 |
Variable 6, simulation |
421 |
Variable 7, value |
422 |
DV7: Device Family |
423 |
DV7: Family Status |
424 |
DV7: Units |
425 |
DV7: Classification |
426 |
DV7: PDQ |
427 |
DV7: LS |
428 |
DV7: USL |
429 |
DV7: LSL |
430 |
DV7: Minimum Span |
431 |
DV7: Damping Value |
432 |
DV7: Simulated |
433 |
DV7: Update Period |
434 |
DV7: Serial Number |
435 |
DV7: Lower trim |
436 |
DV7: Upper trim |
437 |
DV7: Trim support |
438 |
DV7: Min lower trim |
439 |
DV7: Max lower trim |
440 |
DV7: Min upper trim |
441 |
DV7: Pres Max upper trim |
442 |
DV7: Min trim diff |
443 |
Variable 7, simulation |
444 |
Variable 8, value |
445 |
Safe ESD |
446 |
Safe ESD |
447 |
Safe STOP |
448 |
Safe STOP |
449 |
SIL fault |
450 |
SIL fault |
451 |
SIL function active |
452 |
SIL function active |
453 |
Channel 1 active |
454 |
Channel 1 active |
455 |
Channel 1 Data Ex |
456 |
Channel 1 Data Ex |
457 |
Channel 1 FailState |
458 |
Channel 1 FailState |
459 |
Channel 1 bus activity |
460 |
Channel 1 bus activity |
461 |
Input DIN 1 |
462 |
Input DIN 1 |
463 |
Input DIN 2 |
464 |
Input DIN 2 |
465 |
Input DIN 3 |
466 |
Input DIN 3 |
467 |
Input DIN 4 |
468 |
Input DIN 4 |
469 |
Input DIN 5 |
470 |
Input DIN 5 |
471 |
Input DIN 6 |
472 |
Input DIN 6 |
473 |
Intermediate pos. 1 |
474 |
Intermediate pos. 1 |
475 |
Intermediate pos. 2 |
476 |
Intermediate pos. 2 |
477 |
Intermediate pos. 3 |
478 |
Intermediate pos. 3 |
479 |
Intermediate pos. 4 |
480 |
Intermediate pos. 4 |
481 |
Intermediate pos. 5 |
482 |
Intermediate pos. 5 |
483 |
Intermediate pos. 6 |
484 |
Intermediate pos. 6 |
485 |
Intermediate pos. 7 |
486 |
Intermediate pos. 7 |
487 |
Intermediate pos. 8 |
488 |
Intermediate pos. 8 |
489 |
DV8: Device Family |
490 |
DV8: Family Status |
491 |
DV8: Units |
492 |
DV8: Classification |
493 |
DV8: PDQ |
494 |
DV8: LS |
495 |
DV8: USL |
496 |
DV8: LSL |
497 |
DV8: Minimum Span |
498 |
DV8: Damping Value |
499 |
DV8: Simulated |
500 |
DV8: Update Period |
501 |
DV8: Serial Number |
502 |
DV8: Lower trim |
503 |
DV8: Upper trim |
504 |
DV8: Trim support |
505 |
DV8: Min lower trim |
506 |
DV8: Max lower trim |
507 |
DV8: Min upper trim |
508 |
DV8: Pres Max upper trim |
509 |
DV8: Min trim diff |
510 |
Variable 8, simulation |
511 |
Variable 9, value |
512 |
DV9: Device Family |
513 |
DV9: Family Status |
514 |
DV9: Units |
515 |
DV9: Classification |
516 |
DV9: PDQ |
517 |
DV9: LS |
518 |
DV9: USL |
519 |
DV9: LSL |
520 |
DV9: Minimum Span |
521 |
DV9: Damping Value |
522 |
DV9: Simulated |
523 |
DV9: Update Period |
524 |
DV9: Serial Number |
525 |
DV9: Lower trim |
526 |
DV9: Upper trim |
527 |
DV9: Trim support |
528 |
DV9: Min lower trim |
529 |
DV9: Max lower trim |
530 |
DV9: Min upper trim |
531 |
DV9: Pres Max upper trim |
532 |
DV9: Min trim diff |
533 |
Variable 9, simulation |
534 |
Variable 10, value |
535 |
DV10: Device Family |
536 |
DV10: Family Status |
537 |
DV10: Units |
538 |
DV10: Classification |
539 |
DV10: PDQ |
540 |
DV10: LS |
541 |
DV10: USL |
542 |
DV10: LSL |
543 |
DV10: Minimum Span |
544 |
DV10: Damping Value |
545 |
DV10: Simulated |
546 |
DV10: Update Period |
547 |
DV10: Serial Number |
548 |
DV10: Lower trim |
549 |
DV10: Upper trim |
550 |
DV10: Trim support |
551 |
DV10: Min lower trim |
552 |
DV10: Max lower trim |
553 |
DV10: Min upper trim |
554 |
DV10: Pres Max upper trim |
555 |
DV10: Min trim diff |
556 |
Variable 10, simulation |
557 |
Variable 11, value |
558 |
现场总线 紧急 |
559 |
No text available. |
560 |
Fieldbus enable LOCAL CLOSE |
561 |
The operation of the actuator via the local control in direction CLOSE will be released in the case of a locked display unit. |
562 |
Fieldbus enable LOCAL OPEN |
563 |
The operation of the actuator via the local control in direction OPEN will be released in the case of a locked display unit. |
564 |
Fieldbus enable local control |
565 |
The operation of the actuator via the local control will be enabled in the case of a locked display unit. |
566 |
Fieldbus DOUT 1 |
567 |
Transmitting a digital signal from the DCS to the relay board of the controller. |
568 |
Fieldbus DOUT 2 |
569 |
Fieldbus DOUT 3 |
570 |
Fieldbus DOUT 4 |
571 |
DV11: Device Family |
572 |
DV11: Family Status |
573 |
DV11: Units |
574 |
DV11: Classification |
575 |
DV11: PDQ |
576 |
DV11: LS |
577 |
DV11: USL |
578 |
DV11: LSL |
579 |
DV11: Minimum Span |
580 |
DV11: Damping Value |
581 |
DV11: Simulated |
582 |
DV11: Update Period |
583 |
DV11: Serial Number |
584 |
DV11: Lower trim |
585 |
DV11: Upper trim |
586 |
DV11: Trim support |
587 |
DV11: Min lower trim |
588 |
DV11: Max lower trim |
589 |
DV11: Min upper trim |
590 |
DV11: Pres Max upper trim |
591 |
DV11: Min trim diff |
592 |
Variable 11, simulation |
593 |
Loop Warning Variables |
594 |
Loop Warning Variables- Variables that display a warning message before new values are sent. |
595 |
Drive commands |
596 |
Fieldbus command close |
597 |
No text available. |
598 |
Fieldbus command open |
599 |
Fieldbus command set value |
600 |
Fieldbus command reset |
601 |
Fieldbus Speed |
602 |
no text |
603 |
% |
604 |
Setpoint |
605 |
Auxiliary commands |
606 |
允许就地现场总线 |
607 |
No text available. |
608 |
允许现场总线 开 |
609 |
允许现场总线 关 |
610 |
PVST |
611 |
MPV_指令 现场总线 |
612 |
无直接位置 |
613 |
直接位置 1 |
614 |
直接位置 2 |
615 |
直接位置 3 |
616 |
直接位置 4 |
617 |
直接位置 5 |
618 |
直接位置 6 |
619 |
直接位置 7 |
620 |
直接位置 8 |
621 |
直接位置 9 |
622 |
直接位置 10 |
623 |
直接位置 11 |
624 |
直接位置 12 |
625 |
CW |
626 |
直接位置 1 CW |
627 |
直接位置 2 CW |
628 |
直接位置 3 CW |
629 |
直接位置 4 CW |
630 |
直接位置 5 CW |
631 |
直接位置 6 CW |
632 |
直接位置 7 CW |
633 |
直接位置 8 CW |
634 |
直接位置 9 CW |
635 |
直接位置 10 CW |
636 |
直接位置 11 CW |
637 |
直接位置 12 CW |
638 |
CCW |
639 |
直接位置 1 CCW |
640 |
直接位置 2 CCW |
641 |
直接位置 3 CCW |
642 |
直接位置 4 CCW |
643 |
直接位置 5 CCW |
644 |
直接位置 6 CCW |
645 |
直接位置 7 CCW |
646 |
直接位置 8 CCW |
647 |
直接位置 9 CCW |
648 |
直接位置 10 CCW |
649 |
直接位置 11 CCW |
650 |
直接位置 12 CCW |
651 |
Digital outputs |
652 |
现场总线 DOUT1 |
653 |
现场总线 DOUT2 |
654 |
现场总线 DOUT3 |
655 |
现场总线 DOUT4 |
656 |
现场总线 DOUT5 |
657 |
现场总线 DOUT6 |
658 |
Count of input data to read |
659 |
Input data byte 01 |
660 |
Input data byte 02 |
661 |
Input data byte 03 |
662 |
Input data byte 04 |
663 |
Input data byte 05 |
664 |
Input data byte 06 |
665 |
Input data byte 07 |
666 |
Input data byte 08 |
667 |
Input data byte 09 |
668 |
Input data byte 10 |
669 |
Input data byte 11 |
670 |
Input data byte 12 |
671 |
Input data byte 13 |
672 |
Input data byte 14 |
673 |
Input data byte 15 |
674 |
Input data byte 16 |
675 |
Input data byte 17 |
676 |
Input data byte 18 |
677 |
Input data byte 19 |
678 |
Input data byte 20 |
679 |
Input data byte 21 |
680 |
Input data byte 22 |
681 |
Input data byte 23 |
682 |
Input data byte 24 |
683 |
Input data byte 25 |
684 |
Input data byte 26 |
685 |
Input data byte 27 |
686 |
Input data byte 28 |
687 |
Input data byte 29 |
688 |
Input data byte 30 |
689 |
Input data byte 31 |
690 |
Input data byte 32 |
691 |
EDD generator |
692 |
Version EDD generator program |
693 |
01.00.05 |
694 |
Designated device version |
695 |
Device description is compatible to this device version family |
696 |
02.00.xx |
697 |
上限 |
698 |
定义对应全开位置的值 |
699 |
下限 |
700 |
定义对应全关位置的值 |
701 |
行程单位 |
702 |
设定显示输出的行程单位。如果改变单位, 相关参数必需手动调整(如分度值)。 |
703 |
ppt |
704 |
° |
705 |
mm |
706 |
小数点位置 |
707 |
设定主显示小数点后的位数。 |
708 |
TAG/KKS-ID |
709 |
过程性能标识 |
710 |
主板软件版本 |
711 |
主板软件版本 |
712 |
主板硬件版本 |
713 |
主板硬件版本 |
714 |
生产商标识 |
715 |
PNO.指定的生产商ID. |
716 |
设备标识 |
717 |
控制单元类别 |
718 |
控制单元序列号 |
719 |
控制单元序列号 |
720 |
原始工厂序列号 |
721 |
Serial number (works number) of the original produced actuator that included the control unit. |
722 |
认证 |
723 |
认证 |
724 |
应用 |
725 |
执行器有关说明 |
726 |
安装区域 |
727 |
过程性能部分,执行器安装区域 |
728 |
安装日期 |
729 |
执行器安装日期 |
730 |
执行器型号 |
731 |
带输出轴和转速的执行器描述 (如:DiM30 A-25) |
732 |
最大调节力矩 |
733 |
调节执行器输出最大力矩 => 由设定的设备密钥确定(见控制单元) |
734 |
转速 |
735 |
输出转速/Rpm |
736 |
全行程时间 |
737 |
90°全行程时间 (适用DPiM) |
738 |
机械输出接口 |
739 |
机械输出接口 |
740 |
最低环境温度 |
741 |
控制单元供电(防潮加热器送电)时最低环境温度 |
742 |
最高环境温度 |
743 |
最高允许环境温度 |
744 |
最小关断力矩 |
745 |
执行器输出最小力矩 => 由设定的设备密钥确定(见控制单元) |
746 |
最大关断力矩 |
747 |
执行器输出最大力矩 => 由设定的设备密钥确定(见控制单元) |
748 |
防护等级 |
749 |
防护等级 |
750 |
接线图 |
751 |
执行器接线图 |
752 |
验收号 |
753 |
生产商验收号 |
754 |
额定电压 |
755 |
Angabe der Versorgungsspannung |
756 |
相数 |
757 |
Number of phases of the main power system |
758 |
额定频率 |
759 |
Angabe der Frequenz des Spannungsversorgungssystems |
760 |
额定电流 |
761 |
Angabe des Bemessungstromes |
762 |
A |
763 |
启动电流 |
764 |
Maximum current when motor is energised |
765 |
额定功率 |
766 |
Angabe der Bemessungsleistung |
767 |
功率因素 |
768 |
额定条件下的功率因素 |
769 |
输出转速/Rpm |
770 |
额定条件下电机转速 |
771 |
工作制式 |
772 |
执行器的工作制式(如S2 10分钟) |
773 |
电机型号 |
774 |
Angabe des Motortyps |
775 |
绝缘等级 |
776 |
Angabe der Isolationsklasse des Antriebsmotors |
777 |
电机序列号 |
778 |
Angabe der Seriennummer des Antriebsmotors |
779 |
内部定位器 |
780 |
内部定位器允许或禁止信息 => 有设定设备密钥确定 |
781 |
禁止 V003 |
782 |
允许 V005 |
783 |
电机保护 |
784 |
电机温度传感器 |
785 |
热开关 |
786 |
PTC |
787 |
电气性能 |
788 |
执行器的电气性能 |
789 |
就地远程控制 |
790 |
执行器是否可以使用显示单元接口进行远程控制信息 => 由设定的设备密钥确定 |
791 |
禁止 |
792 |
允许 |
793 |
增强型控制器 |
794 |
This parameter controls the use of the enhanced controller that provides more complex settings for the controller. |
795 |
禁止 |
796 |
允许 |
797 |
组合传感器序列号 |
798 |
组合传感器序列号 |
799 |
分体EM6序列号 |
800 |
分体执行器,执行器内部接口板序列号 |
801 |
电机温度检测 |
802 |
Information about the version of the motor monitoring - PTC: the microcontroller does the motor monitoring - TMS: a certified module is used to do the motor monitoring. The microcontroller can not control this module |
803 |
未知 |
804 |
PTC |
805 |
TMS |
806 |
模拟输出 |
807 |
指示执行器是否带模拟量输出 |
808 |
禁止 |
809 |
允许 |
810 |
主板序列号 |
811 |
主板序列号 |
812 |
显示板序列号 |
813 |
显示板序列号 |
814 |
接口板1序列号 |
815 |
接口板1序列号 |
816 |
接口板2序列号 |
817 |
选择的接口板2序列号 |
818 |
显示板软件版本 |
819 |
显示板软件版本 |
820 |
显示板硬件版本 |
821 |
显示板硬件版本 |
822 |
接口板1硬件版本 |
823 |
接口板1硬件版本 |
824 |
接口板2硬件版本 |
825 |
接口板2硬件版本 |
826 |
内部24V故障 |
827 |
指示内部24VDC电源-由主电源L1,L2供电-正常还是故障。#x0D;如果允许,只有在执行器提供外加24V DC外部电源时,才能检测。#x0D;否则,在主电源故障时(内部电源也失效),控制单元失电,该功能失效。 |
828 |
禁止 |
829 |
允许 |
830 |
外部24V故障 |
831 |
指示外部 24VDC正常还是故障。 |
832 |
相故障 |
833 |
指示主电源是否缺相。 通过新的运行或故障确认复位。 如果给电子单元供电的两相L1和L2之一发生故障,控制单元就不具备该功能。 只有在控制单元采用外部24V DC供电时,才能指示这两相的故障。 |
834 |
接口板1软件版本 |
835 |
接口板1软件版本 |
836 |
接口板2软件版本 |
837 |
接口板2软件版本 |
838 |
执行器没有启动 |
839 |
如果在电机得电且超过了“运行监控延迟时间”, 但在此期间位置没有明显变化,该指示被激活。 该指示可以通过新的运行或故障确认复位。 |
840 |
过力矩故障 |
841 |
如果力矩超过其中一个关断力矩值,该指示有效。 |
842 |
关方向过力矩 |
843 |
指示在关阀时,关方向力矩超过设定的关断力矩。 指示可以通过反向运行执行器或故障确认进行复位。 |
844 |
开方向过力矩 |
845 |
指示在开阀时,开方向力矩超过设定的关断力矩。 指示可以通过反向运行执行器或故障确认进行复位。 |
846 |
力矩报警 |
847 |
如果力矩超过其中一个报警力矩值,该指示有效。 |
848 |
关方向力矩报警 |
849 |
指示在关阀时,关方向力矩超过报警值。 可以反方向运行执行器进行复位。 |
850 |
开方向力矩报警 |
851 |
指示在开阀时,开方向力矩超过报警值。 可以反方向运行执行器进行复位。 |
852 |
电机超温 |
853 |
如果电机温度超过允许值,该指示有效。 |
854 |
零位模式 |
855 |
如果允许,执行器在零位模式下不能运行。 |
856 |
就地模式 |
857 |
如果允许,执行器在就地模式下不能运行。 |
858 |
ESD有效 |
859 |
在执行器执行ESD功能时有效。 |
860 |
故障安全 |
861 |
在执行器处于故障安全模式时有效。 |
862 |
硬件故障 |
863 |
指示在电子单元自诊断期间检测到失效硬件元件。 |
864 |
组合传感器故障 |
865 |
指示在自诊断期间电子单元检测到复合传感器故障。 故障存在,指示也有效。在故障有效时,执行器不能运行! 控制单元试图重新初始化复合传感器以消除故障。 |
866 |
禁止内部定位器 |
867 |
指示DiMxx5型执行器中的定位器没有被允许 (AUTOMATIC命令无效)。 |
868 |
需要维护 |
869 |
是否超过运行数据的极限值。 |
870 |
非远程模式 |
871 |
执行器是否处于远程模式。 |
872 |
配置无效 |
873 |
至少一个关断力矩超过连接部件或阀门的所允许的最大力矩。 |
874 |
控制单元超温 |
875 |
控制单元的温度超过允许值。 |
876 |
方向监控 |
877 |
执行器以错误方向转动。 可以通过新的运行或故障确认复位。 |
878 |
手轮操作 |
879 |
执行器的位置在没有给电机指令时,位置正在改变。. 位置在改变,该指示就有效。 |
880 |
超出运行监控时间 |
881 |
目前运行时间超出了“关方向运行监控时间”或“开方向运行监控时间”之一。 |
882 |
选项电池故障 |
883 |
内部电池故障。如果该指示有效, 控制单元在主电源断电时,不能由备用电池供电。 |
884 |
功率单元故障 |
885 |
指示带内部差异分析的功率组件错误. |
886 |
指示内部24VDC电源-由主电源L1,L2供电-正常还是故障。#x0D;如果允许,只有在执行器提供外加24V DC外部电源时,才能检测。#x0D;否则,在主电源故障时(内部电源也失效),控制单元失电,该功能失效。 |
887 |
指示外部 24VDC正常还是故障。 |
888 |
紧急停止 |
889 |
外部紧急停止信号 |
890 |
禁止 |
891 |
允许 |
892 |
如果力矩超过其中一个关断力矩值,该指示有效。 |
893 |
关方向过力矩 |
894 |
开方向过力矩 |
895 |
就地模式 |
896 |
需要维护 |
897 |
控制单元超温 |
898 |
执行器的位置在没有给电机指令时,位置正在改变。. 位置在改变,该指示就有效。 |
899 |
选项电池故障 |
900 |
内部电池故障。如果该指示有效, 控制单元在主电源断电时,不能由备用电池供电。 |
901 |
蓝牙PIN |
902 |
该参数定义蓝牙接口的PIN。 PIN用于与主站建立连接期间执行器的授权。 |
903 |
蓝牙名称 |
904 |
定义执行器相关蓝牙接口的不同标识。 |
905 |
序列号 |
906 |
TAG/KKS-ID |
907 |
应用 |
908 |
动态损耗变量 |
909 |
0..100% Verbrauch des Vertrauenskollektives der dynamischen Wartungsmeldung. Diese Variable gibt den höchsten relativen Verbrauch bezogen auf den jeweiligen Grenzwert der thermischen Alterung oder der mechanischen Alterung an. |
910 |
差异错误代码 |
911 |
显示功率驱动差异分析期间检测到故障的错误代码.如果检测到错误,执行器将不能再操作. 0x00 - 没有检测到错误 0x01 - 电路+24V POW OFF错误 0x02 - 电路+24V POW ON错误 0x03 - 电路+24V ELR_POW_FB OFF错误 0x04 - 电路+24V POW OFF错误 0x05 -电路SAUF错误 0x06 - 电路SZU错误 0x07 - 电路+24V POW OFF错误 0x08 - 电路ELRAUF错误 0x09 - 电路ELRZU错误 0x0A - Ausgang POW_EN 没有置位, 反馈POW_RB有效 0x0B - Ausgang POW_EN置位,反馈POW_RB无效 0x0C - ELR_ZU和ELR_AUF没有置位,反馈 ELR_RB有效 0x0D - ELR_ZU或ELR_AUF置位,反馈ELR_RB无效 |
912 |
系统错误代码 |
913 |
显示执行器自诊断测试期间发生的故障代码。 故障代码: 0x00 - 无故障 0x01 - 主程序故障 0x02 - 看门狗(硬件)溢出 0x03 -看门狗(软件)溢出 0x08 - 堆栈上溢 0x09 - 堆栈下溢 0x0A - 不可恢复硬件故障 0x11 - 测试Flash存储器错误 0x12 - 读flash存储器的启动型式时错误 0x13 - 读flash存储器的结束型式时错误 0x14 - flash存储器求和校验错误。 |
914 |
系统测试周期 |
915 |
显示控制单元自诊断测试周期,单位ms |
916 |
ms |
917 |
故障1 |
918 |
显示最新故障类型 |
919 |
无 |
920 |
开方向过力矩 |
921 |
关方向过力矩 |
922 |
执行器启动监控 |
923 |
方向监控 |
924 |
电机过热 |
925 |
电子单元超温 |
926 |
空 |
927 |
故障安全 |
928 |
组合传感器故障 |
929 |
组合传感器设定故障 |
930 |
减速箱输入力矩超出 |
931 |
阀门开过力矩 |
932 |
阀门关过力矩 |
933 |
系统测试故障 |
934 |
内部24V故障 |
935 |
外部24V故障 |
936 |
相1故障 |
937 |
相2故障 |
938 |
相3故障 |
939 |
相序校正故障 |
940 |
备用电池故障 |
941 |
外部24V过载 |
942 |
紧急关断 (ESD) |
943 |
差异错误 |
944 |
错误功率单元 |
945 |
零位模式 |
946 |
就地模式 |
947 |
非远程模式 |
948 |
测试模式允许 |
949 |
仿真模式有效 |
950 |
配置无效 |
951 |
非挥发存储器故障 |
952 |
硬件接口故障 |
953 |
设备密钥无效 |
954 |
组合传感器溢出 |
955 |
组合传感器量程错误 |
956 |
阀门行程极限值 |
957 |
运行次数累计值 |
958 |
当前运行次数/h |
959 |
开运行监控时间 |
960 |
关运行监控时间 |
961 |
建议更换密封圈 |
962 |
建议检修减速箱 |
963 |
关方向力矩报警 |
964 |
手轮操作 |
965 |
需要维护 |
966 |
内部定位器无效 |
967 |
位置校准失败 |
968 |
力矩校准失败 |
969 |
模拟输入校准失败 |
970 |
内部锁就地 |
971 |
内部锁远程 |
972 |
TMS组件错误 |
973 |
RTC 错误 |
974 |
RTC 没有设置 |
975 |
RTC 电池电压低 |
976 |
FO组件错误 |
977 |
FOC budget ch. 1 |
978 |
FO故障 通道1 |
979 |
FOC budget ch. 2 |
980 |
FO故障 通道2 |
981 |
故障2 |
982 |
显示第2个故障类型 |
983 |
故障3 |
984 |
显示第3个故障类型 |
985 |
故障4 |
986 |
显示第4个故障类型 |
987 |
故障5 |
988 |
显示第5个故障类型 |
989 |
故障6 |
990 |
显示第6个故障类型 |
991 |
故障7 |
992 |
显示第7个故障类型 |
993 |
故障8 |
994 |
显示第8个故障类型 |
995 |
阀门关过力矩 |
996 |
故障9 |
997 |
显示第9个故障类型 |
998 |
故障10 |
999 |
显示第故障10类型 |
1000 |
故障1时间 |
1001 |
显示故障时间(控制单元上电时间) |
1002 |
故障2时间 |
1003 |
故障3时间 |
1004 |
故障4时间 |
1005 |
故障5时间 |
1006 |
显示故障时间(控制单元上电时间) |
1007 |
故障6时间 |
1008 |
故障7时间 |
1009 |
故障8时间 |
1010 |
故障9时间 |
1011 |
故障10时间 |
1012 |
设备密钥 |
1013 |
控制单元的主要配置(如:一体化定位器, timer). 新的密钥只有在执行器复位后才生效. |
1014 |
运行模式 |
1015 |
显示有效模式 |
1016 |
就地 |
1017 |
零位 |
1018 |
远程 |
1019 |
调试 |
1020 |
设定值 |
1021 |
以指定的单位显示设定值 |
1022 |
实际位置 |
1023 |
以参数->数据记录->行程单位,指定的单位显示阀位值 |
1024 |
故障安全动作延时 |
1025 |
设定故障和故障安全动作之间的延迟时间。 |
1026 |
动作 |
1027 |
如果设定值在3.0…22mA范围之外或现场总线通讯故障(大于参数“故障安全动作延时”指定的时间)时,选择执行器的动作。 |
1028 |
到故障安全位 |
1029 |
停止执行器 |
1030 |
禁止 |
1031 |
调节型安全位 |
1032 |
设定调节型执行器的故障安全位置。 |
1033 |
故障安全 |
1034 |
故障安全功能的状态信息 |
1035 |
禁止 |
1036 |
有效 |
1037 |
开关型安全位 |
1038 |
设定开关型执行器的故障安全位 |
1039 |
全关 |
1040 |
全开 |
1041 |
中间位置1 |
1042 |
以当前单位设定中间位置1的值 |
1043 |
中间位置2 |
1044 |
以当前单位设定中间位置2的值 |
1045 |
中间位置3 |
1046 |
以当前单位设定中间位置3的值 |
1047 |
中间位置4 |
1048 |
以当前单位设定中间位置4的值 |
1049 |
中间位置5 |
1050 |
以当前单位设定中间位置5的值 |
1051 |
中间位置6 |
1052 |
以当前单位设定中间位置6的值 |
1053 |
中间位置7 |
1054 |
以当前单位设定中间位置7的值 |
1055 |
中间位置8 |
1056 |
以当前单位设定中间位置8的值 |
1057 |
远控优先级 |
1058 |
选择远控信号。 - 现场总线: 忽略常规输入指令。 - 常规输入: 忽略现场总线指令。 - 同等: 现场总线和常规输入指令同时有效 (逻辑 OR 组合)。 |
1059 |
现场总线 |
1060 |
常规输入 |
1061 |
总线+常规 |
1062 |
控制模式 |
1063 |
设定远程指令输入的功能。 可以选点动模式或自保持模式。 |
1064 |
点动模式 |
1065 |
自保持模式 |
1066 |
故障安全动作 |
1067 |
定义内部定位器故障时执行器的故障安全动作是 在自动指令有效时有效还是在任何时候都有效。 |
1068 |
自动指令优先 |
1069 |
忽略自动指令 |
1070 |
步进模式选择 |
1071 |
设定周期脉冲时间Ton为固定值(线性), 或从1个指定值每次减少Ton直到最小值0.5秒(递减), 在递减步进模式中,总是在全关位置T on达到最小,无运行方向无关. |
1072 |
线性 |
1073 |
递减 |
1074 |
过热故障延时 |
1075 |
设定电机超温检测、输出和断电之间的延迟时间。 温度传感器仅由执行器的主电源供电。 如果主电源故障,温度检测将失电, 因此电机温度被检测为过高。电机超温指示将被激活 ,为了克服由于短时间失电造成该指示,可以设定延迟时间。 |
1076 |
相序校正 |
1077 |
定义连接电源系统的旋转磁场。 如果设定为“允许”,连续检查旋转磁场。 |
1078 |
允许 |
1079 |
顺时针 |
1080 |
逆时针 |
1081 |
相监控 |
1082 |
如果有效,检测到缺相时,电机断电,并报“相故障”。 可以通过下次检测或故障确认进行复位。 |
1083 |
禁止 |
1084 |
允许锁存 |
1085 |
允许不锁存 |
1086 |
相监控延时 |
1087 |
定义“相校正故障”或“内部24V故障”信号的延迟时间,范围1…30s |
1088 |
开方向启用 |
1089 |
开方向允许步进模式 |
1090 |
关方向启用 |
1091 |
关方向允许步进模式 |
1092 |
步进模式 T on |
1093 |
设定步进模式的运行时间 |
1094 |
步进模式 T off |
1095 |
设定步进模式的停运行时间 |
1096 |
最高控制单元温度 |
1097 |
最高允许电子单元温度 |
1098 |
最低控制单元温度 |
1099 |
最低允许电子单元温度 |
1100 |
过热故障复位 |
1101 |
电机如果出现过热故障,就要求将电机冷却到有效运行温度范围内。 热故障信号复位后,电机才可能重新运行。复位可通过: 1. 自动故障复位,设定参数为“自动”。 2.手动确认,设定参数为“手动”。 故障确认可以通过就地控制单元以及远控指令或远控模式的参数来完成。 在防爆执行器中,如果工作制式是严格遵循的,参数只允许设置为“自动”。 |
1102 |
自动 |
1103 |
手动 |
1104 |
内部启动位置 |
1105 |
定义步进模式的第2位置值. 第1位置值总是全关位置. |
1106 |
步进控制信号 |
1107 |
设定控制步进模式有效的信号源. 如果设定为“内部”, 步进模式从全关位置开始#x0D;到“内部启动位置”有效. 如果设定为“外部”, 步进模式 在步进模式允许方向且指令有效时有效. |
1108 |
内部 |
1109 |
外部 |
1110 |
回差1 |
1111 |
指定中间位置信号的回差 |
1112 |
回差2 |
1113 |
回差3 |
1114 |
回差4 |
1115 |
回差5 |
1116 |
回差6 |
1117 |
回差7 |
1118 |
回差8 |
1119 |
信号特性 1 |
1120 |
Specifies the signal behaviour of the specific intermediate position. No signal The intermediate position will not be signalized. C____------O The signal of the intermediate position will be high inbetween the specified intermediate position and the final position OPEN. C------____O The signal of the intermediate position will be high in between the final position CLOSE and the specified intermediate position. C___---___O The signal of the intermediate position will be high in a range specified by the hysteresis arround the specified intermediate position. |
1121 |
无信号 |
1122 |
关____------开 |
1123 |
关------____开 |
1124 |
关___---___开 |
1125 |
信号特性 2 |
1126 |
信号特性3 |
1127 |
信号特性 4 |
1128 |
信号特性 5 |
1129 |
信号特性 6 |
1130 |
信号特性 7 |
1131 |
信号特性 8 |
1132 |
关方向 |
1133 |
从执行器电机侧方向看,阀门为关时,执行器的转动方向。 |
1134 |
逆时针 |
1135 |
顺时针 |
1136 |
关全行程时间 |
1137 |
从阀门开到阀门关的时间。 |
1138 |
开全行程时间 |
1139 |
从阀门关到阀门开的时间。 |
1140 |
实际运行时间 |
1141 |
最后一次运行时间 |
1142 |
校准日期 |
1143 |
执行器最后一次校准日期 |
1144 |
配置日期 |
1145 |
该参数可以用于存储最后一次配置的日期 |
1146 |
电机运行时间 |
1147 |
电机累计运行时间 |
1148 |
行程关断次数 |
1149 |
到达末端位置时停止的次数。 |
1150 |
电机启动次数 |
1151 |
电机启动次数 |
1152 |
实际运行次数 |
1153 |
最近1个小时期间电机的启动次数。 该值被连续更新。 |
1154 |
1/h |
1155 |
过力矩次数 |
1156 |
Number of stops due to a torque exceeding the 'Tripping torque ...' |
1157 |
调整范围 |
1158 |
以设置行程单位显示的行程信息 (见参数“数据记录”,“行程单位”) |
1159 |
电机累计运行时间 |
1160 |
电机运行时间,该参数不能复位。 |
1161 |
行程累计关断次数 |
1162 |
到达末端位置时停止的次数。该值不能被复位。 |
1163 |
全关位偏差 |
1164 |
设定定位器转换设定点值做为全关位置的范围。 如果设定点值在关位置和偏差范围之间,执行器将自动运行到末端位置。 如果设定点值高于末端位置+偏差+Xp,离开末端位置。 |
1165 |
全开位偏差 |
1166 |
设定定位器转换设定点值做为全开位置的范围。 如果设定点值在开位置和偏差范围之间,执行器将自动运行到末端位置。 如果设定点值低于末端位置-偏差-Xp,离开末端位置。 |
1167 |
关断模式 |
1168 |
设定末端位置时的关断方式。 |
1169 |
力矩关/力矩开 |
1170 |
行程关/力矩开 |
1171 |
力矩关/行程开 |
1172 |
行程关/行程开 |
1173 |
力矩 |
1174 |
显示当前力矩 |
1175 |
关方向关断力矩 |
1176 |
执行器关时,如果力矩超过这个值,执行器就关断。 |
1177 |
开方向关断力矩 |
1178 |
执行器开时,如果力矩超过这个值,执行器就关断。 |
1179 |
力矩单位 |
1180 |
设定力矩单位 |
1181 |
Nm |
1182 |
ft-lb |
1183 |
阀门累计行程 |
1184 |
以全行程(=1)为倍数累计的阀门行程 |
1185 |
> 累计行程极限值 |
1186 |
以全行程(= 1)倍数累计最大允许阀门行程. 如果超出该值, 将输出“需要维护”。 如果设定为0,禁止该检查。 |
1187 |
维护日期 |
1188 |
该参数可以用于存储最后一次维护的日期 |
1189 |
热老化 |
1190 |
计算执行器相关部件的热老化,如密封圈。这些部件老化过程与环境温度有关。 |
1191 |
> 热老化极限值 |
1192 |
热老化极限值。如果超过该值,输出“需要维护”和“推荐更换密封圈”信号。如果设为0,禁止该检查。 |
1193 |
机械老化 |
1194 |
内部齿轮部件老化计算。 |
1195 |
> 机械老化极限 |
1196 |
机械老化极限值。如果超出该值,输出“需要维护”和“推荐检修齿轮”信号。如果设为0,禁止该检查。 |
1197 |
机械老化执行器型号 |
1198 |
T该参数定义机械老化计算的算法。 为了使用正确的算法,需要选择合适的执行器型号。 如果设为“无”,不进行机械老化计算。 |
1199 |
无 |
1200 |
D30 5-15Nm |
1201 |
D30 10-30Nm |
1202 |
DR30 15-30Nm |
1203 |
DP30 10-30Nm |
1204 |
D59 20-60Nm |
1205 |
DR59 30-60Nm |
1206 |
DP59 20-60Nm |
1207 |
D60 20-60Nm |
1208 |
DR60 30-60Nm |
1209 |
D120 40-120Nm |
1210 |
DR120 60-120Nm |
1211 |
D249 80-250Nm |
1212 |
D250 40-120Nm |
1213 |
D250 80-250Nm |
1214 |
DR250 120-250Nm |
1215 |
D500 150-500Nm |
1216 |
DR500 200-500Nm |
1217 |
D1000 300-1000Nm |
1218 |
DR1000 500-1000Nm |
1219 |
DP119 40-120Nm |
1220 |
DP319 120-320Nm |
1221 |
DP799 320-800Nm |
1222 |
DP1599 800-1600Nm |
1223 |
D250 60-120Nm |
1224 |
D2000 800-2000Nm |
1225 |
DP150 50-150Nm |
1226 |
DP299 125-300Nm |
1227 |
DP300 125-300Nm |
1228 |
DP450 250-450Nm |
1229 |
DP600 200-600Nm |
1230 |
DP900 500-900Nm |
1231 |
DP1200 500-1200Nm |
1232 |
DP1800 1000-1800Nm |
1233 |
> 预设机械老化 |
1234 |
该参数将预设的一个现存执行器型号的极限值为“> 机械老化极限值”。 |
1235 |
生产商 |
1236 |
与执行器配套阀门的生产商 |
1237 |
有关生产商信息描述 |
1238 |
阀门类型 |
1239 |
阀门相关信息 |
1240 |
直行程 |
1241 |
角行程 |
1242 |
多转式 |
1243 |
执行器类别 |
1244 |
执行器的驱动源 |
1245 |
气动 |
1246 |
电动 |
1247 |
电液型 |
1248 |
其它 |
1249 |
阀门序列号 |
1250 |
阀门序列号 |
1251 |
执行器序列号 => 由设定的设备密钥确定 |
1252 |
减速箱序列号 |
1253 |
序列号 |
1254 |
Angabe des Herstellers |
1255 |
减速箱型号 |
1256 |
减速箱型号 |
1257 |
安装日期 |
1258 |
安装日期 |
1259 |
电机过热次数 |
1260 |
Number of times when motor was overheated |
1261 |
电子单元超温时间 |
1262 |
电子单元超过最高允许值的累计时间 |
1263 |
执行器启动故障次数 |
1264 |
Number of times while the motor is energised and the position did not change significantly during this period. |
1265 |
电子单元上电时间 |
1266 |
电子单元上电时间 |
1267 |
上电次数 |
1268 |
系统复位次数 |
1269 |
死区时间 |
1270 |
自动位 |
1271 |
内部定位器有效的自动位选择。 |
1272 |
强制禁止 |
1273 |
强制允许 |
1274 |
远控控制 |
1275 |
远控边缘检测 |
1276 |
该参数与执行器切换到远控模式执行器的动作有关。 如果参数设为有效,需要新的具有边缘触发特性的执行器启动指令来启动执行器运行。 如果参数设置为禁止, 如果执行器的运行指令始终有效, 在切换到远控模式时,执行器就直接启动。 |
1277 |
有效 |
1278 |
末端位忽略力矩 |
1279 |
在试图离开末端位置时,在末端位置延迟时间内禁止力矩检测。。 如果执行器离开末端位置或超出延迟时间时,力矩仍超过关断力矩,就发出过力矩信号且执行器断电。 |
1280 |
禁止 |
1281 |
开位 |
1282 |
关位 |
1283 |
开位和关位 |
1284 |
力矩报警次数 |
1285 |
Number of warnings due to a torque exceeding the 'Torque warning level' |
1286 |
输出力矩 |
1287 |
定义力矩输出值, “实际值”输出当前力矩。 当使用低速现场总线或DCS系统时,可能检测不到力矩的峰值。 “最大值”输出最近一次运行的最大力矩。新的运行将更新力矩值。 “不含末端位置的最大值”与“最大值”的区别是不包含末端位置范围内的力矩值。 “趋势值”为1秒的最大值,之后自动更新。 低速DCS系统推荐使用该设置。 |
1288 |
实际值 |
1289 |
最大值 |
1290 |
不含末端位最大值 |
1291 |
趋势值 |
1292 |
末端位信号 |
1293 |
设置末端位置指示。如果设置为行程,在达到末端位置时,指示有效。 如果设置为符合关断模式时,只有执行器到达末端位置时,指示有效。 |
1294 |
行程 |
1295 |
取决关断模式 |
1296 |
过力矩信号 |
1297 |
设置在末端位过力矩信号是否指示。 |
1298 |
末端位不含过力矩 |
1299 |
末端位含过力矩 |
1300 |
末端位自保持 |
1301 |
设定执行器在达到末端位置偏差之内时, 即使没有运行到末端位置命令时,是否自动运行。 只有在阀门的至少一个末端位置 是由力矩关断的才可设定为允许。 |
1302 |
关方向报警力矩 |
1303 |
执行器关时,如果力矩超过这个值,执行器就发出报警指示。 |
1304 |
开方向报警力矩 |
1305 |
执行器开时,如果力矩超过这个值,执行器就发出报警指示。 |
1306 |
禁止显示单元 |
1307 |
选择指令“允许就地”如何工作: -“完全禁止”,和enter按钮上锁一样,所有按钮均禁止操作。 -“禁止就地操作”,仅禁止电机操作 - “忽略信号”,禁止指令输入 |
1308 |
完全禁止 |
1309 |
禁止就地操作 |
1310 |
忽略信号 |
1311 |
中间位忽略力矩 |
1312 |
如果允许,在试图离开中间位置时,以电机的breakdown(最大)力距运行。禁止时,在超过设定力矩时,执行器将关断。 |
1313 |
禁止 |
1314 |
允许 |
1315 |
> 极限启动次数 |
1316 |
电机启动的极限次数。如果超过该次数,输出需要维护信号。 如果该参数设为0,禁止该检查。 |
1317 |
开方向死区 |
1318 |
开方向调节偏差 |
1319 |
关方向死区 |
1320 |
关方向调节偏差 |
1321 |
外部死区 |
1322 |
最大输入力矩 |
1323 |
最大允许输入力矩. 参数“关方向关断力矩”,“开方向关断力矩”,不能超过该值。 |
1324 |
齿轮比率 |
1325 |
Angabe der Übersetzung des Zusatzgetriebes |
1326 |
齿轮系数 |
1327 |
Angabe des Getriebefaktors |
1328 |
Mechnical form of output |
1329 |
最大次数 |
1330 |
实际运行次数的最大值。 |
1331 |
> 极限次数/每小时 |
1332 |
每小时电机启动次数的极限值。 |
1333 |
就地自保持模式 |
1334 |
如果参数选择允许,就地操作为自保持模式。 |
1335 |
语言 |
1336 |
设定显示的语言 |
1337 |
德语 |
1338 |
英语 |
1339 |
载入语言 |
1340 |
LCD背景灯延时 |
1341 |
设置没有按钮按下时,背景灯熄灭的时间。 |
1342 |
自动退出 |
1343 |
设定是否自动退出以及如何自动退出。 |
1344 |
禁止 |
1345 |
延时退出 |
1346 |
菜单退出 |
1347 |
退出延时 |
1348 |
设定完成自动退出的时间。 |
1349 |
PC接口 |
1350 |
该参数可以禁止红外接口 |
1351 |
禁止 |
1352 |
允许 |
1353 |
实际制式周期值 |
1354 |
最近1个小时电机得电时间。 该值连续更新。 |
1355 |
最大制式周期 |
1356 |
1个小时电机得电最长时间。 |
1357 |
运行指示 |
1358 |
0 = 禁止 (开/关LED在末端位指示) 1 = 单闪 (开/关LED在执行器对应方向运行时闪烁,对应末端位常亮) 2 = 双闪 (开/关LED 在执行器运行时同时闪烁,对应末端位常亮) 3 = 双常亮 (开/关LED在执行器运行时同时常亮,对应末端位常亮) |
1359 |
单闪 |
1360 |
双闪 |
1361 |
双常亮 |
1362 |
末端位延时 |
1363 |
设定执行器能够以电机的breakdown(破坏)力矩且无过力矩信号条件下,离开末端位置的时间。 |
1364 |
中间位延时 |
1365 |
设定执行器离开中间位置时,禁止力矩检测的时间。 |
1366 |
行程输出 |
1367 |
定义如何显示行程: -“无限制”,行程显示不受全关和全开范围的限制。 (见数据记录->上限值, 下限值) -“限制”,行程显示限制在全关和全开范围内。 |
1368 |
无限制 |
1369 |
限制 |
1370 |
增强型控制器 |
1371 |
禁止 |
1372 |
允许 |
1373 |
关运行监控时间 |
1374 |
设定从全开到全关位置所不能超过的运行时间。 一旦当前的运行时间超出该值,就输出行时间监控信号。 如果值为0,监控被禁止。 |
1375 |
开运行监控时间 |
1376 |
设定从全关到全开位置所不能超过的运行时间。 一旦当前的运行时间超出该值,就输出行时间监控信号。 如果值为0,监控被禁止。 |
1377 |
最大开力矩 |
1378 |
阀门或减速箱开方向最大允许力矩, 0代表无限制。 |
1379 |
最大关力矩 |
1380 |
阀门或减速箱关方向最大允许力矩,0代表无限制。 |
1381 |
相序 |
1382 |
有关输入电源的信息 |
1383 |
故障 |
1384 |
CW 检测 |
1385 |
CCW 检测 |
1386 |
CW 手动 |
1387 |
CCW 手动 |
1388 |
检测进行中 |
1389 |
相 1 |
1390 |
显示L1相状态. 下一次动作或故障确认后,输出复位。 |
1391 |
故障 |
1392 |
正常 |
1393 |
禁止检测 |
1394 |
相 2 |
1395 |
显示L2相状态. 下一次动作或故障确认后,输出复位。 |
1396 |
相 3 |
1397 |
显示L3相状态. 下一次动作或故障确认后,输出复位。 |
1398 |
内部24V |
1399 |
显示由主电源提供的24V状态 |
1400 |
外部24V |
1401 |
显示外部24V状态 |
1402 |
电子单元温度 |
1403 |
显示电子单元温度 |
1404 |
温度校正值 |
1405 |
定义测量值和环境温度的差值。如,设为10°C, 环境温度比测量温度低10°C。 |
1406 |
NV-存储器故障 |
1407 |
在启动过程显示非挥发存储器是否有故障 |
1408 |
否 |
1409 |
是 |
1410 |
与接口板的通讯是否正常信息 |
1411 |
EM6故障代码 |
1412 |
在自动进行的自诊断期间,控制单元检查复合传感器(Em6)。 在有故障时,输出“组合传感器故障”指示。 该参数说明检测到何种故障。 EM6检测分几步,生成不同的故障代码组。 在与EM6常规通讯期间的故障: 101-与远程EM6无通讯可能 102-与远程EM6无通讯可能 103-与远程EM6无通讯可能 104-与远程EM6无通讯可能 105-与远程EM6无通讯可能 106-参考电压无效 107-与远程EM6通讯丢失 108-参考电压不在有效 109-与EM6通讯产生严重错误 复合传感器EM6的非挥发存储器以固定间隔检测。 检测的故障代码如下: 1-序列号读故障 2-角偏移量读故障 3-模拟量的校准因子读故障 4-关方向读故障 5-力矩值读故障 6-LEARN值读故障 7-检查和标记读故障 带分体安装控制单元故障: 11-序列号读故障 12-Dim-06板序列号读故障 13-Dim-06板部件号读故障 14-关方向读故障 15-力矩值读故障 16-LEARN值读故障 |
1413 |
显示方向 |
1414 |
选定显示内容为正常或翻转180度。 |
1415 |
正常 |
1416 |
翻转 |
1417 |
回差输出 |
1418 |
力矩监控延时 |
1419 |
设定力矩测量中滤除峰值的周期,该时间内执行器不会过力矩关断。范围0…2000ms,,缺省值为0ms |
1420 |
限制为最大力矩 |
1421 |
如果允许,执行器在力矩监控延时期间监控最大可调力矩,如果禁止,执行器以堵转力矩运行。 |
1422 |
紧急关闭(ESD) |
1423 |
设定ESD功能。 如果允许,执行器运行到指定的末端位置。 |
1424 |
0% 全关 |
1425 |
100% 全开 |
1426 |
紧急关断 (ESD) |
1427 |
紧急关断指令的状态信息. 允许: 需要外部紧急关断. 禁止: 不需要外部紧急关断. |
1428 |
禁止 |
1429 |
允许 |
1430 |
选择忽略,即使电机超温,执行器也将运行到指定末端位置。 对防爆执行器,必需设定为“优先”。 注意:参数“忽略”可能导致设备损坏和人身伤害! |
1431 |
优先 |
1432 |
忽略 |
1433 |
过力矩 |
1434 |
该参数选择在有效外部ESD指令期间,力矩监控特性。 “优先”: 力矩监控正常操作。如果执行器在中间位置过力矩,执行器将停止并输出故障信号。 “忽略”: 在外部ESD有效时,禁止力矩监控,执行器将运行到指定位置。 这将使执行器以堵转力矩运行,如果执行器在相应方向设置为力矩关断, 执行器在末端位置将不会停止。必需设定为末端位置优先。 “末端位置优先”: 在ESD有效期间,中间位置禁止力矩监控,末端位置力矩监控有效。 |
1435 |
优先 |
1436 |
末端位优先 |
1437 |
就地模式 |
1438 |
选择忽略,即使执行器处于就地模式,执行器也将运行。 注意:参数“忽略” 可能导致设备损坏和人身伤害! |
1439 |
零位模式 |
1440 |
选择忽略,即使执行器处于零位模式,执行器也将运行。 注意:参数“忽略”可能导致设备损坏和人身伤害! |
1441 |
执行器运行监控 |
1442 |
如果允许,检查在电机得电时位置是否改变。 通过向相反方向运行或故障确认,复位指示。 |
1443 |
运行监控延时 |
1444 |
设定参数“驱动启动监控”的时间。 如果到了该时间,行程没有明显变化, 就激活“驱动启动监控”信号。 |
1445 |
反向延时 |
1446 |
定义反向运行的时间间隔。 |
1447 |
功率单元 |
1448 |
设置使用的功率控制单元类型。 对标准接触器单元或固态继电器,选择标准。 对所有pole disconnecting固态继电器,则选择ATEX。 |
1449 |
标准 |
1450 |
ATEX |
1451 |
开LED颜色 |
1452 |
兰 |
1453 |
绿 |
1454 |
红 |
1455 |
黄 |
1456 |
橘黄 |
1457 |
青 |
1458 |
粉红 |
1459 |
白 |
1460 |
开过力矩LED颜色 |
1461 |
故障LED颜色 |
1462 |
关过力矩LED颜色 |
1463 |
关LED颜色 |
1464 |
力矩关断最长时间 |
1465 |
力矩关断最长时间,范围0...60s |
1466 |
位置指示 |
1467 |
0 = 末端位亮 (对应末端位常亮) 1 = 中间和末端位亮 (开/关LED在执行器任何中间位常亮,对应末端位常亮) 2 = 中间亮/末端灭 (开/关LED在执行器任何中间位常亮,对应末端位灭) |
1468 |
末端位亮 |
1469 |
中间和末端位亮 |
1470 |
中间亮/末端灭 |
1471 |
德语 |
1472 |
英语 |
1473 |
中文 |
1474 |
西班牙语 |
1475 |
意大利语 |
1476 |
荷兰语 |
1477 |
波兰语 |
1478 |
俄语 |
1479 |
接口板 |
1480 |
该参数指示是否安装了接口板(如现场总线接口板)。 检测到接口板,参数值为'有'。 如果移除接口板,参数必需手动设置为'无'。 |
1481 |
无 |
1482 |
有 |
1483 |
位置输出 |
1484 |
选择行程如何输出: - 无限制,行程不受限于全关到全开范围。 (见数据记录->上限值,下限值) -限制,显示位置限制在全关和全开之间。 |
1485 |
到主站数据 |
1486 |
以16进制显示传送到主站的报文.参照总线执行器操作手册. |
1487 |
来自主站数据 |
1488 |
以16进制显示从主站接收的报文.参照总线执行器操作手册. |
1489 |
波特率 |
1490 |
现场总线接口实际传输速率 |
1491 |
接口类型 |
1492 |
接口卡类型信息 |
1493 |
无 |
1494 |
继电器 |
1495 |
Profibus |
1496 |
RS485 |
1497 |
Profibus |
1498 |
FF总线 |
1499 |
NA 6 |
1500 |
NA 7 |
1501 |
DeviceNet 1CH |
1502 |
DeviceNet 2CH |
1503 |
NA 10 |
1504 |
NA 11 |
1505 |
NA 12 |
1506 |
NA 13 |
1507 |
NA 14 |
1508 |
HART |
1509 |
NA 16 |
1510 |
Modbus |
1511 |
地址 |
1512 |
Shows the actual adress of the actuator. |
1513 |
RTC Enabled |
1514 |
Activation and deactivation of the real time clock |
1515 |
时间 |
1516 |
日期 |
1517 |
DST |
1518 |
手动 |
1519 |
自动 |
1520 |
时区 GMT |
1521 |
时间格式 |
1522 |
12h |
1523 |
24h |
1524 |
日期格式 |
1525 |
DD.MM.YYYY |
1526 |
YYYY-MM-DD |
1527 |
MM-DD-YYYY |
1528 |
显示时间 |
1529 |
总线时间同步 |
1530 |
装入工厂设定 |
1531 |
将装入工厂设定 |
1532 |
存储为工厂设定 |
1533 |
存储设定值为工厂设定。 |
1534 |
输出O1 |
1535 |
选择输出代表的功能。 |
1536 |
禁止 |
1537 |
末端位 |
1538 |
全关 |
1539 |
全开 |
1540 |
全关...中间位置1 |
1541 |
中间位置...全开 |
1542 |
运行-常亮 |
1543 |
运行-闪烁 |
1544 |
正在关-常亮 |
1545 |
正在关-闪烁 |
1546 |
正在开-常亮 |
1547 |
正在开-闪烁 |
1548 |
执行器没有启动 |
1549 |
过力矩 |
1550 |
关方向过力矩 |
1551 |
开方向过力矩 |
1552 |
力矩报警 |
1553 |
综合故障1 |
1554 |
综合故障2 |
1555 |
电机超温 |
1556 |
远程控制 |
1557 |
零位 |
1558 |
就地控制 |
1559 |
ESD有效 |
1560 |
组合传感器故障 |
1561 |
内部定位器无效 |
1562 |
需要维护 |
1563 |
非远程模式 |
1564 |
手轮操作 |
1565 |
系统故障 |
1566 |
中间位置 1 |
1567 |
中间位置 2 |
1568 |
中间位置 3 |
1569 |
中间位置 4 |
1570 |
中间位置 5 |
1571 |
中间位置 6 |
1572 |
中间位置 7 |
1573 |
中间位置 8 |
1574 |
总线 DOUT1 |
1575 |
总线 DOUT2 |
1576 |
总线 DOUT3 |
1577 |
总线 DOUT4 |
1578 |
PVST 有效 |
1579 |
PVST 错误 |
1580 |
PVST 放弃 |
1581 |
紧急-停止 |
1582 |
输出O2 |
1583 |
关方向过力矩 |
1584 |
开方向过力矩 |
1585 |
电机超温 |
1586 |
内部定位器无效 |
1587 |
输出O3 |
1588 |
综合故障1 |
1589 |
综合故障2 |
1590 |
内部定位器无效 |
1591 |
输出O4 |
1592 |
输出O5 |
1593 |
输出O6 |
1594 |
输出O7 |
1595 |
输出O1逻辑 |
1596 |
输出信号通常为常开(NO)接点。 如果选择常闭(NC)接点,继电器在输出无效时得电,且在输出有效时断电。 如果电源故障,继电器接点释放,输出为有效信号。 |
1597 |
NO接点 |
1598 |
NC接点 |
1599 |
输出O2逻辑 |
1600 |
输出O3逻辑 |
1601 |
输出O4逻辑 |
1602 |
输出O5逻辑 |
1603 |
输出O6逻辑 |
1604 |
输出O7逻辑 |
1605 |
死区时间 |
1606 |
定义开关量指令输入有效的最小脉冲时间。 |
1607 |
指令输入1 |
1608 |
定义指令输入功能. |
1609 |
停 |
1610 |
关 |
1611 |
开 |
1612 |
自动 |
1613 |
紧急关断(ESD) |
1614 |
步进模式有效 |
1615 |
允许就地 |
1616 |
允许远程 |
1617 |
允许关 |
1618 |
允许开 |
1619 |
故障确认 |
1620 |
强制就地 |
1621 |
强制就地停 |
1622 |
强制就地关 |
1623 |
强制就地开 |
1624 |
执行 PVST |
1625 |
指令输入2 |
1626 |
指令输入3 |
1627 |
指令输入4 |
1628 |
输入1逻辑 |
1629 |
定义指令是 24 V DC有效 (高有效)还是 0 V 有效(低有效). |
1630 |
高有效 |
1631 |
低有效 |
1632 |
输入2逻辑 |
1633 |
输入3逻辑 |
1634 |
输入4逻辑 |
1635 |
模拟输出1 |
1636 |
选择做为模拟输出1的4...20mA输出的信号. |
1637 |
位置 |
1638 |
电子单元温度 |
1639 |
现场总线 AOUT1 |
1640 |
Current Flow |
1641 |
Indicates if the connection type is 'Actuator' and a current source (Low Impedance) is detected, or when the connection type is 'Current Output' a current sink (High Impedance) is detected. If no current signal is detected, the value 0 (No Impedance) is reported. |
1642 |
No Impedance |
1643 |
Low Impedance |
1644 |
High Impedance |
1645 |
Device Conn. Type |
1646 |
Defines the Device Connection Type of the actuator. The default value of the DREHMO actuator is the type: Actuator. The following type exists: 0 = Not defined 1 = Current Input 2 = Current Output 3 = Voltage Input 4 = Voltage Output 5 = Secondary 6 = Transmitter 7 = Actuator 8 = Non-DC Isolated Bus Device 9 = DC Isolated Bus Device |
1647 |
Not defined |
1648 |
Current Input |
1649 |
Current Output |
1650 |
Voltage Input |
1651 |
Voltage Output |
1652 |
Secondary |
1653 |
Transmitter |
1654 |
Actuator |
1655 |
Non-DC Iso Bus Dev |
1656 |
DC Iso Bus Dev |
1657 |
AnaIn Current Zero |
1658 |
Reference value for 4 mA, which is used for calculation of the loop current (trimming) from the physical input signal. |
1659 |
AnaIn Current Span |
1660 |
Reference value for 20 mA, which is used for the calculation of the loop current (trimming) of the physical input signal. |
1661 |
AnaOut Current Zero |
1662 |
Reference value for 4 mA, which is used for the correction (trimming) the internal loop current from the generated physical output signal. |
1663 |
AnaOut Current Span |
1664 |
Reference value for 20 mA, which is used for the correction (trimming) of the internal loop current from the generated physical output signal. |
1665 |
AnaIn LRV |
1666 |
With this function it is possible to set the range of the input current between -250% and +250%. |
1667 |
AnaIn URV |
1668 |
AnaOut LRV |
1669 |
AnaOut URV |
1670 |
With this function it is possible to set the range of the input current between -250% and +250%. |
1671 |
Polling Address |
1672 |
标识所有设备的唯一地址,地址范围0到64。 |
1673 |
Loop Current Mode |
1674 |
In Low Impedance Mode and 'Loop Current Mode'= Enabled (Defaultvalue) should the actuator drive by analog inputsignal. When parameter 'Loop Current Mode'= Disabled the actuator drives with the HART commands OPEN, CLOSE, SETPOINT. The parameter defines, if analog signal will be used or not. |
1675 |
Disabled |
1676 |
Enabled |
1677 |
总线有效超时时间 |
1678 |
总线有效超时时间必需设置在1到3600秒之间(缺省值: 15秒)。 |
1679 |
APP FW-Version |
1680 |
Firmware version of LPT-Application from HART-Board. |
1681 |
堆栈固件版本 |
1682 |
HART堆栈固件版本. |
1683 |
IAP FW-Version |
1684 |
Firmware version of STM-Application (In-Application Program IAP) from HART-Board. |
1685 |
Manufacturer ID |
1686 |
Indicates the company that produced the device. Manufacturer Ids are allocated by the HART Communication Foundation. Only the designated manufacturer may use this ID. |
1687 |
Expanded Device Type |
1688 |
Indicates the type of the device (i.e., the product name). The 'Expanded Device Type' indicates the set of commands and data items supported by the Field Device. |
1689 |
Device ID |
1690 |
A number unique to a particular field device. This number must be different for every device produced with a given Device Type. |
1691 |
Device Revision Level |
1692 |
A whole Number indicating the revision level of command and data item set for this Device Type. |
1693 |
Software Revision Level |
1694 |
无符号整数指示现场设备的固件版本。现场设备的固件版本升级必需要更高版本。 |
1695 |
硬件版本等级 |
1696 |
无符号整数指示现场设备的硬件版本。 |
1697 |
Protocol Major Rev. Nr. |
1698 |
The HART Stack is kompatible with Protocol Revision 7.4 (Major Revision 7). |
1699 |
Identity Tag |
1700 |
An 8-character label assigned by the end user based on location and use of the field device. The Tag supports only the Packed ASCII character set. |
1701 |
Long Tag |
1702 |
A 32-character label assigned by the end user based on location and use of the field device. The Long Tag supports ISO Latin-1 characters from DCS. |
1703 |
Message |
1704 |
During commissioning the configurator write a message into the device for documentation. This process called 'As Installed Record Keeping'. |
1705 |
Date Code |
1706 |
Describe a date code, which only will be written by DCS-System. |
1707 |
Descriptor |
1708 |
Describe a 16 Byte Device Description value in ASCII format. Via HART will 12 Byte communicated in ASCII Packet format. |
1709 |
Final Assembly Nr |
1710 |
The Final Assembly Number is a 24-bit number (0...16.777.215) and will be used for administration of the device in the plant. |
1711 |
请求信息的前导码数 |
1712 |
主站到从站的请求信息要求的前导码最小数。 |
1713 |
响应信息的前导码数 |
1714 |
从站到主站的响应信息要求的前导码最小数。 |
1715 |
配置改变计数器 |
1716 |
The Configuration Change Counter must be incremented once for every command received thath changes the device configuration. The counter must also be incremented once for every user action that changes the device's configuration or calibration (e.g., from local operator interface). This value is never reset or written and must be maintained even if power is removed from the device or a device reset is performed. |
1717 |
Config. Changed Bit PM |
1718 |
If Configuration Change Counter has been incremented, then the Configuration Changed Bit for Primary Master (PM) will be set. |
1719 |
Config. Changed Bit SM |
1720 |
If Configuration Change Counter has been incremented, then the Configuration Changed Bit for Secondary Master (SM) will be set. |
1721 |
Wireless HART Adapter |
1722 |
If the parameter 'WirelessHART Adapter' is set to value 0 (Disabled), the power supply of 24V for the wireless adapter will be interrupted. Otherwise the voltage is provided when the system is ready for operation. |
1723 |
CurrentOut Resistor |
1724 |
If the parameter 'Current Out Resistor' has the value 0 (Disabled) the additional resistor is disabled by the switch S2 on the HART module. Otherwise it is enabled. |
1725 |
OFF mode |
1726 |
The actuator is in the OFF mode. The drive can not motor-driven. ATTENTION: Special rules may optionally be configured for fail-safe functions and ESD! |
1727 |
LOCAL mode |
1728 |
The acutator is in local mode. The actuator can be operated locally. The local method can be locked of remote DCS. Special arrangements may optionally be configured for fail-safe functions and ESD! |
1729 |
REMOTE mode |
1730 |
The actuator is in the REMOTE mode and can not be moved by DCS. |
1731 |
Mode not REMOTE |
1732 |
The actuator is not in mode REMOTE. |
1733 |
LEARN mode |
1734 |
The actuator is in LEARN mode. The actuator can be operated locally. The sensor calibration for the limit and torque detection can be performed. The local mode can be locked by a remote DCS. The fail-safe and ESD mechanisms are not available in this mode! For this mode, there are different access rights. |
1735 |
Service active |
1736 |
Future Use !!! At AUMA: For operation via service interface (Bluetooth) and service software AUMA Tool Suite. |
1737 |
Actuator running |
1738 |
The power unit of the drive is actuated. |
1739 |
Actuator running OPEN |
1740 |
The power unit of the drive is actuated in direction OPEN. |
1741 |
Actuator running CLOSE |
1742 |
The power unit of the drive is actuated in direction CLOSE. |
1743 |
Stepmode active |
1744 |
A stepmode is parameterized in direction OPEN or CLOSE and the following condition is also given: The process parameters 'clock source' is ' internal', or the process parameters 'clock source' is set to external and remote command 'clock mode active' is set. |
1745 |
Actuator in Stepmode |
1746 |
The actuator is in the range in which the stepmode is active. |
1747 |
Stepbreak active |
1748 |
The actuator stopped during stepmode operation. |
1749 |
The predefined setpoint is reached. |
1750 |
Limit Switch OPEN |
1751 |
The actuator is in a position outside the working range or not on position OPEN. |
1752 |
Limit Switch CLOSE |
1753 |
The actuator is in a position outside the working range or not on position CLOSE. |
1754 |
Limit reached |
1755 |
The actuator is in a position outside the working range or not on position OPEN and CLOSE. |
1756 |
Signal Limit OPEN |
1757 |
Signals the end position OPEN according to the setting of the 'end position'. Forms: 'travel position' or 'Switching off mode'. |
1758 |
Signal Limit CLOSE |
1759 |
Signals the end position CLOSE according to the setting of the 'end position'. Forms: 'travel position' or 'Switching off mode'. |
1760 |
Limit OPEN |
1761 |
Final position for OPEN, depends on the parameterized direction. With configured shutdown via limit switch this signal indicates when the endposition is exceeded. With configured torque shutdown the signal indicates the end position only if the tripping torque in direction OPEN is exceeded. |
1762 |
Limit CLOSE |
1763 |
Final position for CLOSE, depends on the parameterized direction. With configured shutdown via limit switch this signal indicates when the endposition is exceeded. With configured torque shutdown the signal indicates the end position only if the tripping torque in direction CLOSE is exceeded. |
1764 |
Torque OPEN |
1765 |
The torque measurement provides a value that is greater than the parameterized tripping torque OPEN. The signal is independent of other parameterizations. |
1766 |
Torque CLOSE |
1767 |
The torque measurement provides a value that is greater than the parameterized tripping torque CLOSE. The signal is independent of other parameterizations. |
1768 |
Signal Torque OPEN |
1769 |
The torque measurement provides a value that is greater than the parameterized tripping torque OPEN. The signal is indicated always in intermediate positions and only in final position, when the parameter 'torque indication' has the value 'Ind. in final positions'. |
1770 |
Signal Torque CLOSE |
1771 |
The torque measurement provides a value that is greater than the parameterized tripping torque CLOSE. The signal is indicated always in intermediate positions and only in final position, when the parameter 'torque indication' has the value 'Ind. in final positions'. |
1772 |
Signal Torque |
1773 |
Or function of the signals 'Signal Torque OPEN' and 'Signal Torque CLOSE'. |
1774 |
Torque failure OPEN |
1775 |
The torque measurement provides a value that is greater than the parameterized tripping torque OPEN. The signal is indicated always in intermediate positions and only in final position, when the parameter 'Switching off mode' has the value 'Final position limit sw.'. |
1776 |
Torque failure CLOSE |
1777 |
The torque measurement provides a value that is greater than the parameterized tripping torque CLOSE. The signal is indicated always in intermediate positions and only in final position, when the parameter 'Switching off mode' has the value 'Final position limit sw.'. |
1778 |
Torque failure |
1779 |
Or function of the signals 'Torque failure OPEN' and 'Torque failure CLOSE'. |
1780 |
Torque warning OPEN |
1781 |
The torque measurement provides a value that is greater than the configured warning torque OPEN. The signal is independent of other parameterizations. |
1782 |
Torque warning CLOSE |
1783 |
The torque measurement provides a value that is greater than the configured warning torque CLOSE. The signal is independent of other parameterizations. |
1784 |
Torque warning |
1785 |
Or function of the signals 'Torque warning OPEN' and 'Torque warning CLOSE'. |
1786 |
Signal torque warning OPEN |
1787 |
The torque measurement provides a value that is greater than the configured warning torque OPEN. The torque measurement provides a value that is greater than the configured warning torque OPEN. The signal is indicated always in intermediate positions and only in final position, when the parameter 'Switching off mode' has the value 'Final position limit sw.'. |
1788 |
Signal torque warning CLOSE |
1789 |
The torque measurement provides a value that is greater than the configured warning torque CLOSE. The torque measurement provides a value that is greater than the configured warning torque CLOSE. The signal is indicated always in intermediate positions and only in final position, when the parameter 'Switching off mode' has the value 'Final position limit sw.'. |
1790 |
Signal torque warning |
1791 |
Or function of the signals 'Signal torque warning OPEN' and 'Signal torque warning CLOSE'. |
1792 |
Device OK |
1793 |
Future Use |
1794 |
Emerg. shutdown (ESD) |
1795 |
An external ESD command is active and the currently configured ESD action is active. The execution of the ESD action is not blocked by a potentially operating mode, nor by a potentially motor overtemperature. |
1796 |
Fail safe active |
1797 |
The actuator is in internally generated state Fail-safe. This is only set in the mode REMOTE, when the external setpoint falls below a threshold value or the field communication failure have occured. |
1798 |
Emergency-STOP |
1799 |
Indicates an external Emergency-Stop signal. |
1800 |
Int. positioner disabled |
1801 |
The actuator can be operated from REMOTE only with discrete commands. To activate the internal positioner the bit Automatic must be active. A local fault H1 (entry in Fault Register Book) is generated only when the signal is mapped into the collective fault 1. |
1802 |
Interlock LOKAL active |
1803 |
One of the signals 'Enable LOCAL', 'Enable LOCAL OPEN' or 'Enable LOCAL CLOSE' is assigned to a command input and inactive. Drive the actuator in operating mode LOCAL is limited. |
1804 |
Interlock REMOTE active |
1805 |
One of the signals 'Enable REMOTE', 'Enable REMOTE OPEN' or 'Enable REMOTE CLOSE' is assigned to a command input and inactive. Drive the actuator in operating mode REMOTE is limited. |
1806 |
Handwheel operation |
1807 |
An actuator movement without activation of the power unit but with handwheel operation is present. |
1808 |
Acutator in LOCAL mode |
1809 |
The actuator is in LOCAL mode and the power unit is used. |
1810 |
Acutator in LOCAL mode OPEN |
1811 |
The actuator is in LOCAL mode and the power unit is used in direction OPEN. |
1812 |
Acutator in LOCAL mode CLOSE |
1813 |
The actuator is in LOCAL mode and the power unit is used in direction CLOSE. |
1814 |
Drives from REMOTE |
1815 |
The actuator is in the REMOTE mode and the power unit is active. |
1816 |
Local STOP |
1817 |
Find Device |
1818 |
Singals that the actuator is in a mode, which response all broadcast messages with it own device id. |
1819 |
Intermediate position 1 |
1820 |
Indication of the intermediate position according to the adjusted signal behavior. |
1821 |
Intermediate position 2 |
1822 |
Intermediate position 3 |
1823 |
Intermediate position 4 |
1824 |
Intermediate position 5 |
1825 |
Intermediate position 6 |
1826 |
Intermediate position 7 |
1827 |
Intermediate position 8 |
1828 |
Actual position |
1829 |
Actual actuator position in the range 0 ... 10000 (Format: Integer), scaled between the educated final positions CLOSE and OPEN. With the parameter 'Position output' from the Addon-Card it is possible to set the format form the actual position. The values from 'Position output' are 'Limited' or 'Over-/underflow'. Different from the other analog values is the scaling to the special applications (sealing gap control, etc.). |
1830 |
Torque actual value |
1831 |
Get the actual value of torque at the output. The format of the value is percent of the acutator's nominal torque (0% - 100%). |
1832 |
Delay run monitoring |
1833 |
The controll unit of the actuator does not register any movement despite activation of the power unit. |
1834 |
Rotation monitoring |
1835 |
The control of the actuator's power unit registers a movement in the wrong direction. |
1836 |
Op-time survey |
1837 |
Or function of the signals 'Op-time survey OPEN' and 'Op-time survey CLOSE'. |
1838 |
Op-time survey OPEN |
1839 |
The operating data for the current operating time survey in direction OPEN exceeds the configured valve limit. |
1840 |
Op-time survey CLOSE |
1841 |
The operating data for the current operating time survey in direction CLOSE exceeds the configured valve limit. |
1842 |
Overtemperatur trip |
1843 |
The motor protection trips by motor overtemperature. The release may be delayed due the actuator parameter 'Thermal failure delay'. To reset the behavior set the parameter 'Thermal failure reset'. |
1844 |
Collective failure 1 |
1845 |
The 'Collective failure 1' can collect different signals with OR-functions. There appears an exclamation point as warning on LCD. This indication is self-resetting. |
1846 |
Collective failure 2 |
1847 |
The 'Collective failure 2' can collect different signals with OR-functions. There appears an exclamation point as warning on LCD. This indication is self-resetting. |
1848 |
Fahrbefehl abgewiesen |
1849 |
Occurs, if the command OPEN / CLOSE are excecute while setpoint and Automatic Bit are given in operating mode with internal positioner. |
1850 |
Configuration invalid |
1851 |
One or more of the following parameter settings are invalid: - The device key of the electronic name plate is invalid. - The torques specified on the device key are implausible. - The parameterized tripping torque OPEN exceeds the maximum input torque OPEN for the valve - The parameterized tripping torque CLOSE exceeds the maximum input torque CLOSE for the valve - The parameterized tripping torque CLOSE / OPEN exceeds the configured maximum input torque for gear / thrust unit. - In case of a Profibus the redundancy concept has been configured via DPV2 for the redundancy concept, although the required DPV2 functionality hasn't been enabled on the device key. |
1852 |
Device Key invalid |
1853 |
The parameterized device key in the electronic nameplate of the actuator control is invalid. |
1854 |
Discrepancy error |
1855 |
There is a discrepancy monitored between the electrical signals and the read-back signals in the hardware monitoring of the power unit. |
1856 |
Wrong power unit |
1857 |
A wrong power unit has been occured based on the evaluation of an hardware encoding as specified in the configuration. |
1858 |
RTC not set |
1859 |
Future Use |
1860 |
Torque of Gear / thrust unit |
1861 |
The parameterized Tripping torque OPEN / CLOSE exceeds the allowable input torque of the gear unit. |
1862 |
Torque valve OPEN |
1863 |
The parameterized tripping torque of the valve exceeds the allowed maximum torque OPEN. |
1864 |
Torque valve CLOSE |
1865 |
The parameterized tripping torque of the valve exceeds the allowed maximum torque CLOSE. |
1866 |
Hardware error |
1867 |
An error of hardware components has occurred and the hardware has been evaluated as a defect. |
1868 |
HW Interface error |
1869 |
An error of the interface module used has been occurred and it has been evaluated as defect. |
1870 |
Systemtesterror |
1871 |
During self-examination of the Hard.- and Software the contro unitl has detected an error and then performed a system reset. - The error indication can reset via slot 1, index 240 from REMOTE with a Profibus interface. The error type can read over the acyclic services 'System test error code' from slot 1, index 195. - The error message can LOCAL using the function System > Reset, or by an off-on switch cycle reset. The error type can be retrieved in local menu under the actual values / diagnosis. - This message is important for safety-related systems when the actuator must drive to a safe position due an pending error. |
1872 |
Sensor failure |
1873 |
During self-diagnosis of the combi sensor for position.- and torque sensing a fault has been detected, and the sensor has been defined as not working. Actuator movement is not possible and may be canceled. It tries out a new hardware configuration of the sensor to correct the error. The indication is self-resetting at troubleshooting. |
1874 |
Range overflow |
1875 |
At more than 1490 rotations of the hollow shaft, this signal enters. |
1876 |
Nomansland |
1877 |
Appears when the sensor position is below -50% or over +150%. |
1878 |
position calibration error |
1879 |
Error during calibration of the combi sensor. |
1880 |
Torque calibration error |
1881 |
Electronics overtemperature |
1882 |
The measured temperature on base board exceeds the 'max. electronics temperature'. |
1883 |
Battery module fault |
1884 |
An error in the optional battery module is present. More information available under actual values / diagnosis > Battery Backup. |
1885 |
NV-Memory error |
1886 |
An error occurred has occurred while accessing on the internal volatile memory . |
1887 |
Or function of the signals 'Phase 1 failure', 'Phase 2 failure' and 'Phase 3 failure'. |
1888 |
Phase 1 failure |
1889 |
Phase 1 of the power supply has failed. |
1890 |
Phase 2 failure |
1891 |
Phase 2 of the power supply has failed. |
1892 |
Phase 3 failure |
1893 |
Phase 2 of the power supply has failed. |
1894 |
Phase sequence failure |
1895 |
A phase sequence can not be detected automatically. |
1896 |
24V internal failure |
1897 |
The required AC voltage on the secondary side of the power transformer not present. The controller could be alternatively supplied via an external power supply. The control of reversing contactor units as a power unit is not possible due to the pending error. |
1898 |
24V external failure |
1899 |
The external 24V DC power supply is not connected. |
1900 |
Maintenance required |
1901 |
Collective message of various operating data counters and maintenance messages. This signal is present when one of the following limits are exceeded: - Limit valve stroke - Accum. operation cycles - Thermal aging - Mechanical aging |
1902 |
Limit valve stroke |
1903 |
The value of the operating data counter 'valve stroke' exceeds the associated configurable limit 'Limit valve stroke'. |
1904 |
Accum. operation cycles |
1905 |
The value of the operating data counter 'operation cycles' exceeds the associated configurable limit 'limit operation cycles'. |
1906 |
Actual op. cycles/h |
1907 |
The value of the operating data counter 'Actual op. cycles/h' exceeds the associated configurable limit 'Limit op. cycles/h'. |
1908 |
Dynamic maintenance |
1909 |
Or function of the signals 'mechanical aging' and 'thermal aging'. |
1910 |
Mechanical aging |
1911 |
The value for the mechanical aging exceeds the associated limit value for mechanical aging and activate the dynamic service message. |
1912 |
Thermal aging |
1913 |
The value for the thermal aging exceeds the associated limit for the thermal aging and activate the service message. |
1914 |
Dyn. Consumptionvar. |
1915 |
0..100% consumption of the collective confidence of the dynamic maintenance message. This variable indicates the highest relative consumption to the limit of thermal aging or mechanical aging. |
1916 |
Warning mains quality |
1917 |
Warning temperature |
1918 |
Warning humidity |
1919 |
Warning dew point |
1920 |
Warning vibration |
1921 |
Warning duty cycle value |
1922 |
Channel 1 activity |
1923 |
On channel 1 it has been valid data (baud rate found) detected of the connected fieldbus system. |
1924 |
Channel 2 activity |
1925 |
On channel 2 it has been valid data (baud rate found) detected of the connected fieldbus system. |
1926 |
Channel 1 DataEx |
1927 |
On channel 1 of the connected fieldbus is a validated data exchange with the host (data exchange). |
1928 |
Channel 2 DataEx |
1929 |
On channel 2 of the connected fieldbus is a validated data exchange with the host (data exchange). |
1930 |
Channel 1 active |
1931 |
Channel 1 of the connected fieldbus system is the active channel. The signals of this channel are used for remote control of the actuator. |
1932 |
Channel 2 active |
1933 |
Channel 2 of the connected fieldbus system is the active channel. The signals of this channel are used for remote control of the actuator. |
1934 |
CLEAR Channel 1 |
1935 |
All outputs of the hosts on the fieldbus channel 1 in the device (slave) are reset (Global Control Clear). |
1936 |
CLEAR Channel 2 |
1937 |
All outputs of the hosts on the fieldbus channel 2 in the device (slave) are reset (Global Control Clear). |
1938 |
AnaIn1 |
1939 |
0 ... 1000ppt the analog input 1, scaled between 4 ... 20 mA. |
1940 |
AnaIn2 |
1941 |
0 ... 1000ppt the analog input 2, scaled between 4 ... 20 mA |
1942 |
Dig. I/O Input 1 |
1943 |
Status of digital input 1. |
1944 |
Dig. I/O Input 2 |
1945 |
Status of digital input 2. |
1946 |
Dig. I/O Input 3 |
1947 |
Status of digital input 3. |
1948 |
Dig. I/O Input 4 |
1949 |
Status of digital input 4. |
1950 |
Dig. I/O Input 5 |
1951 |
Status of digital input 5. |
1952 |
Dig. I/O Input 6 |
1953 |
Status of digital input 6. |
1954 |
Status actual position |
1955 |
1 = ok, 0 = nok |
1956 |
Status AnaIn 1 |
1957 |
Status channel AnaIog Input 1. |
1958 |
Status AnaIn 2 |
1959 |
No setpoint available |
1960 |
It is not a valid setpoint for the internal positioner available. |
1961 |
Status Feldbus Channel 1 |
1962 |
Error state of the channel 1. |
1963 |
Status Feldbus Channel 1 |
1964 |
Error state of the channel 2. |
1965 |
Signal loss ParallelIfa AnaIn1 |
1966 |
Signal loss ParallelIfa AnaIn2 |
1967 |
PVST active |
1968 |
Future Use |
1969 |
PVST abort |
1970 |
PVST warning |
1971 |
Backflushing |
1972 |
Drives the actuator in direction OPEN when a discrete command from remote is released. It must be mode REMOTE active. If the type of the control is 'Int. positioner' and the parameter has the value 'Enabled V005', it must be reset the 'Automatic-bit'. The signal behavior can configured under menu item 'Control'. |
1973 |
Drives the actuator in direction CLOSE when a discrete command from remote is released. It must be mode REMOTE active. If the type of the control is 'Int. positioner' and the parameter has the value 'Enabled V005', it must be reset the 'Automatic-bit'. The signal behavior can configured under menu item 'Control'. |
1974 |
STOP |
1975 |
Stops the actuator when a discrete command from remote is released. It must be mode REMOTE active. If the type of the control is 'Int. positioner' and the parameter has the value 'Enabled V005', it must be reset the 'Automatic-bit'. The signal behavior can configured under menu item 'Control'. |
1976 |
automatic mode |
1977 |
Enables the integrated 3-point positioner, and allows driving the actuator via setpoint if the parameter 'Int. positioner' has the value 'Enabled V005'. |
1978 |
Stepping mode |
1979 |
Enables the step mode for extending the cycle time if the process parameters 'clock source' has the value 'External'. |
1980 |
Emergency Shutdown (ESD) |
1981 |
Enables Emergency shutdown 'ESD' of the actuator, if it is not deactivated by the control parameter 'Emergency shutdown ESD'. It is possible to enable the function in LOCAL or OFF mode by parameterization. The actuator's behavior for a possible torque or motor over-temperature shutdown can be parameterized. The control mode is always the 'Jog' even if 'Modal' is parameterized. For the ESD command is an enabled configured 'Edge detection REMOTE' inactive. This result change in a mode with different behavior as in the run command OPEN, CLOSE. |
1982 |
Activates the emergency STOP function. |
1983 |
Fieldbus enable REMOTE |
1984 |
Enable driving the actuator from REMOTE. |
1985 |
Fieldbus enable REMOTE OPEN |
1986 |
Enable driving the actuator from REMOTE in driection OPEN. |
1987 |
Fieldbus enable REMOTE CLOSE |
1988 |
Enable driving the actuator from REMOTE in driection CLOSE. |
1989 |
Fault acknowledge |
1990 |
Alternative reset mechanism for selected stored faults from REMOTE: - Reset command for a torque OPEN / CLOSE error instead of an acknowledge from a run command in opposite direction. - Reset command for a tripped 'Delay run monitoring error' instead of a new edge in the run command - Reset command for a tripped Phase 1, Phase 2 or Phase 3 error if the parameter 'phase failure monitoring' has not the value self-resetting. |
1991 |
Change fieldbus channel |
1992 |
Iin the case of an existing redundant fieldbus changes the connection with a pass from logic 0 to logic 1 the active channel, if a valid data exchange takes place on the other channel. |
1993 |
Partial Stroke |
1994 |
Default LOCAL |
1995 |
This signal allows an alternative REMOTE operation in a special mode 'Default LOCAL' via additional discrete commands 'Default LOCAL STOP', 'Default LOCAL CLOSE' and 'Default LOCAL OPEN'. The signals have only effects if the actuator is in the REMOTE mode and there is no blocking of the local operation. Because of an input signal changes the mode under these conditions to 'Default LOCAL'. The control over the discrete commands OPEN, CLOSE or setpoint are in REMOTE mode not possible as long as the signal is present. |
1996 |
Default LOCAL STOP |
1997 |
Stops the actuator, when control via the command 'Default LOCAL CLOSE' or 'Default LOCAL OPEN' is active in the 'Default LOCAL'. |
1998 |
Default LOCAL CLOSE |
1999 |
Drives the actuator in the mode 'Default LOCAL' in direction CLOSE. The command is usually performed in the jog-mode. If the command input has been configured as 'Default LOCAL STOP' works it with self-latching. |
2000 |
Default LOCAL OPEN |
2001 |
Drives the actuator in the mode 'Default LOCAL' in direction OPEN. The command is usually performed in the jog-mode. If the command input has been configured as 'Default LOCAL STOP' works it with self-latching. |
2002 |
Drive the actuator to the parameterized intermediate position via the internal positioner. |
2003 |
Setpoint value |
2004 |
0..1000ppt setpoint, scalled between end position CLOSED and OPEN. |
2005 |
Process actual value |
2006 |
Position value 0 ... 1000 ppt, scaled between end position CLOSED and AUF. Prozess actual value |
2007 |
Fieldbus AOUT |
2008 |
Transmitting an analog value from the DCS to the relay board of control. Scales in 0..1023 for 4-20mA. |
2009 |
Channel 1 active |
2010 |
Channel 1 active. |
2011 |
Channel 2 active. |
2012 |
Channel 1 DataEx |
2013 |
Dataexchange on channel 1. |
2014 |
Channel 2 DataEx |
2015 |
Dataexchange on channel 2. |
2016 |
Channel 1 Fail-State |
2017 |
Channel 1 fail-state fieldbus (0=OK; 1= fail-safe) |
2018 |
Channel 2 Fail-State |
2019 |
Channel 2 fail-state fieldbus (0=OK; 1= fail-safe) |
2020 |
Channel 1 Busactivity |
2021 |
Data transmission on channel 1. |
2022 |
Channel 2 Busactivity |
2023 |
Data transmission on channel 2. |
2024 |
Redundancy |
2025 |
The interface module has 2 channels (display in MMI). |
2026 |
Fail-safe |
2027 |
The interface module requests the state fail-safe. |
2028 |
Simulate |
2029 |
The actuator can be simulated via fieldbus (0 = OFF, 1 = ON). |
2030 |
DataEx Fieldbus |
2031 |
The fieldbus is in data exchange and receives valid telegrams from the control system. |
2032 |
Squawk |
2033 |
If Squawk message is indicated all LEDs without the Bluetooth LED are flashing on display board (iMC02). |
2034 |
Optical Fiber Error |
2035 |
A possibly installed fiber optic module reports a general error. |
2036 |
Optical Fiber Budget Channel 1 |
2037 |
Warning: FO cable system reserve reached (critical or permissible Rx receive level). |
2038 |
Optical Fiber Error Channel 1 |
2039 |
Optical receiving signal (no or insufficient Rx receive level) or RS-485 format error. |
2040 |
Optical Fiber Budget Channel 2 |
2041 |
Optical Fiber Error Channel 2 |
2042 |
Not ready remote |
2043 |
Signalisiert das der Antrieb nicht über Feldbus verfahren werden kann. Sammlemeldung aus den Bytes 12 und 13. |
2044 |
Signalisiert eine Warnung im Gerät. Sammelmeldung aus den Bytes 16, 17, 18 und 19. |
2045 |
Error |
2046 |
Signalisiert einen Fehler im Gerät. Sammelmeldung aus Bytes 14 und 15. |
2047 |
NAMUR Meldung 'Wartungsbedarf' ist gesetzt, wenn das Ausgangssignal zwar noch gültig ist, aber der Abnutzungsvorrat demnächst erschöpft oder aufgrund von Einsatzbedingungen eine Funktion in Kürze eingeschränkt sein, z. B. Alterung der pH-Elektrode. |
2048 |
Out of specification |
2049 |
NAMUR Meldung 'Außerhalb der Spezifikation' ist gesetzt, wenn vom Gerät durch Selbstüberwachung ermittelte Abweichungen von den zulässigen Umgebungs-, Prozessbedingungen oder Störungen im Gerät darauf hinweisen, dass die Sollwertabweichung bei Aktoren wahrscheinlich größer ist als wie unter den normalen Betriebsbedingungen. |
2050 |
function check |
2051 |
NAMUR Meldung 'Funktionskontrolle' ist gesetzt, wenn am Feldgerät gearbeitet wird, das Ausgangssignal ist daher vorübergehend ungültig (z.B. eingefroren). |
2052 |
Failure |
2053 |
NAMUR Meldung "Funktionskontrolle" ist gesetzt, wenn aufgrund einer Funktionsstörung im Feldgerät oder an seiner Peripherie das Ausgangssignal ungültig ist. |
2054 |
Zeigt an das kein Fehler im System ist |
2055 |
Wrong operation command |
2056 |
Falls z.B. AUF/ZU Befehl gleichzeitig im Betrieb als Fahrbefehl an den Antrieb weitergleitet werden. In der iMC handhaben die Busplatinen diese Logik und nicht die Basisplatine. |
2057 |
Antrieb ist nicht in Betriebsart FERN. |
2058 |
Interlock active |
2059 |
Verriegelt den Betrieb über Feldbus. |
2060 |
Der Antrieb wurde lokal gestoppt. |
2061 |
EMERGENCY stop active |
2062 |
Eine externe Not HALT Anforderung liegt am Antrieb an. |
2063 |
EMERGENCY shutdown |
2064 |
Ein externer ESD Befehl steht an und die aktuell parametrierte ESD Aktion ist aktiv, wobei die Ausführung der ESD Aktion weder durch eine möglicherweise ausschließende Betriebsart, noch durch eine möglicherweise ausschließende Motorübertemperatur blockiert ist. |
2065 |
Der Antrieb befindet sich im intern generierten Zustand Fail-safe. Dieser wird ausschließlich in der Betriebsart FERN, bei Unterschreitung eines Grenzwertes der externen Sollwertvorgabe oder bei Feldbuskommunikationsausfall, gesetzt. |
2066 |
I/O interface |
2067 |
Signalisiert das der Antrieb über die zusätzlich analogen oder digitalen Ein-/ausgänge betrieben wird. |
2068 |
Patrial Stroke Test Betrieb. |
2069 |
Wartung aktiv. |
2070 |
Handwheel active |
2071 |
Armatur wird per Handrad betätigt. |
2072 |
Configuration error |
2073 |
Fehlerhafte Einstellungen der PRM vorgenommen. |
2074 |
Mains quality |
2075 |
HW-Komponente als defekt erkannt |
2076 |
Motorschutz hat ausgelöst wegen Motorübertemperatur |
2077 |
Phase fault |
2078 |
Eine der drei Phasen ist ausgefallen |
2079 |
Torque fault OPEN |
2080 |
Torque fault CLOSE |
2081 |
Internal fault |
2082 |
Bei Selbstüberprüfung hat die Steuerung einen Fehler festgestellt, einen Reset durchgeführt und versucht den fail-safe einzunehmen |
2083 |
No reaction |
2084 |
Zustandsmeldung |
2085 |
Phase correction |
2086 |
Collective failure 1 |
2087 |
Sammelstörung 1 |
2088 |
Sensor defect |
2089 |
Kombisensor EM6 ist nicht funktionstüchtig |
2090 |
Incorrect phase sequence |
2091 |
Antrieb dreht richtig oder falsch herum. |
2092 |
Torque Wrn CLOSE |
2093 |
Torque Wrn OPEN |
2094 |
Wrn controls temperature |
2095 |
Kritische Temperatur in der Strg (Elektornik Übertemperatur) |
2096 |
Wrn gearbox temperature |
2097 |
Kiritische Temp. im Getriebe |
2098 |
Wrn motor temperature |
2099 |
Kritische Temperatur am Motor |
2100 |
24 V DC external |
2101 |
Externe Speisespannung liegt nicht an. |
2102 |
24 V DC internal |
2103 |
Elektronik wird nicht mehr aus Anschlussnetz versorgt. |
2104 |
Collective failure 2 |
2105 |
Sammelstörung 2. |
2106 |
Wrn RTC not set |
2107 |
Realtime Clock nicht gesetzt. |
2108 |
Konfiguration ungültig |
2109 |
Warning LWL budget |
2110 |
Warnung der Lichtstärke |
2111 |
Warning LWL circle |
2112 |
LWL Ring unterbrochen |
2113 |
Warning input AIN 1 |
2114 |
Warnung am analog Eingang. |
2115 |
Warning input AIN 2 |
2116 |
Warnung am analog Eingang |
2117 |
Internal warning |
2118 |
Analog zum internen Fehler gibt es auch eine interne Warnung. Überprüft wird der Systemtestfehler. |
2119 |
Wrn on time starts |
2120 |
Warnung bei den Anläufen. |
2121 |
Wrn on time running |
2122 |
Warnung bei der Laufzeit |
2123 |
Operation time warning |
2124 |
Stellzeit größer als die Zeit für Laufzeitüberwachung |
2125 |
Wrn setpoint position |
2126 |
Kein Sollwert vorhanden. |
2127 |
Failure behaviour active |
2128 |
Antrieb befindet sich im Modus fail save. |
2129 |
PVST fault |
2130 |
FAULT |
2131 |
Signalisiert einen Fehler im System |
2132 |
Maintenance necessary |
2133 |
Wartung erforderlich |
2134 |
Berechnet den Verschleiß der internen Getriebekomponenten. |
2135 |
Berechnet aus der gemessenen Elektroniktemperatur die Alterung der Dichtungselemente. |
2136 |
Valve stroke |
2137 |
Gibt den akkumulierten Armaturenweg als Vielfaches des Gesamthubes wieder (1 = vollständiger Hub). |
2138 |
Accumulated cycles |
2139 |
Gibt die Gesamtzahl der Betätigungen des Leistungsstellgliedes an. |
2140 |
Number of cycles per hour |
2141 |
Gibt die Anzahl der Schaltspiele während der letzten Stunde an. Der Wert wird laufend aktualisiert |
2142 |
Wrn 24 V external |
2143 |
Wrn mains quality |
2144 |
Wrn temperature |
2145 |
Wrn humidity |
2146 |
Wrn dew point |
2147 |
Wrn vibration |
2148 |
Wrn duty cycle value |
2149 |
Warnings |
2150 |
Signalisiert eine Warnung im System |
2151 |
State position actual value |
2152 |
State input AIN 1 |
2153 |
State input AIN 2 |
2154 |
Internal Poistioner disabled |
2155 |
Interlock LOCAL active |
2156 |
Configuration |
2157 |
Diagnostic data |
2158 |
Maintanance |
2159 |
Reset functions |
2160 |
Real-Time Clock |
2161 |
Variable 0, AI loop current |
2162 |
Variable 1, AO loop current |
2163 |
Variable 2, setpoint position |
2164 |
Variable 3, actual position |
2165 |
Variable 4, commands |
2166 |
Variable 5, reserved |
2167 |
Variable 6, discrete signal 1 |
2168 |
Variable 7, torque |
2169 |
Variable 8, discrete signal 2 |
2170 |
Variable 9, analog input 1 |
2171 |
Variable 10, analog input 2 |
2172 |
Variable 11, additional commands |
2173 |
Input |
2174 |
Operating modes |
2175 |
Operating messages |
2176 |
Actuator position |
2177 |
Torque overload |
2178 |
Torque warning |
2179 |
Device status |
2180 |
Intermediate positions |
2181 |
Actual position |
2182 |
Torque value |
2183 |
Actuator faults |
2184 |
General faults |
2185 |
Electronic fault messages |
2186 |
Maintenance messages |
2187 |
Dynamic maintenance |
2188 |
Bus communication |
2189 |
AnalogIn |
2190 |
DigitalIn |
2191 |
Diagnosis |
2192 |
Partial Stroke Test |
2193 |
Output |
2194 |
Commands |
2195 |
Release commands |
2196 |
Additional commands |
2197 |
Setpoint |
2198 |
Digital Outputs |
2199 |
Analog Output |
2200 |
Fieldbus State |
2201 |
LWL State |
2202 |
电子铭牌 |
2203 |
综合 |
2204 |
执行器 |
2205 |
控制单元 |
2206 |
基本信息 |
2207 |
部件信息 |
2208 |
选项 |
2209 |
电机 |
2210 |
减速箱/推力单元 |
2211 |
阀门 |
2212 |
运行数据 |
2213 |
综合 |
2214 |
运行数据 |
2215 |
动态维护 |
2216 |
故障次数统计 |
2217 |
系统数据 |
2218 |
实际值/自诊断 |
2219 |
历史故障记录 |
2220 |
过程数据 |
2221 |
电源 |
2222 |
系统 |
2223 |
接口 |
2224 |
综合信息 |
2225 |
HART |
2226 |
Version |
2227 |
Device Identification |
2228 |
Plant Identification |
2229 |
Communication State |
2230 |
参数 |
2231 |
电源 |
2232 |
显示单元 |
2233 |
Language |
2234 |
日期和时间 |
2235 |
LED |
2236 |
显示 |
2237 |
应用 |
2238 |
数据记录 |
2239 |
基本设定 |
2240 |
启动特性 |
2241 |
中间位置 |
2242 |
中心点 |
2243 |
回差 |
2244 |
信号特性 |
2245 |
监控 |
2246 |
DCS/PLC系统 |
2247 |
紧急关闭(ESD) |
2248 |
故障安全 |
2249 |
综合故障1 |
2250 |
综合故障2 |
2251 |
控制 |
2252 |
输出信号 |
2253 |
Plant Configuration |
2254 |
Comm. Config |
2255 |
Calibrat. values |
2256 |
继电器接口 |
2257 |
输出 |
2258 |
模拟输出 |
2259 |
指令输入 |
2260 |
其它 |
2261 |
基本设定 |
2262 |
过程 |
2263 |
调节特性 |
2264 |
步进模式 |
2265 |
工厂设定 |
2266 |
Read parameters from device... |
2267 |
Write parameters to device... |
2268 |
Wireless |
2269 |
WirelessHART Device |
2270 |
IEEE 802.15.4 2.4GHz DSSS with O-QPSK Modulation |
2271 |
Primary |
2272 |
Primary Analog Channel |
2273 |
Secondary Analog Channel |
2274 |
Tertiary |
2275 |
Tertiary Analog Channel |
2276 |
Quaternary |
2277 |
Quaternary Analog Channel |
2278 |
Quinary |
2279 |
Quinary Analog Channel |
2280 |
Lock all |
2281 |
Trim not supported |
2282 |
Configuration cannot be changed |
2283 |
Locked by gateway |
2284 |
Analog Input Channel |
2285 |
Analog Output Channel |
2286 |
The device is in simulation mode and the level output is not representative of the process. |
2287 |
The Non-Volatile memory check is invalid or maybe corrupt, or the battery of a battery-backed memory has failed. |
2288 |
The RAM memory check is invalid or maybe corrupt |
2289 |
A watchdog reset has been performed |
2290 |
Voltage conditions out of range |
2291 |
A voltage condition is outside its allowable range |
2292 |
An internal or environmental condition is beyond acceptable limits. |
2293 |
A hardware problem not related to the sensor has been detected. |
2294 |
The device was unable to acquire the communication bandwidth required to support the Burst Messaging specified |
2295 |
Battery life |
2296 |
Percent range |
2297 |
Loop current |
2298 |
Primary variable |
2299 |
Secondary variable |
2300 |
Tertiary variable |
2301 |
Quaternary variable |
2302 |
Read receive time |
2303 |
Write date and time |
2304 |
Non-Volatile Clock |
2305 |
When set the device contains a battery-backed clock. In this case, the clock does not need to be reset if there is a power failure. |
2306 |
Clock Uninitialized |
2307 |
The real-time clock has never been set with the date and time. For example, the clock is volatile and power was removed from and restored to the device. |
2308 |
None |
2309 |
No restrictions |
2310 |
SI Only |
2311 |
Restricted to SI Unit codes only |
2312 |
Process automation device |
2313 |
Discrete device |
2314 |
Hybrid:Process automation+discrete |
2315 |
I/O System |
2316 |
WirelessHART Process automation device |
2317 |
WirelessHART Discrete device |
2318 |
WirelessHART Process automation+discrete |
2319 |
WirelessHART Gateway |
2320 |
WirelessHART Access point |
2321 |
WirelessHART Process adapter |
2322 |
WirelessHART Discrete adapter |
2323 |
WirelessHART enabled handheld/portable maintenance tool |
2324 |
Device Profile |
2325 |
US |
2326 |
United States of America |
2327 |
JP |
2328 |
Japan |
2329 |
DE |
2330 |
Germany |
2331 |
FR |
2332 |
France |
2333 |
ES |
2334 |
Spain |
2335 |
RU |
2336 |
Russian Federation |
2337 |
CN |
2338 |
People's Republic of China |
2339 |
Secondary Master |
2340 |
Primary Master |
2341 |
Device Diagnostic Status 0 |
2342 |
Device Diagnostic Status 1 |
2343 |
I/O and Subdevice Status |
2344 |
WirelessHART Status |
2345 |
Time Set Option |
2346 |
Real Time Clock Flags |
2347 |
Country |
2348 |
Country of intended device installation |
2349 |
SI Unit Control |
2350 |
Indicates if device should only display SI unit codes |
2351 |
Time Stamp |
2352 |
Relative time value on network |
2353 |
8u |
2354 |
Dynamic Variables Returned for Device Variables |
2355 |
Command Response Truncated |
2356 |
Configuration Change Counter Mismatch |
2357 |
Status bytes mismatch |
2358 |
count |
2359 |
Device Variable |
2360 |
Current Date |
2361 |
Current Date based upon the real-time clock in the field device |
2362 |
Current Time |
2363 |
Current Time based upon the real-time clock in the field device |
2364 |
Set Clock Time |
2365 |
Time to set the real time clock in the field device to, or time that the real-time clock was last set |
2366 |
Set Clock Date |
2367 |
Date to set the real-time clock in the field device to, or date that the real-time clock was last set |
2368 |
Variable to trim |
2369 |
STX Count |
2370 |
Count of STX messages received by this device |
2371 |
ACK Count |
2372 |
Count of ACK messages received by this device |
2373 |
BACK Count |
2374 |
Count of BACK messages received by this device |
2375 |
Analog Channel Number |
2376 |
Analog Channel Number- Index into an array of Analog Channels. |
2377 |
Index 1 into Analog Channel Array |
2378 |
Index into Analog Channel Array- Is the first of an array of addresses, whose value is identified by the Analog Channel Code. |
2379 |
Index 2 into Analog Channel Array |
2380 |
Index into Analog Channel Array- Is the second of an array of addresses, whose value is identified by the Analog Channel Code. |
2381 |
Index 3 into Analog Channel Array |
2382 |
Index into Analog Channel Array- Is the third of an array of addresses, whose value is identified by the Analog Channel Code. |
2383 |
Index 4 into Analog Channel Array |
2384 |
Index into Analog Channel Array- Is the fourth of an array of addresses, whose value is identified by the Analog Channel Code. |
2385 |
Retrieve data for: %{PRM_9425} |
2386 |
ERROR: loading data failed! |
2387 |
Read device information |
2388 |
Read properties of %{PRM_9425} |
2389 |
Read data for curve in direction OPEN |
2390 |
Read data for curve in direction CLOSE |
2391 |
Accomplished! |